Valve/Actuator Combinations
2-Way Ball Valve Assemblies Using TAC DuraDrive Actuators
Note:
All valve sizes — ANSI Class IV (0.01% of C
v
) shut-off
Table-4 Selection Chart—2-Way Ball Valve Assemblies with TAC DuraDrive Actuators.
2-Way Ball Valve Assemblies with TAC DuraDrive Non-Spring Return
a
a
Non-spring return 2-way ball valve assemblies are shipped open, voltage rise to close.
Spring Return
Actuator Models (Actuator Codes)
24 Vac 24 Vac 24 Vac
Floating
MF41-6043 (505)
Proportional
MS41-6043 (505)
Floating
MF41-6083 (506)
Proportional
MS41-6083 (506)
Two-Position
MA40-7043 (N.C.) (526)
MA40-7043 (N.O.) (536)
Floating
MF40-7043 (N.C.) (526)
MF40-7043 (N.O.) (536)
Proportional
MS40-7043 (N.C.) (526)
MS40-7043 (N.O.) (536)
120 Vac
Two-Position
MA40-7040 (N.C.) (522)
MA40-7040 (N.O.) (532)
Valve Assembly
Part Number
Valve Size
(in.)
P
Code
b
b
To find the corresponding flow coefficients for these port codes, refer to "Port Codes for TAC DuraDrive Ball Valve Assemblies" on page 6.
Close-Off Pressure, psi (kPa)
Ball
Valve Assembly
with TAC DuraDrive
Vx-2213-5xx-9-P
c
Valve/Linkage
Assembly
VB-2213-500-9-P
c
To determine a specific part number, identify the actuator’s control signal type (“A,” “F,” or “S”), actuator code, and P code. Refer to "Part Numbering System" on
page 4.
1
21, 22, 23, 24,
25, 26, 27
100 (689)
(field assemble
d
)
d
Factory assemblies not available. Purchase actuator and VB-2213-500-0-xx valve body/linkage and field assemble.
—
100 (689)
(field assemble
d
)
1-1/4
41. 42, 43, 44,
45, 46
70 (482)
(field assemble
d
)
— 70 (482)
1-1/2 51, 52, 53, 54 —
70 (482
(field assemble
d
)
70 (482)
2
61, 63, 65, 66,
67
—
70 (482)
(field assemble
d
)
70 (482)
2-1/2
71, 72, 73, 74,
75, 76
—
70 (482)
(field assemble
d
)
70 (482)
3 82, 85 —
70 (482)
(field assemble
d
)
70 (482)
Vx-2213-505-9-P
Vx-2213-5xx-9-P