- 1. Disconnect air line to actuator.
- 1. Disconnect air line to actuator.
- 2. Rotate start point adjustment counterclockwise (as viewed from the bottom) to remove as much spring compression as possible.
- 3. Remove the four cover mounting screws, the top cover, and the diaphragm.
- 4. While holding down the piston with the heel of your hand, remove the connecting pin.
- 5. Slowly release pressure on piston and remove piston.
- 6. Remove spring and insert replacement.
- 7. Position piston over spring, making sure position indicator is aligned with guide.
- 8. Pushing down on piston, align holes in valve stem extension and piston shaft and insert connecting pin.
- 9. Position diaphragm and top cover on actuator and even secure with the four screws.
- 10. Refer to "ADJUSTMENTS" on page 4 and adjust start point of actuator to desired value.