Valves Products Catalog Make the most of your energy
General Information TAC TAC is a Schneider Electric Company with a long tradition of global leadership in building controls technology. We offer the most extensive line of controls and components available to today's market, including: valve bodies, valve assemblies, actuation devices and sensors, as well as interfaces, and automated systems that link these products and other building systems together.
Manufactured Parts Numbering System Primary Designation (First Letter) HS humidity sensor, electronic A Accessories HSP H Humidity humidity transmitter, electronic P Pressure S Switch or Step Controller V Valve C Controller or Controlled Device MA M Motor (Actuator) MC R Receiver-Controller or P.E.
Model Number Index Model Page Numerics 47XX ............................................134 500 .................................................92 A AE-504 .............35, 91, 110, 132, 156 AGXXXXXX ......................67, 68, 116 AHXXXXXX ......................67, 68, 116 AK-42039-500 .................................... 14 AK-42309-500 14, 22, 23, 51, 72, 78, ..........79, 80, 122, 123, 143, 147, 148 AL-1XX ..........16, 23, 61, 73, 80, 110, ..............................................
Model Number Index Model Page Model Page Model Page MC-351 .......................................... 37 MC-351, 4XX, 4XX1 .......................33 MC-371 ........................................160 MC-3XX ........................................155 MC-418-XXX ..................................87 MC-419-XXX ..................................87 MC-41X ........................................184 MC-41X1 ......................................184 MC-42 ............................................
Model Number Index Model Page MP-471-600 .32, 34, 87, 90, 132, 156 MP-471-691 3 ...................................4 MP-475 ....35, 91, 130, 132, 133, 134, ..............................154, 156, 158, 160 MP-47X ..............................32, 37, 87 MP-47XX ........................................32 MP-481 ...........................................37 MP-481-600 .32, 34, 87, 90, 132, 156 MP-481-691 ...................................34 MP-485 ..35, 59, 60, 61, 91, 108, 109, ............................
Model Number Index Model Page Model Page Model Page VA-7213-XXX-4-P ..........................42 VA-7215-2XX-4-P ........................126 VA-7215-XXX-4-P ..................42, 136 VA-7221-XXX-4-P ....................13, 14 VA-7222-XXX-4-P ..........................13 VA-7223-2XX-4-P ....................27, 28 VA-7223-XXX-4-P ..........................42 VA-7225-2XX-4-P ........................126 VA-7225-XXX-4-P ..................42, 136 VA-7225-XXX-4-P ........................136 VA-72X3 .........
Model Number Index Model Page VF-7215-25X-4-P ......................... 131 VF-7215-30X-4-P ......................... 131 VF-7215-XXX-4-P .................. 42, 136 VF-7221-2XX-4-P........................... 14 VF-7222-2XX-4-P ...........................14 VF-7223-XXX-4-P .......................... 42 VF-7225-25X-4-P .........................131 VF-7225-30X-4-P ......................... 131 VF-7225-XXX-4-P .................. 42, 136 VF-72X3 .................................28, 127 VF-72XX.................
Model Number Index Model Page Model Page VP-7323-XXX-4-P ..........................88 VP-9213-3XX-4-P ..........................32 VP-9213-3XX-5-P ..........................32 VP-9213-4XX-4-P ..........................32 VP-9213-4XX-5-P ..........................32 VP-9213-9XX-5-P ..........................32 VP-9213-XXX-4-P ..........................33 VP-9313-30X-4-P ...........................89 VP-9313-30X-5-P........................... 89 VP-9313-XXX-4-P ....................
VALVE SELECTION GUIDE Valve Selection Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Valve Part Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 6 USE SELECTION GUIDES TO DETERMINE WHAT PAGES HAVE THE REQUIRED VALVE SELECTION AND TECHNICAL DATA. SEE VALVE SELECTION OVERVIEW.
Valve Selection KEY 1. This section allows selection of a Valve Assembly (consisting of factory assembled valve body, linkage, and actuator) or Component Parts (valve body, linkage, and actuator unassembled). Refer to page 3 for an explanation of the part numbering system for valves. For details on the general information required for valve sizing and selection, refer to pages 172 through 179. 2.
Valve Selection PART NUMBERING SYSTEM GLOBE AND BUTTERFLY VALVE Refer to the product listing for part numbering. Always a Letter Always a Number(Digit) VXX-XXXX-XXX-X-XX VALVE B — VALVE BODY VALVE ASSEMBLIES* A — 2-Position (SPST) C — 2-Position (SPDT) F — Floating SPDT K — Pneumatic M — Modular Actuator (order MMC control module separately) P — Multiple Electric/Electronic Input: 1. 2-Position SPST 2. 2-Position SPDT 3. Slidewire (Series 90) 4. Current Input 5. Floating Control (Direct Digital) 6.
Valve Selection PART NUMBERING SYSTEM BALL VALVES V ( Control Type) - 2 ( Configuration ) 53- ( Actuator ) - 8 - (Port Code ) VX-2X53-XXX-8-XX Control Signal Type P Code A = Two Position F = Floating S = Proportional B = Valve Body & Linkage (less actuator) 2-Way Connection Size 1/2" 3 = Threaded NPT Configuration 2 = 2-Way 1 Plug Type and Temp Ratings 3 = 3-Way 2 5 = Stainless Steel Ball 3/4" 1" Two Position MA40-7043=536 MA40-7043-501=537 MA40-7040=532 MA40-7040-501=533 MA40-7041=534 MA
Valve Selection PART NUMBERING SYSTEM ZONE VALVES WITH FLOATING AND PROPORTIONAL ACTUATORS Zone Valves With Floating And Proportional Actuators V M 2 X X X A X X X X XX X Body Type M = Modulating Options Non-Spring Return Actuators 0 = No Options T = Three-Wire Signal Time-Out Spring Return Actuators 2 T = Time-Out Configuration Electrical Leads 2 = 2-Way 3 = 3-Way 00 = No leads Voltage Valve Size A = 24 Vac Only 2 = 1/2" 3 = 3/4" 4 = 1" 5 = 1-1/4" When ordering body and actuator together drop "A
Valve Selection PART NUMBERING SYSTEM ZONE VALVES WITH TWO POSITION, SPRING RETURN ACTUATORS V X X X X X X X X X XX X 1 Body Type & Temperature 2 Options 0 = No Options A = End Switch (required with terminal block) T = On/Off (General) S = On/Off (Steam) High temperature actuator must be used. Electrical Leads 00 = 6" Motor Wires 01 = Terminal Block with End Switch (General Temp.
Valve Selection Guide for Two-Way Valves Chilled or Hot Water 281°F Maximum; 35 psig Maximum Steam Valve Application Globe Valves Valve Body Type Stem Up Open Valve Selectio n Guide for Two-Wa y Valves Union, Angle Union, Straightway VB-7211-0-3-P VB-7211-0-4-P Union, Sweat Flared a VB-7212-0-4-P a Screwed VB-7214-0-4-P VB-7213-0-4-P VB-9213-0-4-P 250 psig 250 psig 125 psig 1/2 to 2 in. 1/2 to 2 in. 2-1/2 & 3 in. 2-1/2 to 6 in. 0.4 to 40 0.
Valve Selection Guide for Two-Way Valves Valve Application Hot Water 340°F Max.; 100 psig Max. Steam Hot Water 300°F Max.; 50 psig Max. Steam Hot Water 366°F Max.; 150 psig Max. Steam Globe Valves Ball Valve Valve Body Type Screwed Hot Water 250°F Max.; 15 psig Max.
Valve Selection Guide for Two-Way Valves Valve Application Water 281°F Max.; 35 psig Max. Steam Water 275°F Max.; 30 psig Max.
Valve Selection Guide for Three-Way Valves Valve Application Chilled or Hot Water 300°F Maximum Chilled or Hot Water 300°F Maximum Chilled or Hot Water 300°F Maximum Chilled or Hot Water 300°F Maximum Flanged Screwed Flanged Globe Valve Body Type Flared Flared VB-7312-0-4-P VB-324-0-5-P 250 psig 250 psig 250 psig 250 psig 250 psig 125 psig 250 psig 125 psig Sizes Available 5/8 in. O.D., SAE 45° 1/2 in. O.D. Tube 1/2 to 2 in. 2-1/2 & 3 in. 1/2 to 2 in. 2-1/2 to 6 in. 1/2 to 2 in.
Valve Selection Guide for Three-Way Valves Valve Application Chilled or Hot Water 281°F Maximum Chilled or Hot Water 275°F Maximum 32 to 200°F (0 to 94°C) Hot & Chilled Water 32 to 250F (0 to 121C) Water and Steam 15 psia (103 kPa) Steam.
Valve Selection Guide for SI-Threaded Valves, Two-Way and Three-Way Globe Two-Way Valves Two-Way Valves Two-Way Valves Three-Way Valves Three-Way Valves Chilled or Hot Water 138°C Maximum; 240 kPa (2.4 Bar) Max. Steam Chilled or Hot Water 138°C Maximum; 240 kPa (2.4 Bar) Max.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators 2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydrauli c, and Pneumat ic Actuator s TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 4 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code).
