Environment
Temperature Limits Shipping and storage: -40 to 160 °F (-40 to 71 °C) ambient.
Operating: -22 to 140 °F (-30 to 60 °C) ambient.
Humidity 15 to 95% RH, non-condensing.
Locations NEMA 1. NEMA 2, UL Type 2 (IEC IP54) with customer-supplied watertight conduit
connectors. Enclosure is air plenum rated.
Agency Listings (Actuator)
UL UL 873, Underwriters Laboratories (File #9429 Category Temperature-Indicating and
Regulating Equipment). Plenum rated.
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). This product fits into
Installation Category (Overvoltage Category) II per EN 61010-1.
cUL Canadian Standards C22.2 No. 24-93.
Australia This product meets requirements to bear the C-Tick Mark according to the terms specified by
the Communications Authority under the Radiocommunications Act 1992.
2-Way Ball Valve Assembly Dimensions
Valve Assembly
Part Number
Valve Size
in.
P
Code
a
a
To find the corresponding flow coefficients for these port codes, refer to "Port Codes for TAC DuraDrive Ball Valve Assemblies" on page 6.
Valve Dimensions in inches (millimetres) (Refer to Figure-9)
ABCD
2-Way
VA-2213-815-9-P
thru
VA-2213-818-9-P
VA-2213-821-9-P
VA-2213-831-9-P
VF-2213-821-9-P
VF-2213-831-9-P
VS-2213-821-9-P
thru
VS-2213-839-9-P
1
21, 23 3-1/16 (78) 7 (178) 8-1/2 (216) 3 (76)
22, 25 3-3/4 (95) 7-3/8 (188) 8-3/16 (208) 2-7/8 (72)
24, 26 4-5/16 (110) 7-5/8 (194) 9-1/8 (231) 3-1/4 (82)
27 3-1/16 (78) 7-13/16 (200) 8-1/2 (216) 3 (76)
Actuator Specifications (Continued)
A
B
3-1/2 (89)
D
C
Figure-9 MA4D-703x, MF4D-703x, MS4D-703x, MA4D-803x, MF4D-803x, or MS4D-803x with 2-Way Ball Valve.