User Guide

F-27120-5 © Copyright 2008 TAC All Rights Reserved. 7
MF51-7203
MF61-7203
Red
Black
Common
Hot (+DC)
1
Line
Volts
Controller
Blue
2
Yellow/Black
Hot
Common
3
Green/Yellow
Extend
Retract
1 Provide overload protection and
disconnect as required.
2 Actuators may be wired in
parallel. All actuator black wires
are connected to the
transformer common and all
red wires are connected to the
hot lead. Power consumption
must be observed.
3 The Common connection from
the actuator must be connected
to the Hot connection of the
controller. The actuator Hot
must be connected to the
controller Common.
4 If the controller uses a full-
wave power supply and does
not provide isolated outputs, a
separate transformer is
required.
4
24 Vac Transformer
or 22-30 Vdc
Figure-4 Triac Sink.
Red
Black
Common
Hot (+DC)
Controller
3
2
Retract
Yellow/Black
1
Line
Volts
Hot
Common
Blue Extend
1
Line
Volts
Green/Yellow
MF51-7203
MF61-7203
1 Provide overload protection
and disconnect as required.
2 Actuators may be wired in
parallel. All actuator black
wires are connected to the
transformer common and all
red wires are connected to the
hot lead. Power consumption
must be observed.
3 The actuator Hot must be
connected to the controller
Common.
4 If the controller uses a full-
wave power supply and does
not provide isolated outputs, a
separate transformer is
required.
4
24 Vac Transformer
or 22-30 Vdc
24 Vac Transformer
or 22-30 Vdc
Figure-5 Triac Sink With Separate Transformers.