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 2. Select Actuator Type with correct Input Signal having sufficient close-off for the application.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 2A. Nominal Two-Way Valve, Hydraulic Actuator Close Off Ratings. Spring Closes (Normally Closed Spring Opens (Normally Open) MP-5x1x Analog Actuators: 6 to 9, MA-521X & MF-521X Digital All Actuators: Analog, 2 Position, 0 to 10 Volt, and 4 to 20 mA Actuators: 2 Position and Floating and Floating VA, VF, VS Close Off Rating with Springs Show Psi (kpa) Size in.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 4. Factory Assemblies, select exact Actuator Code (XXX) (2-Position SPST, TAC System 8000 2 to 15 Vdc, or 4 to 20 mAdc). Any MA-52XX, MP-5XXX, MPR-5X1X, MF-22XX3, MS-22353 can be assembled to 1/2 to 1-1/4 in. valve bodies with the close-off pressure ratings listed in Table 2. Select below listed Actuators or Actuator Codes (XXX) for factory available assemblies.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 5. Dimensions in Inches (Millimeters). Refer to page 19 for illustrations. Valve Body Part Number Series MF-5X1X E E Actuator Series MF-22XXX MS-22353 MK-2690 MK-46X1 E E E Size in.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 7. Ambient Temperature Restrictions for Valve Actuators. Temperatures °F (°C) Linkage Extension MF-22XXX MS-22353 MPR-581X,MP-541X, MF-5X1X MK-2690 MK-46X1 MA-521X — — AV-601a None a AV-601 and AV-7600-1 Maximum Ambient 140 (60) 140 (60) Max. Allowable Fluid 220 (104) 220 (104) Maximum Fluid 281 (138) 281 (138) Max.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators NOTE: Allow 3 inches clearance above actuator for removal. Mount MA/MP/MPR-5XXX actuators above the valve body at 45° from vertical on steam applications.
2-Way Globe Valves, Union End (1/2 to 1-1/4 in.) and Flared (1/2 & 5/8 in. O.D.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 3 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.) 2-Way Globe Valves, Screwe d (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flange d (2-1/2 to 6 in.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 2. 1/2 to 2 in. Valves, select Actuator or Actuator Code (XXX) with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage and Positive Positioner if required. Effective Area 6 Sq. In. 11 Sq. In.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 3. 2-1/2 to 6 in. Valves, select Actuator or Actuator Code (XXX) with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage and Positive Positioner if required. Effective Area 50 Sq. In. 100 Sq. In.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 5. Dimensions in Inches (Millimeters).
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators American Standard 125 lb. Cast Iron Pipe Flanges. F E B Length of Machine Bolt D A Flange Detail Dimensions in Inches (Metric conversion 25.4 mm = 1 in.) .
2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.) with Hydraulic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 3 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.) Size Normally Open Valves Normally Closed Valves 2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.
2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.) with Hydraulic Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage . MA-5200 Series Input Signal Two-Position Electric Actuator Code (XXX) Factory Available Valve Assembly N.C. VA-7213-2XX-4-P VS-7213-XXX-4-P VA-7223-2XX-4-P VS-7223-XXX-4-P mAdc 2XX 2XX MA-521X MF-5XXX Actuator N.
2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.) with Hydraulic Actuators TABLE 4. Controller Calibration with Spring Usage for VB-7XXX Valves. Actuator Series MP-521X Seriesa Valve Spring(s) 1/2 to 1-1/4 in. (15 to 32 mm) Large Unpainted 1/2 to 2 in. (15 to 50 mm) Calibrationb Nominal Control Range b 7.5 Volts 6 to 9 Volts 15 mA 12 to 18 mA Blackc 5.0 Volts 3.5 to 6.5 Volts (highest close-off) 10 mA 7 to 13 mA 7.
2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.) with Hydraulic Actuators on steam applications. 3-1/4 a 6-3/4 MA/MF/MP/MPR-5XXX with E VB-7213-0-4-P VB-7214-0-4-P VB-7223-0-4-P VB-7224-0-4-P Flow C A B a 30 AV-601 linkage extension (not shown) required for hot water applications for MF-5XXX, MP-54XX, MPR-5XXX, MP-55XX. © Copyright 2006 TAC. All Rights Reserved.
2-Way Globe Valves, Screwed (1/2 to 2 in.) and Union Sweat (1/2 to 2 in.) with Hydraulic Actuators TABLE 6. Ambient Temperature Restrictions for Valve Actuators. Temperatures °F (°C) 20X, 21X, 22X Actuator Code (XXX) 24X, 26X MPR-561X, MPR-571X, MP-541X, MP-551X w/ AV-601 Linkage Extension MP-521X-XXXa MP-521X-XXX w AV-601 Linkage Extension MF-5XXX-XXX w/ AV-601 Linkage Extension Maximum Ambient 140 (60) 140 (60) 140 (60) 140 (60) Max.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 3 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.) Application Chilled or Hot Water 281°F Max.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage. Floating Refer to Floating Floating SPDT SPDT Table 3C SPDT and Multiple Input Input Signal 1/2 to 1-1/4 in.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators TABLE 3A. Factory Assemblies (VC-72XX, 92XX), Two-Position SPDT Input, select Actuator Code (XXX). Any MC-3XX or MC-4XX electric gear train actuator can be assembled to valve bodies with the close-off pressure ratings listed in Table 2. Select Actuator Type having sufficient close-off for the application. Select actuator, linkage, valve body and field assemble.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators TABLE 3C. Factory Assemblies (VF-72XX, VP-72XX, VP-92XX, VS-72XX), Multiple Input (refer toTable 3C below), select exact Actuator Code (XXX). Any MF-22XX3, MS-22353, MP-3XX, 4XX or 9XXX electric gear train actuator can be assembled to valve bodies with the close-off pressure ratings listed in Table 2. Select Actuator Type having sufficient close-off for the application.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators \ TABLE 3E. Input Signal for Modular Actuators MM/MMR-400 or MM/MMR-500), MF-631X3. Order these control modules separately.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators TABLE 4. Dimensions in Inches (Millimeters). (Refer to the following pages for illustrations.) Valve Body Part Number VB-7213-0-4-P VB-7214-0-4-P VB-7253-0-4-P VB-7273-0-4-P VB-9213-0-4-P VB-9213-0-5-P a MA-318-XXX MA-41X-XXX Actuator Series (Code) MC-351, MC-351, MP-9730 MP-38X, 48X, MP-38X, 481 w/ MP-9750 MP-36X, 37X, AV-352 MP-9810 47X MM/MMR Size In.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators o Refer to Table 4 and Table 5 for dimensional data.
2-Way Globe Valves, Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Electric Gear Train Actuators American Standard 125 lb. Cast Iron Pipe Flanges. F Length of Machine Bolt E B D A Flange Detail Dimensions in Inches (Metric Conversion 25.4 mm = 1 in.).
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 3. Factory Assemblies, Two Position, Floating, Proportional Actuators, Select Actuator Code (XXX). Input Signal Two Position SPST Proportional Voltage 60 Hz 24 Vac ± 20% 4.4 4.2 120 Vac ± 10% 6.4 4.3 230 Vac ± 10% 5.8 4.6 24 Vac ± 20% 120 Vac ± 10% 240 Vac ± 10% 9.6 11.4 11.8 9.6 11.4 11.8 24 Vac ± 20% 11.6 11.2 120 Vac ± 10% 12.5 10.6 230 Vac ± 10% 16.1 11.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 4. MX40-6043 Dimensions in Inches (Millimeters). Valve Size in.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 5. MX40-6083 and MX40-6153 Dimensions in Inches (Millimeters). Refer to illustrations below. Valve Assembly Part Number Union Straightway VX-7211-XXX-4-P VX-7221-XXX-4-P NPT VX-7213-XXX-4-P VX-7223-XXX-4-P a Valve Dimensions in inches (millimeters) Valve Size in.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 6. MX40-704X-2XX Dimensions in Inches (Millimeters). Refer to illustrations below. Valve Dimensions in inches (millimeters) Valve Size in.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 7. MX40-715X-2XX and MX40-707X-2XX Dimensions in Inches (Millimeters). Refer to illustrations below. Valve Dimensions in inches (millimeters) Valve Size in.
2-Way Globe Valves, Screwed (1/2 to 2 in.), Union Straightway (1/2 to 2 in.) with TAC DuraDrive™ Actuators American Standard 125 lb. Cast Iron Pipe Flanges. F Length of Machine Bolt E B D A Flange Detail Dimensions in Inches (Metric Conversion 25.4 mm = 1 in.).
2-Way Stainless Steel Globe Valves, Screwed (1/2 to 3/4 in.) with Hydraulic, Pneumatic Actuators TABLE 1. Select Valve Body including P Code. Use Table 2 to select actuator type having sufficient close-off for the application. Use Table 3 to select Actuator Part Number with correct voltage and input signal. 1/2 to 3/4 in. Size Normally Closed Valves VBS-9263-0-4-P Modified Linear (Refer to page 170) Valve Body Flow Type NOTE: These charts are color coded as shown below to assist valve selection.
2-Way Stainless Steel Globe Valves, Screwed (1/2 to 3/4 in.) with Hydraulic, Pneumatic Actuators TABLE 2. Select Actuator Type having sufficient close-off for the application. Also, select valve linkage. See Table 3 for actuator part number having correct voltage and input signal. Input Signal Valve Linka 1/2 to 3/4 in.
