User Guide

F-27087-6 Copyright 2010 Schneider Electric All Rights Reserved. 7
Insulation of Ball Valve Assembly
The ball valve should be completely insulated to minimize the effect of heat transfer and
condensation at the actuator.
Caution: The actuator itself must not be insulated. Doing so can result in excess heat or
condensation within the actuator.
Temperature Limits for Ball Valve Assembly
When installing the ball valve assembly, observe the minimum and maximum temperature
limits, given below (Table-2).
Installation of Ball Valve Assembly
Mount the valve assembly in the piping according to Figure-5.
Notes:
2-way ball valves containing characterized inserts must be piped in the direction of the
arrow on the side of the valve body.
2-way spring return ball valve assemblies are shipped either normally open, voltage rise
to close (actuator code 53x), or normally closed, voltage rise to open (actuator code
52x).
Spring return 3-way ball valve assemblies are shipped either A to AB closed, voltage
rise to open (actuator code 52x), or A to AB open, voltage rise to close (actuator code
53x).
All 2-way non-spring return ball valve assemblies are shipped open, voltage rise to
close.
All non-spring return 3-way ball valve assemblies are shipped A to AB open, voltage rise
to close.
Mount the valve in a weather-protected area, in a location that is within the ambient
temperature limits of the actuator.
When selecting a location, allow sufficient clearance on all sides to allow for any
maintenance that may be needed. Refer to Ball Valve Assemblies and Ball Valve Body
/Linkage Assemblies Selection Guide, F-27086, for dimensions.
Mount the valve assembly so that the actuator is above the horizontal, relative to the
valve. This ensures that any condensate that forms on the valve body will not travel
into the actuator, where it may cause corrosion or electrical malfunction.
Table-2 Ambient Temperature Limits for Ball Valves Assemblies and Actuators.
Ambient Temperature For
Temperature Limits
Minimum °F (°C) Maximum °F (°C)
Valve Fluid (water) 20 (-7) 250 (121)
Mx41-6043
Mx41-6083
Storage -40 (-40) 158 (70)
Operating -25 (-32) 130 (55)
Mx40-704x
Storage -40 (-40) 160 (71)
Operating -22 (-30) 140 (60)