User Guide

F-27086-7 Copyright 2007 TAC All Rights Reserved. 21
Valve Assemblies with Mx40-704x Spring Return TAC DuraDrive Actuators
Note:
The Ball Valve Assemblies use the basic Mx41-6043, Mx41-6083, and Mx40-704x TAC DuraDrive actuators.
Specifications for actuators containing auxiliary switches are also provided here. Ball valve assemblies using the
switch-equipped actuators may be field-assembled using ball valve body/linkage assemblies (VB-2x13-500-9-xx).
Actuator Specifications
Inputs
Control Signal MA40-704x: ON/OFF SPST control contacts or Triacs (500 mA rated)
MS40-7043: Proportional, 2 to 10Vdc or 4 to 20 mAdc with 500 Ohm resistor.
MS40-7043 MP/MP5: Proportional 6 to 9 Vdc.
MF40-7043: Floating point control, 24 Vac.
Power Requirements All 24 Vac circuits are Class 2.
Connections MA40-704x and MA40-704x-501: 3 ft. (0.9 m) long, appliance cable, 1/2 in. conduit
connector. For M20 Metric conduit, use AM-756 adaptor.
MF40-7043 and MF40-7043-501, MS40-7043 and MS40-7043-501: 3 ft. (0.9 m) long,
plenum rated cable, 1/2 in. conduit connector. For M20 Metric conduit, use AM-756 adaptor.
Motor Type MA40-704x: Brush DC.
MF40-7043, MS40-7043: Brushless DC.
Outputs
Electrical Auxiliary Switches: Available when actuators are ordered as separate units. Auxiliary
switches are not offered with factory ball valve assemblies.
Position Feedback Voltage: 2 to 10 Vdc (maximum 0.7 mA) output signal for position
feedback or operation of up to four slave actuators.
Control Mode: Switch provided for selection of direct acting or reverse acting control mode on
proportional models.
Timing: MA-704x — Approx. 50 sec.; MF- and MS-7043 — Approx. 130 sec.
Auxiliary Power Supply: MS40-7043-MP and MS40-7043-MP5 — +20 Vdc @ 25 mA (max.)
Mechanical Stroke: Angle of rotation is limited to a maximum of 95°, with mechanical stop.
Output torque rating: Mx40-704x — 35 lb-in (4 N-m)
Position indicator: Visual scale numbered from 0 to 90°, provided for position indication.
Environment
Temperature Limits Shipping and storage: -40 to 160 °F (-40 to 71 °C) ambient.
Operating: -22 to 140 °F (-30 to 60 °C) ambient.
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 2 (IEC IP54)
Agency Listings (Actuator)
UL UL 873, Underwriters Laboratories (File #9429 Category Temperature-Indicating and
Regulating Equipment).
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
cUL Canadian Standards C22.2 No. 24.
Australia This product meets requirements to bear the C-Tick Mark according to the terms specified by
the Communications Authority under the Radiocommunications Act 1992.
Part Number
Voltage
50/60 Hz
Voltage
Vdc
Running Holding
50 Hz 60 Hz 50 Hz 60 Hz
VAWVAWWW
MA40-7043 24 Vac ± 20% 22 to 30 4.4 2.9 4.4 2.9 0.8 0.8
MS40-7043 24 Vac ± 20% 22 to 30 5.6 4.2 5.6 4.2 2.4 2.4
MF40-7043 24 Vac ± 20% 22 to 30 5.9 4.4 5.9 4.4 2.9 2.9
MS40-7043-MP 24 Vac ± 20% 22 to 30
6.9 5.0 6.6 5.0 3.2 3.2
MS40-7043-MP5 24 Vac ± 20% 22 to 30
MA40-7040 120 Vac ± 10% 6.4 3.8 4.3 3.4 1.6 1.2
Mx40-7043-501 and MS40-7043-MP5
One auxiliary switch available. SPDT 6 A
resistive @ 24 Vac, adjustable 0 to 95° (0 to 1
scale). Switch meets VDE requirements for
6 (1.5) A, 24 Vac.
MA40-7040-501
One auxiliary switch available. SPDT 6 A
resistive @ 250 Vac, adjustable 0 to 95° (0 to
1 scale). Switch meets VDE requirements for
6 (1.5) A, 250 Vac.