2-Way Stainless Steel Globe Valves, Screwed (1/2 to 3/4 in.) with Hydraulic, Pneumatic Actuators TABLE 3. Select Actuator Part Number with correct voltage and input signal.. Input Signal Voltage Vac 50/60 Hz 24 MA-5213 Two-Position SPST 120 MA-5210 240 MA-5211 24 MP-5213 2 to 15 Vdc. TAC System 8000, stroke occurs 6 to 9 Vdc approx., non-positive positioning 120 VA Aux.
2-Way Stainless Steel Globe Valves, Screwed (1/2 to 3/4 in.) with Hydraulic, Pneumatic Actuators TABLE 4. Dimensions in Inches (Millimeters). Actuator Series Valve Body MA/MF/MP/ MPR-5XXXa Part Number Size In. A B E E 1/2 3 (76) 1-27/64 (36) 7-13/16 (198) 4-3/4 (121) 3/4 3-5/8 (92) 1-37/64 (40) 8-5/32 (207) 5-3/32 (129) VBS-9263-0-4-P a MK-2690 Add 2-3/32 in. (53 mm) to the “E” dimension for a valve assembly using an AV-601 linkage extension.
2-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators Hot Water 250°F Max. 15 psig (103 kPa) Steam Screwed NPT 1/2 to 2 in. Size Normally Open Valves 2-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDriv e™ Actuator s Application TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Linked Valve Assembly with correct Input Signal (refer to Table 2 and Table 3 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code).
2-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application.
2-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators Using Pipe Reducers with Two-Way Ball Valve Assemblies The following table provides estimated effective Cv’s when using pipe reducers with two-way ball valve assemblies. Caution: It is strongly recommended that the valve size not be reduced to less than one-half the line size. Installing a valve that is less than one-half the line size can cause flow disturbances that may result in stress failure at the pipe reduction area. TABLE 3.
2-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 4. Dimensions in Inches (Millimeters). (Refer to the following pages for illustrations.) Ball Valve Assembly Dimensions Valve Assembly Part Number Valve Dimensions in inches (millimeter) Valve Size in.
2-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators end of section end of section 4 (102) 4 (102) 7(178) Shaft Dia. 7-7/8 (200) E 6-1/2 (165) E A 10-7/8 (276) A MX40-634X MX40-704X 4 (102) 10-1/2 (267) 4 (102) 1/4 (6) 7-7/8 (200) 6-7/8 (175) E E 11-5/16 (287) 10-7/8 (276) MX40-717X MX40-707X 58 A MX40-717X © Copyright 2006 TAC. All Rights Reserved.
2-Way Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators 2-Way Butterfly Valves, Flangele ss (2 to 24 in.) with Electric Gear Train and Pneumat ic Actuator TABLE 1. Select Valve Assembly with correct Input Signal (refer to Table 3, Table 3A and Table 3B also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.
2-Way Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators TABLE 2. Factory Assemblies, select Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application.
2-Way Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators TABLE 3A. Factory Assemblies (VC-6X64), SPDT (Snap Acting) Input, select exact Actuator Code (XXX). Input Signal Normal Position Voltage Vac Hz SPDT Snap Acting None 120 60 VA Auxiliary Switch Actuator Actuator Code (XXX) for Factory Available Assembly 96 Yes MC-431 113 TABLE 3B. Factory Assemblies VP-6X6X), Multiple Input (refer to table below), select exact Actuator Code (XXX). Any 220 lbin.
2-Way Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators TABLE 5. Dimensions in Inches (Millimeters).
2-Way Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators 9-1/2 3 E 9-1/2 3 3 6-3/4 4 Alignment Holes Match 125-150 lb. Flange Drilling 16-1/4 B 20-3/8 Adjustable Packing Nut 30 6 D 30 Outboard Bearing 6 Adjustable Packing Nut C 4 Alignment Holes Match 125-150 lb. Flange Drilling VC-6064 (2"–14") VP-6064 (2"–14") D A B 6-3/4 Outboard Bearing C A E VP-6065 (8"–24") 9-1/2 9-1/2 3 3 3 Holes Match 125-150 lb.
2-Way Zone Valves, Brass Threaded, Sweat, Flare, Inverted Flare (1/2 to 1-1/4 in.) with Electric Actuators Part Numbering System Two Position, Spring Return Actuator Zone Valve V X X X X X X X X X XX X 1 Body Type & Temperature 2 Options 0 = No Options A = End Switch (required with terminal block) T = On/Off (General) S = On/Off (Steam) High temperature actuator must be used. Electrical Leads 00 = 6" Motor Wires 01 = Terminal Block with End Switch (General Temp.
2-Way Zone Valves, Brass Threaded, Sweat, Flare, Inverted Flare (1/2 to 1-1/4 in.
2-Way Zone Valves, Brass Threaded, Sweat, Flare, Inverted Flare (1/2 to 1-1/4 in.) with Electric Actuators TABLE 1. Select Valve Body (Valve Size, Cv Rating, Configuration) less actuator or select Valve Assembly with correct Input Signal (Refer to Pages 172 to 179 for Valve Sizing). NOTE: These charts are color coded as shown below to assist valve selection. Note it is only possible to select a valve assembly or component parts (actuator, valve body). ORDERING EXAMPLES: 1.
2-Way Zone Valves, Brass Threaded, Sweat, Flare, Inverted Flare (1/2 to 1-1/4 in.) with Electric Actuators TABLE 2. Use the zone valve numbering system on pages 64 and 65 to configure the valve body. Select the actuator type with correct input signal and having sufficient close-off for the application. Use the zone valve numbering system on pages 64 and 65 to configure the actuator or the valve/actuator assembly. Actuator AGXXXXXX Input Signal 2 Position SPST Voltage Impedance — Valve Body Size in.
2-Way Zone Valves, Brass Threaded, Sweat, Flare, Inverted Flare (1/2 to 1-1/4 in.) with Electric Actuators TABLE 3. Dimensions in Inches (Millimeters). Actuator Series Valve Body Part Number VTXXXX VSXXXX VMXXXX VTXXXX VSXXXX AGXXXXXX AHXXXXXX AX33A00X AXX3A00X Size In. A B D D D 1/2 Sweat 1.29 (33) 0.9 (23) 3.30 (84) 3.62 (92) — 3/4 Sweat 1.37 (35) 0.9 (23) 3.38 (86) 3.74 (95) — 1 Sweat 1.69 (43) 0.9 (23) 3.62 (92) 4.0 (102) — 1-1/4 Sweat 1.85 (47) 1 (25) 3.70 (94) 4.
2-Way Zone Valves, Brass Threaded, Sweat, Flare, Inverted Flare (1/2 to 1-1/4 in.) with Electric Actuators VM2XXXX33A00X VM2XXXXX3A00X page F-27414-1 © Copyright 2006 TAC. All Rights Reserved.
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 3 and Table 3A also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 2. SPST and 2 to 15 Vdc TAC System 8000 inputs, select Actuator Type or Actuator Code (XXX) with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage .
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 2A. Pneumatic Input, select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage and Positive Positioner if required.
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 3. Factory Assemblies (Two-Position SPST, TAC System 8000 2 to 15 Vdc, 4 to 20 mA), select exact Actuator Code (XXX). Any MA-52XX, MF-22XX3, MP-5XXX, MPR-5X1X, MS-22353 can be assembled to 1/2 in. to 1-1/4 in. valve bodies with the close-off pressure ratings listed in Table 2 and Table 2A. Select below listed Hydraulic Actuators or Actuator Codes (XXX) for factory available assemblies.
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators figure Chilled Water Return % Chilled Water Flow % Four Pipe Single Coil TK-1001 D.A.
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 6. 3-Way Valve Dimensions in Inches (millimeters). Valve Body Part Number Size In.
3-Way Mixing and Sequencing Globe Valves, Flared (5/8 in. O.D.) with Electric, Hydraulic, and Pneumatic Actuators TABLE 7. Flow Pattern. Stem Up (SU) (Normal Position) Body Part Number VB-7312-0-4-P VB-7332-0-4-P Stem Down (SD) Flow Type Flow Closed Port Flow Closed Port Mixing B to AB A A to AB B Sequencing B to AB A A to AB B TABLE 8. Ambient Temperature Restrictions for Valve Actuators.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 2B also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 2. 1/2 to 1-1/4 in. Valves, select Actuator or Actuator Code (XXX) having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage and Positive Positioner if required. Effective Area 6 Sq. In. Valve Linkage AV-7400 AV-401 AK-42309-500 AK-42309-500 Positive Positioner 11 Sq. In.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 2A. 1/2 to 4 in. Valves, select Actuator or Actuator Code (XXX) having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage and Positive Positioner if required. (Also refer to Table 2B). Effective Area (stroke) 50 Sq. In. (1/2 In.) 50 Sq. In. (1 In.) 50 Sq. In. (1-1/2 in.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 2B. 2-1/2 to 6 in. Valves, select Actuator or Actuator Code (XXX) having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage and Positive Positioner if required. Effective Area (Stroke) 100 Sq. In. (1 in.) Valve Linkage Positive Positioner 100 Sq. In. (2 in.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators TABLE 4. Dimensions in Inches (Millimeters).
