User Guide

2 © Copyright 2008 TAC All Rights Reserved. F-15571-4
Figure-2 Mounting Thermostat to Electrical Box.
Figure-3 Mounting Thermostat to AT-506 or AT-508 Wall Box
Fitting.
PERFORMANCE
Air Consumption: .008 scim for sizing air compressor
(exception: .024 for TK-1601).
Supply in Pressure: See Performance table.
Air Capacity: 16 scim for sizing air mains (exception: 32 for
TK-1601).
Air Connection: 5/32 plastic tubing.
Table-1 Performance Table.
Part Number Description and Action *
Dial Range
(F)
Factory Setpoint
Setting (F)
Throttling Range
Supply Air
Pressure (psig)
TK-1001
Heating
DA
55.85 75
Adjustable
2 - 10F
o
/10 psi
Factory Set
4F
o
/10 psi
15 or 20
TK-1101
RA
Cooling
TK-1201
Heating-Cooling
DA - 20 psig
RA - 15 psig
15 - RA*
20 - DA*
TK-1301 Day-Night
DA
Night - 20 psig
Day - 15 psig
15 - Day
20 - Night
TK-1601
*Direct acting: Increases output pressure on temperature rise.
Reverse acting: Decreases output pressure on temperature rise.