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in.) with Pneumatic Actuators 12-1/2 10-5/16 12-1/2 10-5/16 12-1/2 10-5/16 3 E E 3 E 3 16-5/8 (2-1/2–4") 19 (5-6") 16-5/8 (1-1/2 - 3") U MK-8XX1 with VB-9313-0-5-P L C C A See Flange Detail Table MK-68X1 or MK-6911 with VB-9323-0-5-P C A B A A C MK-8XX1 with VB-7313-0-4-P See Flange Detail Table B A American Standard 125 lb.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), and Screwed, Union Sweat (1/2 to 2 in.) with Hydraulic Actuators 3-Way Globe Valves, Mixing (1/2 to 2 in.), Divertin g (1/2 to 2 in.), and Screwed , Union Sweat (1/2 to 2 in.) with Hydrauli c Actuator s TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 4 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code).
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), and Screwed, Union Sweat (1/2 to 2 in.) with Hydraulic Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage . See Table 3 for controller calibration. AV-7600-1a AV-7600-1 Electronic Vdc and 4 to 20 mA SPDT Floating and Two Position Valve Linkage (1/2 to 2 in.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), and Screwed, Union Sweat (1/2 to 2 in.) with Hydraulic Actuators TABLE 4. Factory Assemblies, select exact Actuator Code (XXX). Any MA-52XX, MF-5X1X, MP-5XXX, MPR-5X1X can be assembled to 1/2 to 1-1/4 in. valve bodies with the close-off pressure ratings listed in Table 2. Select below listed Hydraulic Actuators or Actuator Codes (XXX) for factory available assemblies.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), and Screwed, Union Sweat (1/2 to 2 in.) with Hydraulic Actuators 3-1/4 6-3/4 E C MA-521X a MP-5X1X MPR-5X1Xa MF-5X1Xa with VB-7313-0-4-P VB-7314-0-4-P VB-7323-0-4-P D A B a AV-601 linkage extension (not shown) required for hot water applications. Refer to Table 4. TABLE 7. Flow Pattern.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 1. Select Valve Body including P Code (Valve Size, CV Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 3A also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.) 3-Way Globe Valves, Mixing (1/2 to 6 in.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage .
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 2A. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage . Refer to Table 3A Floating SPDT Proportional Floating SPDT 1/2 to 2 in. — (Included) (Included) (Included) — 2-1/2 to 4 in.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 3. Factory Assemblies (VA-X3XX, VC-X3XX and VS-X3XX), select exact Actuator Code (XXX). Any MA-3XX, MC-3XX, MC-4XX, MF-221X3, MS-22353, and 220 lb-in. MP-4XX electric gear train actuator can be assembled to valve bodies with the close-off pressure ratings listed in Table 2 and Table 2A.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 3A. Factory Assemblies (VP-93XX), Multiple Input (refer to table below), select exact Actuator Code (XXX). Any 220 lb-in. MP-4XX, MP-9XXX electric gear train or MS-8305X hydraulic actuator can be assembled to valve bodies with the close-off pressure ratings listed in Table 2 and Table 2A.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 4. Dimensions in Inches (Millimeters). (Refer to the following pages for illustrations.) Valve Body Part Number Size In.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators Refer to Table 4 and Table 5A for dimensional data.Table 4Table 5ATable 4 and Table 5A for dimensional data.American Standard 125 lb.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.
3-Way Globe Valves, Mixing (1/2 to 6 in.), Diverting (1/2 to 6 in.), Screwed (1/2 to 3 in.), Union Sweat (1/2 to 2 in.) and Flanged (2-1/2 to 6 in) with Electric Gear Train Actuators TABLE 6. Restrictions on Maximum Ambient Temperature for Valve Actuators. TEMPERATURES °F (°C) Actuator Code Maximum Ambient Max.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators Application Chilled or Hot Water TABLE 1. Select Valve Body including P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 175 for Valve Sizing.) 3-Way Globe Valves, Mixing (1/2 to 2 in.), Divertin g (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDriv e™ Actuator s Screwed NPT Internal Parallel Pipe Thread per ISO 7/1, BS 21, JIS B0203 Screwed NPT Size 1/2 to 2 in.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage. Input Signal Valve Linkage (Shaft Dia.) AV-603 (1/2 in.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 3. Factory Assemblies, Two Position, Floating, Proportional Actuators, Select Actuator Code (XXX). Input Signal Two Position SPST Proportional Voltage 60 Hz 24 Vac ± 20% 4.4 4.2 120 Vac ± 10% 6.4 4.3 230 Vac ± 10% 5.8 4.6 24 Vac ± 20% 120 Vac ± 10% 240 Vac ± 10% 9.6 11.4 11.8 9.6 11.4 11.8 24 Vac ± 20% 11.6 11.2 120 Vac ± 10% 12.5 10.6 230 Vac ± 10% 16.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 4. MX40-6043 Dimensions in Inches (Millimeters). Refer to illustration below. Valve Dimensions in inches (millimeters) Valve Assembly Part Number Three-Way (Refer to illustration below) Valve Size in.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 6. MX40-704X-2XX Dimensions in Inches (Millimeters). Refer to illustration below. Valve Dimensions in inches (millimeters) Valve Assembly Part Number Three-Way (Refer to illustration) Valve Size in.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 8. MX40-717X Dimensions in Inches (Millimeters). Refer to illustration below. Valve Dimensions in inches (millimeters) Valve Assembly Part Number Three-Way (Refer to illustration below) Valve Size in.
3-Way Globe Valves, Mixing (1/2 to 2 in.), Diverting (1/2 to 2 in.), Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators ron Pipe Flanges. F E B D A Length of Machine Bolt Flange Detail Dimensions in Inches (Metric conversion 25.4 mm = 1 in.).
3-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators Application TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Linked Valve Assembly with correct Input Signal (refer to Table 2 and Table 3 also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.) Hot Water 250°F Max. 15 psig (103 kPa) Steam Screwed NPT Size 1/2 to 2 in.
3-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application.
3-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators TABLE 4. Dimensions in Inches (Millimeters). (Refer to the following pages for illustrations.) Ball Valve Assembly Dimensions Valve Assembly Part Number Valve Dimensions in inches (millimeters) Valve Size in.
3-Way Ball Valves, Screwed (1/2 to 2 in.) with TAC DuraDrive™ Actuators tend of section 4 (102) 4 (102) 7 (178) Shaft Dia. 7-7/8 (200) E E D A 10-7/8 (276) D A 7 (178) MX40-634X MX40-704X 10-1/2 (267) 4 (102) 4 (102) 1/4 (6) 6-7/8 (175) E D A D A 11-5/16 (287) 10-7/8 (276) MX40-715X MX40-707X F-27414-1 7-7/8 (200) E MX40-717X © Copyright 2006 TAC. All Rights Reserved.
3-Way Mixing and Diverting Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators TABLE 1. Select Valve Assembly with correct Input Signal (refer to Table 3, Table 3A, and Table 3B also) less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.) Application Chilled or Hot Water Flangeless Wafera 2 in. - 6 in. Lug 8 in. - 12 in. Wafer 2 to 24 in. 2 to 12 in.
3-Way Mixing and Diverting Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators ‘ TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application.
3-Way Mixing and Diverting Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators TABLE 3B. Factory Assemblies (VP-6X6X and VS-6X64), Multiple Input (refer to table below), select exact Actuator Code (XXX). Any 220 lb-in. MP-3XX, MP-4XX, or MP-9XXX electric gear train actuator can be assembled to valve bodies with the close-off pressure ratings listed in Table 2. Select Actuator Type having sufficient close-off for the application.
3-Way Mixing and Diverting Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators tee numbers The 3-Way Assemblies are shipped as a complete unit, assembled, mounted and tested, fully ready for field installation. Two valves are mounted on a 125 lb. cast iron tee; one valve complete with power actuator, the second valve controlled through connecting slave linkage. The valves are linked so that as one valve opens, the other A B A A C B C valve closes.
3-Way Mixing and Diverting Butterfly Valves, Flangeless (2 to 24 in.) with Electric Gear Train and Pneumatic Actuators illustrations 9-1/2 3 125 lb. Flanged Cast Iron Tee Holes Match 125-150 lb. Flange Drilling 16-1/4 6-3/4 Power Valve E 30 D E 6 9-1/2 3 A 3 2 C 6-1/8 E 1/16 Rubber Flanged Seal Both Sides B Holes Match 125-150 lb. Flange Drilling Slave Valve 20-3/8 VC-6764 (2"–5") VP-6764 (2"–5") 125 lb.
3-Way Zone Valves, Brass Threaded (1/2 to 1 in.), Sweat (1/2 to 1-1/4 in.) with Electric Actuators Part Numbering System Two Position, Spring Return Actuator Zone Valve 3-way zone valves V X X X X X X X X X XX X 1 Body Type & Temperature 2 Options 0 = No Options A = End Switch (required with terminal block) T = On/Off (General) S = On/Off (Steam) High temperature actuator must be used.
3-Way Zone Valves, Brass Threaded (1/2 to 1 in.), Sweat (1/2 to 1-1/4 in.
3-Way Zone Valves, Brass Threaded (1/2 to 1 in.), Sweat (1/2 to 1-1/4 in.) with Electric Actuators TABLE 1. Select Valve Body less actuator (Valve Size, Cv Rating, Configuration) or select Valve Assembly with correct Input Signal (Refer to Pages 172 to 175 for Valve Sizing). NOTE: These charts are color coded as shown below to assist valve selection. Note it is only possible to select a valve assembly or component parts (actuator, valve body). ORDERING EXAMPLES: 1.
3-Way Zone Valves, Brass Threaded (1/2 to 1 in.), Sweat (1/2 to 1-1/4 in.) with Electric Actuators TABLE 2. Using the numbering system on Pages 783 or 784 select the actuator type with correct input signal and having sufficient close-off for the application. Actuator AGXXXXXX Input Signal 2 Position SPST Voltage Impedance Valve Body — Size in.
3-Way Zone Valves, Brass Threaded (1/2 to 1 in.), Sweat (1/2 to 1-1/4 in.) with Electric Actuators TABLE 3. Dimensions in Inches. Actuator Series Valve Body Part Number VTXXXX VSXXXX VMXXXX GXXXXXX Size In. A C D D D 1/2 Sweat 1.29 3.30 3.30 3.62 — 3/4 Sweat 1.37 1.69 3.38 3.74 — 1 Sweat 1.69 1.69 3.62 4.0 — 1-1/4 Sweat 1.85 1.85 3.70 4.13 — 1/2 NPT, Rp 1/2 1.37 3.30 3.38 3.62 — 3/4 NPT, Rp 3/4 1.69 1.45 3.62 4.0 — 1 NPT Rp 1 1.85 1.69 3.70 4.13 — 2.
3-Way Zone Valves, Brass Threaded (1/2 to 1 in.), Sweat (1/2 to 1-1/4 in.) with Electric Actuators VMXXXXX33A00X VMXXXXXX3A00X 118 © Copyright 2006 TAC. All Rights Reserved.
METRIC VALVES F-27414-1 © Copyright 2006 TAC. All Rights Reserved.
120 © Copyright 2006 TAC. All Rights Reserved.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators 2-Way Globe Valves, Screwed End (15 to 80 mm) with Pneumat ic Actuator s TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code).
2-Way Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators TABLE 2. 15 to 50 mm Valves, select Actuator with correct Input Signal having sufficient close-off for the application. Select Valve Linkage and Positive Positioner if required.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators TABLE 2A. 65 to 80 mm Valves, select Actuator with correct Input Signal having sufficient close-off for the application. Select Valve Linkage and Positive Positioner if required.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators Actuator Valve Body Part Number MK-2690 MK-46X1 MK-6XX1 C C C C 95 427 532 102 436 541 Size mm A B 65 216 80 241 VB-9225-0-4-P 318 262 318 262 105 57 127 76 76 76 MK-8XX1 94 C C C B Flow 318 318 MK-2690 with VB-7215-0-4-P VB-7225-0-4-P A 318 262 A B A B Flow Flow A A MK-66X1 with VB-7215-0-4-P VB-7225-0-4-P MK-68X1 with VB-9215-0-4-P VB-9225-0-4-P B C 76 422 (64–76) 175 122 94 MK-88
2-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators 2-Way Globe Valves, Screwed End (15 to 50 mm) with Hydrauli c Actuator s TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code). Application Chilled or Hot Water 138°C Maximum 240 kPa (2.4 Bar) Steam Internal Parallel Pipe Thread per ISO 7/1, BS 21, JIS B0203 NOTE: These charts are color coded as shown below to assist valve selection.
2-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage . MA-5200 Series AV-7600-1 Valve Linage Actuator Code (XXX) Actuator Factory Available Valve Assembly VA-7215-2XX-4-P VS-7215-XXX-4-P N.O. VA-7225-2XX-4-P VS-7225-XXX-4-P N.C.
2-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators TABLE 4. Factory Assemblies, select exact Actuator Code (XXX). Any MA-52XX, MF-5X1X, MP-5XXX, MPR-5X1X can be assembled to 1/2 to 1-1/4 in. valve bodies with the close-off pressure ratings listed in Table 2. Select below listed Hydraulic Actuators or Actuator Codes (XXX) for factory available assemblies. For applications that factory assemblies are not available, select actuator, linkage, valve body and field assemble.
2-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators TABLE 5. Dimensions (mm). Actuator Series Valve Body MA/MF/MP/ MPR-5XXXa Part Number Size mm A B C 15 76 27 170 20 92 27 170 29 217 25 VB-7215-0-4-P 117 32 35 217 40 137 38 219 50 156 40 225 15 76 32 170 20 92 25 VB-7225-0-4-P a 117 32 32 170 44 202 44 208 40 137 46 211 50 156 52 213 Add 53 mm to the “C” dimension for a valve assembly using an AV-601 linkage extension.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators 2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuator s TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code). NOTE: These charts are color coded as shown below to assist valve selection. ORDERING EXAMPLES: Valve Body: VB-7215-0-4-11 Actuator: MP-361 Application Chilled or Hot Water 138°C Maximum 240 kPa (2.4 Bar) Steam Chilled or Hot Water 138°C Maximum 240 kPa (2.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 2. 15 to 80 mm Valves, select Actuator Type with correct Input Signal having sufficient close-off for the application. Select Valve Linkage if required.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 2A. 15 to 80 mm Valves, select Actuator Type with correct Input Signal having sufficient close-off for the application. Select Valve Linkage if required.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 3B. Proportional Voltage/Current. Input Signal Normal Position 2-15 Vdc, TAC System 8000, start 6 Vdc, Factory set Adj. 2-12 Vdc, 3 Vdc span, Positive Positioning 2-10 Vdc 4-20 mAdc Normally Closed Normally Open Hz VA Aux.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 4. Dimensions in mm. Actuator Series Valve Body Part Number MF-631X3 MS-79X3 Size in mm (Rp) A B C C C 15 76 27 108 181 — 20 92 27 108 181 — 29 122 198 — 35 122 198 — VB-7215-0-4-P VB-7225-0-4-P VB-9215-0-4-P VB-9225-0-4-P 25 117 32 40 137 38 124 200 — 50 156 40 130 206 — 65 216 95 — 264 — 80 241 102 — 276 — Temperatures °C TABLE 5. Restrictions on Max.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 6. Dimensions in mm.
2-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators end of section 143 140 102 159 92 190 C C B B A A MM/MR-400 MM/MMR-500 with VB-7215-0-4-P MF-631X3 with VB-7215-000-4-P 140 102 159 190 C A B A 229 B MM-400, 500 MMR-400, 500 with VB-9215-0-4-P C A B A B A MC-351, 4XX, 4XX1 MP-361, 371 MP-38X, 48X MP-465, 475 MP5-46XX, 47XX, 361, 381 with (65-80 mm) VB-9215-0-4-P and AV-352 Linkage MC5-4311 A B C 124 78 B A C FLOW B MF-631X3 with VB-9215-0-4-P
Linked 2-Way Globe Valves, Screwed (15 to 50 mm), Union Straightway with TAC DuraDrive™ Actuators TABLE 1. Select Valve Body including P Code (Valve Size, Cv Rating, Port Code) or select Valve Assembly with correct Input Signal less Actuator Code (XXX) including the P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing.
Linked 2-Way Globe Valves, Screwed (15 to 50 mm), Union Straightway with TAC DuraDrive™ Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage. Input Signal Valve Linkage (Shaft Diameter) AV-603 (15 mm.
Linked 2-Way Globe Valves, Screwed (15 to 50 mm), Union Straightway with TAC DuraDrive™ Actuators TABLE 3. Factory Assemblies, Two Position, Floating, Proportional Actuators, Select Actuator Code (XXX). Input Signal Two Position SPST Proportional Voltage 60 Hz 24 Vac ± 20% 4.4 4.2 120 Vac ± 10% 6.4 4.3 230 Vac ± 10% 5.8 4.6 24 Vac ± 20% 120 Vac ± 10% 240 Vac ± 10% 9.6 11.4 11.8 9.6 11.4 11.8 24 Vac ± 20% 11.6 11.2 120 Vac ± 10% 12.5 10.6 230 Vac ± 10% 16.1 11.1 24 Vac ± 20% 4.
Linked 2-Way Globe Valves, Screwed (15 to 50 mm), Union Straightway with TAC DuraDrive™ Actuators TABLE 4. MF40-6043 and MS40-6043 Dimensions in Millimeters. Refer to illlustration below Valve Dimensions in millimeters Valve Assembly Part Number Two-Way (Refer to illustration below) Valve Size mm.
Linked 2-Way Globe Valves, Screwed (15 to 50 mm), Union Straightway with TAC DuraDrive™ Actuators TABLE 5. MF40-6083-2XX and MX40-6153-2XX Dimensions in Millimeters. Refer to illustration below. Valve Dimensions in millimeters Valve Assembly Part Number Two-Way (Refer to illustration below) Valve Size mm. VX-7215-XXX-4-P VX-7225-XXX-4-P A B C E 15 117 — 29 203 32 117 — 35 192 38 137 — 38 187 50 156 — 40 202 TABLE 6. MX40-715X-2XX and MX40-707X-2XX Dimensions in Millimeters.
Linked 2-Way Globe Valves, Screwed (15 to 50 mm), Union Straightway with TAC DuraDrive™ Actuators TABLE 7. MX40-717X Dimensions in Millimeters. Refer to illustration below. Valve Dimensions in millimeters Valve Assembly Part Number Two-Way (Refer to illustration below) Valve Size mm. Metric Thread VX-7215-XXX-4-P VX-7225-XXX-4-P A B C E 40 137 — 38 327 50 156 — 40 343 6-1/8 (156) 4 (102) 3-3/8 (86) 11-5/8 (295) 10-1/2 (267) 11-1/4 (286) E C A F-27414-1 © Copyright 2006 TAC.
2-Way Stainless Steel Globe Valves, Screwed (15 to 20 mm) with Electric, Pneumatic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code) or select Valve Assembly with correct Input Signal (refer to Table 3 also) less Actuator Code (XXX) including the P Code (Size, kvs Rating, Port Code). (Refer to Pages 172 to 179 for Valve Sizing).
2-Way Stainless Steel Globe Valves, Screwed (15 to 20 mm) with Electric, Pneumatic Actuators TABLE 2. Select Actuator Type or Actuator Code (XXX) series with correct Input Signal having sufficient close-off for the application. If selecting Component Parts, select Valve Linkage .
2-Way Stainless Steel Globe Valves, Screwed (15 to 20 mm) with Electric, Pneumatic Actuators TABLE 3. Factory Assemblies, select exact Actuator Code (XXX). Any MA-52XX, MF-5X1X, MP-5XXX, MPR-5X1X can be assembled to 15 to 20 mm valve bodies with the close-off pressure ratings listed in Table 2. Select below listed Hydraulic Actuators or Actuator Codes (XXX) for factory available assemblies. For applications that factory assemblies are not available, select actuator, linkage, valve body and field assemble.
2-Way Stainless Steel Globe Valves, Screwed (15 to 20 mm) with Electric, Pneumatic Actuators TABLE 4. Dimensions in Millimeters. Actuator Series Valve Body Part Number Size mm 15 20 VBS-9265-0-6-P a MA/MF/MP/ A 76 92 MK-2690 MPR-5XXXa E 198 207 B 36 40 E 121 129 Add 53 mm to the “E” dimension for a valve assembly using an AV-601 linkage extension. NOTE: Allow 76 millimeter clearance above actuator for removal.
3-Way Mixing and Diverting Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code). NOTE: These charts are color coded as shown below to assist valve selection.
3-Way Mixing and Diverting Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators TABLE 2. 15 to 50mm Valves, select Actuator having sufficient close-off for the application. Select Valve Linkage and Positive Positioner if required.
3-Way Mixing and Diverting Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators TABLE 2A. 15 to 80 mm Valves, select Actuator or having sufficient close-off for the application. Select Valve Linkage and Positive Positioner if required.
3-Way Mixing and Diverting Globe Valves, Screwed End (15 to 80 mm) with Pneumatic Actuators TABLE 3. Optional Input Signal Interface to Pneumatic. Input Signal Type Two-Position, SPST (Electric) Interface Module Required AL-1XX Two-Position, SPDT Snap Acting (Electric) AL-1XX Voltage 2 to 15 Vdc TAC System 8000 CP-8511-XXX Current Input 4 to 20 mA etc. CP-8511-XXX, CP-8551 TABLE 4. Dimensions (mm).
3-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code). NOTE: These charts are color coded as shown below to assist valve selection.
3-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators TABLE 2. Nominal Hydaulic 3-Way Valve Close Off Ratings (See Table 3 For Controller Calibration.) VA, VF, and VS P Code Valve Body Valve Size mm.
3-Way Globe Valves, Screwed End (15 to 50 mm) with Hydraulic Actuators 83 171 C MA-521X a MF-5X13 a MP-5X1X a MPR-5X1X with VB-7315-0-4-P B A a AV-601 valve linkage extension (not shown) required for MF-5X13, MP-54XX, MP-55XX, and MPR-5XXX in hot water applications. Refer to Table 3 and Table 4. TABLE 5. Flow Pattern. Part Number Flow Type VB-7315-0-4-P Mixing Stem Up (SU) (Normal Position) Closed Port Flow Closed Port B to AB A A to AB B TABLE 6.
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuator s TABLE 1. Select Valve Body including P Code (Valve Size, kvs Rating, Port Code). Application Chilled or Hot Water Chilled or Hot Water 138°C Maximum 240 kPa 138°C Maximum 240 kPa Internal Parallel Pipe Thread per ISO 7/1, BS 21, JIS B0203 NOTE: These charts are color coded as shown below to assist valve selection.
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 2. 15 to 80 mm Valves, select the appropriate Valve Linkage for Actuator Type with correct Input Signal having sufficient closeoff for the application. Input signal Refer to Table 4F and Table 4G Two-Position SPST Refer to Table 4B and Table 4E Refer to Table 4A, Table 4B, and Table 4E.
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 3. 15 to 80 mm Valves, select the appropriate Valve Linkage for Actuator Type with correct Input Signal having sufficient close-off for the application.
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 4B. 2 to 15 Vdc TAC System 8000 input. Input Signal Normal Position 2-15 Vdc, TAC System 8000, start 6 Vdc, Factory set Adj. 2-12 Vdc, 3 Vdc span, Positive Positioning 2-10 Vdc or 4-20 mAdc, Fixed span and Start point Normally Closed Normally Open Voltage Hz VA Aux. Switch Actuator 120 60 50 Yes MP-461-600 MP-471-600 MP-481-600 MP-481-600 w/AV-352 24 60 50 No MS-22353 None TABLE 4C.
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 4G. Input Signal for Modular Actuators ( MM/MMR-400 or MM/MMR-500) and MF-63123. Order these control modules separately.
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 5. Dimensions (mm).
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators 137 102 137 102 181 171 137 173 102 48 159 171 48 108 178 108 178 C Spring Return Only C Spring Return Only E A B A B B MA5-318-500 MA-318-XXX MA-419 MA-418-XXX with VB-9315-0-4-P A B A B B A A A B A C B A MC5-4311 MP5-361, 381 MP-361, 371 MP 465, 475 MP5-46XX MP5-47XX with VB-9315-0-4-P and Electronic Drive 229 140 102 159 150 102 159 MC5-4311 MP5-361, 381 MC-351, 4XX MP-361, 371 MP 465, 4
3-Way Globe Valves, Screwed End (15 to 80 mm) with Electric Gear Train Actuators TABLE 5A. Dimensions (mm) for MF-631X3. Part Number Actuator Size mm A B C 15 76 35 181 20 92 43 181 40 183 41 189 191 25 VB-7315-0-4-P 117 32 VB-9315-0-4-P 143 40 137 41 50 156 48 194 65 216 117 264 80 241 127 276 92 C C B B A A MF-631X3 with VB-7315-000-4-P MF-631X3 with VB-9315-0-4-P 129 81 C B A MF-22XX3 with VB-7315-0-4-P TABLE 6. Flow Pattern.
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™ Actuators Application TABLE 1. Select Valve Body including P Code (Size, Cv Rating, Port Code). (Refer to Pages 172 to 175 for Valve Sizing.
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™ Actuators TABLE 2. 15 to 80 mm Valves, select the appropriate Valve Linkage for Actuator Type with correct Input Signal having sufficient close-off for the application.
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™ Actuators TABLE 3. Factory Assemblies, Two Position, Floating, Proportional Actuators, Select Actuator Code (XXX). Input Signal Two Position SPST Proportional Voltage 60 Hz 24 Vac ± 20% 4.4 4.2 120 Vac ± 10% 6.4 4.3 230 Vac ± 10% 5.8 4.6 24 Vac ± 20% 120 Vac ± 10% 240 Vac ± 10% 9.6 11.4 11.8 9.6 11.4 11.8 24 Vac ± 20% 11.6 11.2 120 Vac ± 10% 12.5 10.6 230 Vac ± 10% 16.1 11.1 24 Vac ± 20% 4.8 4.6 120 Vac ± 10% 10.
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™ Actuators TABLE 4. MF40-6043 and MS40-6043 Dimensions in Millimeters. Refer to illustration below. Valve Dimensions in millimeters Valve Assembly Part Number Three-Way (Refer to illustration below) Valve Size mm 15 VX-7315-505-4-P VX-7325-505-4-P A C E 76 35 162 20 92 43 162 25 117 44 164 32 117 41 170 40 136 40 173 50 156 52 175 5-7/8 (149) 4-15/16 (125) E C A TABLE 5.
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™ Actuators TABLE 6. MX40-704X-2XX Dimensions in Millimeters. Refer to illustration below. Valve Dimensions in millimeters Valve Assembly Part Number Three-Way (Refer to illustration) Valve Size mm. A C E 76 35 175 20 92 43 175 25 117 40 176 32 117 41 182 40 137 40 186 50 156 48 187 15 VX-73X5-XXX-4-P 6-3/4 (171) 4 (102) 5-7/8 (149) E C A 6 (152) TABLE 7.
3-Way Globe Valves, Screwed End (15 to 80 mm) with TAC DuraDrive™ Actuators TABLE 8. MX40-717X Dimensions in Inches (Millimeters). Refer to illustration below. Valve Dimensions in inches (millimetres) Valve Assembly Part Number Three-Way (Refer to illustration below) Valve Size in. VX-73X5-XXX-4-P A C E 40 137 41 327 50 156 48 327 7-1/8 (181) 4 (102) 4-1/8 (105) 11-1/4 (286) E C A 166 © Copyright 2006 TAC. All Rights Reserved.
VALVE GENERAL INFORMATION F-27414-1 © Copyright 2006 TAC. All Rights Reserved.
168 © Copyright 2006 TAC. All Rights Reserved.
Static Pressure Versus Temperature Ratings Maximum Temperature and Pressure Ratings for Globe Valve Bodies Limits for VB-727X, -728X, VBS-727X, -728X 400 (204) 340 (171) Temperature— F ( C) Static Pressur e Versus Tempera ture Ratings Limits for VB-725X, VB-726X, VBS-925X, VBS-926X 300 (149) 281 (138) Limits for VB-93X3-0-5 Limits for VB-721X, 921X, VB-722X, 922X, VB-73XX, 93XX 200 (93) Limits for VB-92X3-0-5 150 (65) 100 (38) 165 169 (1138) (1166) 50 (10) 0 286 321 (1973) (2218) 50 100 150 2
VB-7XXX, VB-9XXX Globe Valve Flow Curves, Rangeability, and Close-off Flow Curves Rangeability Flow curves shown below are representative of all sizes. Rangeability is defined as the ratio of rated to minimum controllable flow. All valve plugs have lower gain when nearly closed to enhance control at low demand. Mixing and diverting valves are nominally linear. Separate curves shown for “A” or “B” ports are not directly additive. Total flow with both ports contributing is rated Cv.
Packing Seal % Rated Life Versus Static Pressure Valve Packing Life TABLE 1. Flow Conversion Factors. Valve packings are designed to provide many years of useful life before they must be replaced. The actual life, under the standard specified conditions, will vary ⎯ depending on the frequency of valve cycle and the condition of the fluid controlled. The more frequently the valve is cycled and the more contaminated the fluid is with dirt and harsh chemicals, the shorter the life of the packing.
Valve Sizing Information for Water GENERAL INFORMATION REQUIRED 1. Fluid controlled: • Chilled water, hot water, or steam. 2. Temperature limitations: • Fluid, maximum, and minimum. • Ambient for actuator. 3. Pressure: • Static. • Close-off ⎯ Fully closed. • Differential ⎯ Pressure drop across the valve in the fully open position. 4. End fitting: • Union end. • Globe screwed. • Flared. • Flanged. • Flangeless. 5. For return to a known position (i.e.
Valve Sizing Information for Water For example, if a valve is controlling 200°F water at an inlet pressure of 18 psig, the maximum pressure drop allowable would be: TABLE 1. Vapor Pressure of Water Table. Water Temperature °F Vapor Pressure psig Water Temperature °F Vapor Pressure psig If the pressure drop for this valve is less than 10.6 psi, cavitation should not be a problem. 40 0.12 140 2.89 50 0.18 150 3.
174 © Copyright 2006 TAC. All Rights Reserved.
Valve Sizing Information for Water WATER VALVE SIZING TABLES WATER CAPACITY IN GALLONS PER MINUTE Differential Pressure (psi) ΔP WATER CAPACITY IN GALLONS PER MINUTE Differential Pressure (psi) ΔP Cv 0.10 0.22 0.30 2 3 4 5 10 15 20 25 30 35 0.17 0.20 0.22 0.32 0.39 0.45 0.5 0.5 0.6 0.42 0.38 0.52 0.44 0.60 0.49 0.67 0.70 0.95 0.85 1.16 0.98 1.34 1.1 1.5 1.2 1.6 1.3 1.8 0.4 0.57 0.69 0.80 0.89 1.26 1.55 1.79 2.0 2.2 2.4 0.75 1.06 1.30 1.50 1.68 2.37 2.90 3.
Valve Sizing Information for Steam RECOMMENDED PRESSURE DROPS FOR STEAM Cv (FLOW COEFFICIENT) DETERMINATION Refer to specific valve data in this catalog for maximum allowable drops and close-off ratings. The Steam Capacity Tables or Slide Rule (refer to this and the following two pages) is based on the following formula: QK Cv = ---------------------------3 ΔP × P 2 A. Two Position Zone Valves and Direct Radiator Valves Use a minimum of 10% of inlet pressure (psig). B.
F-27414-1 © Copyright 2006 TAC. All Rights Reserved. 8.2 9.5 10 11 12 14 15 18 19 20 22 23 24 27 29 30 34 38 41 46 1.5 1.75 1.9 2.0 2.2 2.5 2.8 3.25 3.5 3.6 4.0 4.3 4.4 5.0 5.4 5.5 6.2 7.0 7.5 8.5 2# 125 111 103 91 81 80 74 65 63 59 53 52 48 41 37 32 29 28 26 22 21 19 15 14 13 11.1 5.9 4.4 3.2 1.5 1.6 For two-position control. 7.6 1.4 a 7.1 4.9 0.9 1.3 4.1 0.75 5.4 2.2 0.4 1.0 1.6 0.30 5.2 1.2 0.95 0.5 0.22 0.
178 54 65 76 82 87 109 114 120 153 163 185 218 223 234 256 262 267 278 305 343 354 365 371 425 458 463 496 545 550 589 719 725 790 12 14 15 16 20 21 22 28 30 34 40 41 43 47 48 49 51 56 63 65 67 68 78 84 85 91 100 101 108 132 133 145 0.2a 10 Cv Inlet Pressure psig ΔP 2# © Copyright 2006 TAC. All Rights Reserved.
F-27414-1 © Copyright 2006 TAC. All Rights Reserved. 1281 1362 1401 1471 1580 1907 2120 2125 2338 2861 3444 4469 6131 7194 9581 10355 13804 15532 16540 22442 28769 35881 52459 235 250 257 270 290 350 389 390 429 525 632 820 1125 1320 1758 1900 2533 2850 3035 4118 5279 6584 9626 97087 77843 60723 44754 42026 37351 28017 25923 19465 16589 12092 9319 7742 6326 5751 5736 5161 4276 3981 3790 3686 3465 2610 2507 1.
Valve Sizing Information for Steam 180 © Copyright 2006 TAC. All Rights Reserved.
VALVE LINKAGES F-27414-1 © Copyright 2006 TAC. All Rights Reserved.
182 © Copyright 2006 TAC. All Rights Reserved.
Valve Body Cross Reference Valve Body To select the required valve linkage proceed with the following steps: 1. Match the part number below with the part number on the valve. Valve Body Cross Referen ce 2. Use the part number in parenthesis and the appropriate actuator part number to select the required valve linkage from the valve linkage selection guide on the following pages.
F-27414-1 ACTUATOR PART NUMBER Electric/Electronic Valve Body Part Number Valve Sizes MA-3X8-XXX MA-416-XXX MA4X8-XXX MA-4X9XXX MA-521X-XXX MC-31X MC-32X MC-41X MC-41X1 All MC-3XX, 4XX, 4XXX Except MF-631X3 Those in Preceding Column MP-32X, 33X, 36X, 37X, 42XX, 43XX, 46XX, 47XX, 21XX (180× Models Only) MP-34X, 35X, 38X, 44XX, 45XX, 48XX (180× Models Only) MP-503 MP-513 MU-503 MU-504 MU-506 MF-5X1X, MP-54XX, MP-55XX MU-4610X MU-4710X MM/MMR-400 MM/MMR-500 184 1/2 to 1-1/4 in.
F-27414-1 ACTUATOR PART NUMBER Electric/Electronic Valve Body Part Number Valve Sizes MA-3X8-XXX MA-416-XXX MA4X8-XXX MA-4X9XXX MA-521X-XXX MC-31X MC-32X MC-41X MC-41X1 All MC-3XX, 4XX, 4XXX Except MF-631X3 Those in Preceding Column MP-32X, 33X, 36X, 37X, 42XX, 43XX, 46XX, 47XX, 21XX (180× Models Only) MP-34X, 35X, 38X, 44XX, 45XX, 48XX (180× Models Only) MP-503 MP-513 MU-503 MU-504 MU-506 MF-5X1X, MP-54XX, MP-55XX MU-4610X MU-4710X MM/MMR-400 MM/MMR-500 1/2 to 2 in.
F-27414-1 ACTUATOR PART NUMBER Electric/Electronic Valve Body Part Number Valve Sizes MA-3X8-XXX MA-416-XXX MA4X8-XXX MA-4X9XXX MA-521X-XXX MC-31X MC-32X MC-41X MC-41X1 All MC-3XX, 4XX, 4XXX Except MF-631X3 Those in Preceding Column MP-32X, 33X, 36X, 37X, 42XX, 43XX, 46XX, 47XX, 21XX (180× Models Only) MP-34X, 35X, 38X, 44XX, 45XX, 48XX (180× Models Only) MP-503 MP-513 MU-503 MU-504 MU-506 MF-5X1X, MP-54XX, MP-55XX MU-4610X MU-4710X MM/MMR-400 MM/MMR-500 VB-9283-0-4-X 1/2 to 1-1/4 in.
F-27414-1 ACTUATOR PART NUMBER Valve Body Part Number Valve Sizes Electric/Electronic MX40-6043 MX40-6083 MX40-6153 MX40-634X MX40-704X MX40-707X MX40-715X MX40-717X VB-111-0-X-X 1/2 to 1-1/4 in. — — — — — — — — VB-121-0-X-X 1/2 in. O.D. — — — — — — — — VB-131-X-X-X 5/8 or 7/8 in. O.D. — — — — — — — — VB-151-0-1-X 1/2 to 1-1/4 in. — — — — — — — — VB-202-0-1-X 1/2 to 2 in. — — — — — — — — VB-202-0-2-X 2-1/2 to 4 in.
Valve Sizes Electric/Electronic MX40-6043 MX40-6083 MX40-6153 MX40-634X MX40-704X MX40-707X MX40-715X MX40-717X VB-7313-0-4-X 1/2 to 2 in. AV-603 AV-605 AV-602 — AV-605 AV-602 AV-602 AV-602 VB-7314-0-4-X 1/2 to 2 in. — — — — — — — — VB-7315-0-4-X 15 to 50 mm AV-603 AV-605 AV-602 — AV-605 AV-602 AV-602 AV-602 © Copyright 2006 TAC. All Rights Reserved. VB-7323-0-4-X 1/2 to 2 in. AV-603 AV-605 AV-602 — AV-605 AV-602 AV-602 AV-602 VB-7332-0-4-X 5/8 in. O.D.
F-27414-1 ACTUATOR PART NUMBER Valve Body Part Number Valve Sizes Electric/Electronic MX40-6043 MX40-6083 MX40-6153 MX40-634X MX40-704X MX40-707X MX40-715X MX40-717X VB-9315-0-4-X 15 to 32 mm AV-603 — — — AV-605 — — — VB-9315-0-4-X 40 to 50 mm — — — — — — — — VB-9315-0-4-X 65 to 80 mm — — — — — — — — VB-9323-0-4-X 1/2 to 1-1/4 in. AV-603 — — — AV-605 — — — VB-9323-0-4-X 1-1/2 & 2 in. — — — — — — — — VB-9323-0-5-X 2-1/2 & 3 in.
Valve Body Part Number Pneumatic Valve Sizes MU-4810X MUP-4610X MUP-4710X MUP-4820X MK-2690 MK-46X1 MK-47X1 (Obsolete) MK-48X1 (VB-9XXX only) MK-66XX (1/2 in. stroke) MK-68X1 (MK-69X1 is only used on VB-817 & VB-9323, 4 to 6 in.) MK-88XX (2-1/2 to 4 in.) MK-89XX (5 & 6 in.) ⎯ VB-7211-0-4-X 1/2 to 1-1/4 in. ⎯ ⎯ ⎯ AV-7400 AV-401 ⎯ ⎯ ⎯ ⎯ ⎯ VB-7212-0-4-X 5/8 in. O.D. ⎯ ⎯ ⎯ AV-7400 AV-401 ⎯ ⎯ ⎯ ⎯ ⎯ ⎯ VB-7213-0-4-X 1/2 to 2 in.
F-27414-1 ACTUATOR PART NUMBER Electric/Electronic Valve Body Part Number Pneumatic Valve Sizes MU-4810X MUP-4610X MUP-4710X MUP-4820X MK-2690 MK-46X1 MK-47X1 (Obsolete) MK-48X1 (VB-9XXX only) MK-66XX (1/2 in. stroke) MK-68X1 (MK-69X1 is only used on VB-817 & VB-9323, 4 to 6 in.) MK-88XX (2-1/2 to 4 in.) MK-89XX (5 & 6 in.) ⎯ 1-1/2 & 2 in. AV-394 AV-392 AV-394 ⎯ ⎯ AV-430-0-0-1 AV-420 ⎯ AV-430-0-0-1 ⎯ VB-9225-0-4-X 15 to 80 mm.
Valve Linkages Application For assembling electric gear train actuators to valve bodies. The AV-390 through AV-396 linkages are used to field assemble TAC gear train actuators and VB-9XXX and VB-7XXX series of valve bodies. Valve AV-29, AV-30, AV-9X Series , Linkages AV-300, AV-347, AV-39X Series Electric/Electronic Valve Linkage Kits Features: • Die case aluminum mounting bracket. • Valve position indication provided as standard.
Valve Linkages AV-352 Application The AV-352 valve linkage is used to field-install gear train actuators on specified 2-1/2 to 6 in. valve bodies. Gear Train Actuator Valve Linkage Features: • Compatible with TAC (Barber-Colman) 2-1/2 to 6 in. valves. • Provides increased close-off pressure on 2-1/2 to 4 in. valves. • Required for rated close-off pressure on 5 and 6 in. valves. Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body.
Valve Linkages AV-401 Application For assembling MK-46XX Series pneumatic actuators to specific 1/2 to 2 in. VB-7XXX valve bodies. Pneumatic Actuator Valve Linkage Kit Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body. Actuator Effective Area Spring Range psig (kPa) 11 sq. in. (21 cm2) MK-4601 3 to 6 (21 to 41) MK-4611 5 to 10 (34 to 69) MK-4621 10 to 13 (69 to 90) AV-430 Application For assembling MK-6800 Series 50 sq. in.
Valve Linkages AV-496 Application For assembling pneumatic actuators to 2-1/2 to 6 in. valve bodies. Pneumatic Valve Linkage Kit Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body. Actuator AV-496 2-1/2 to 6 in.
Valve Linkages AV-601 Application The AV-601 valve extension kit is used to increase the allowable ambient temperature range of MA, MF, MP-5X1X-XXX, MPR-5X1X and MP-541X Series actuators. The MF-5X1X, MP-541X, and MPR-5X1X Series of actuators require the AV-601 extension. This kit provides thermal insulation between the valve and the actuator. It does not insulate the actuator from radiant or convective heat transfer.
Valve Linkages AV-603 Application The AV-603 linkage is designed to link the TAC MF40-6043 and MS40-6043 actuators to 1/2” through 2”, 2-way or 3-way globe valves. Globe Valve Linkage Kit Specifications • Motor mounting: In any upright position with motor above center line of the valve body.
Valve Linkages AV-631 Application For assembling MM/ MMR-400 or MM/ MMR-500 Series to specific Honeywell valve bodies.
Valve Linkages AV-632 Application For mounting MM-400/500 modular actuator to Honeywell Q618A and Johnson Y20EBD valve linkages. Adaptor Kit The kit is also used to mount Honeywell Q607 auxiliary switch and Q181A auxiliary potentiometer kits to MM-400/500 modular actuators. AV-641 Application The AV-641 Valve Linkage is designed for mounting MF-22XX3 series Floating Electric and MS-22353 Proportional actuators onto TAC series valve bodies.
Valve Linkages AV-644 and AV-644-10 Application The AV-644 Valve Linkage is designed for mounting MF-22XX3 series Floating Electric and MS-22353 Proportional actuators onto TAC series valve bodies. Valve Linkage Kit Features: • Provides direct couple interface between actuators and valve bodies. Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body. • Replaces AV-643 Valve Linkage (plastic). Note: AV-644-10 includes the drive screw.
Valve Linkages AV-671 Application For mounting MF-60000 Series actuators on 1/2- 2 in VB-7000 and VB-9000 valves. Electric/Electronic Valve Linkage Kit Features: • Provides direct couple interface between actuator valve. Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body. AV-672 Application For mounting MF-60000 Series actuators on 2-1/2, 3, or 4 in. VB-921X and VB-931X valves.
Valve Linkages AV-673 Application For mounting selected TAC actuators on Johnson Controls 1/2 through 2 in. VB-3754, VB-3924, and VB-4324 valves. Electric/Electronic Valve Linkage Kit Features: • Provides direct couple interface between MF-631X3 actuator and 1/2 through 2 in. Johnson Controls VB-3754, VB-3924, and VB-4324 valves. Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body.
Valve Linkages AV-674 Application For mounting selected TAC actuators on 1/2 to 3 in. Honeywell 3/4 in. stroke valves. Electric/Electronic Valve Linkage Kit Features: • Provides direct couple interface between MF-631X3 actuator and 1/2 to 3 in. Honeywell 3/4 in. stroke valve. Specifications • Actuator mounting: In any upright position with actuator above the center line of the valve body. Close-Off Rating Two-Way Valves Honeywell Valve Body Size in.
Valve Linkages AV-680 Application The AV-680 linkage is used to mount the MS-7913 and MS-7923 model actuators to 1-1/2 to 2 in. VB-7XXX globe valve bodies. Electric/Electronic Valve Linkage Kit Specifications • Parts needed to mount MX-7913 and MX-7923 actuators to aa VB-7XXX valves. • If fluid temperatures exceed 300°F (150°C), mount actuator above horizontal, but at least 45° from vertical.
Valve Linkages AV-7400 Application The AV-7400 valve linkage kit is used to field-install MK-2690 pneumatic actuators to a variety of VB-7XXX series 1/2 through 2 in. valve bodies. Pneumatic Actuator Valve Linkage Kit Features: • Springs are provided for all control signal applications, including 3 to 7, 5 to 10, and 8 to 13 psig. • Kit fits all VB-7XXX series valve bodies. • Blue spring used with AV-7600-1 supports hydraulic 4-20 mA and 0-10 Vdc applications.
Valve Linkages 206 © Copyright 2006 TAC. All Rights Reserved.
Malmö, Sweden Phone: + 46 40 38 68 50 Rockford, IL +1 888 444 1311 Singapore +65 6776 3166 http://www.schneider-electric.com/buildings F-27414-3 On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes.