Installation
Inspect the package for damage. If damaged, notify the appropriate carrier
immediately. If undamaged, open the package and inspect the device for
obvious damage. Return damaged products.
Requirements
Tools (not provided): Pipe wrenches•
Training: Installer must be a qualified, experienced technician•
Appropriate accessories•
Caution
Install the valve with the flow in the direction of the flow arrow(s). See Table •
One for details on flow.
Do not exceed the ratings of the device.•
Avoid locations where excessive moisture, corrosive fumes or vibration are •
present.
Mounting
The valve should be mounted in a weather protected area, if the actuator 1.
is not rated for outdoor use, in a location that is within the ambient limits of
the actuator. When selecting a location, allow sufficient room for the valve,
linkage, actuator, and other accessories and for service of the product.
The preferred mounting position for the valve is with the valve stem vertical 2.
above the valve body. Avoid mounting the valve so that the valve stem is
below horizontal.
For steam applications only, position the valve body so the valve stem and 3.
actuator are at 45° from vertical.
The two-way valves must be piped with the “A” port as the inlet and the 4.
“AB” port as the outlet. Mixing valves must be piped with two inlets ( “A”
and “B” ports) and one outlet (“AB” port). Diverting valves must be piped
with one inlet (“B” port) and two outlets (“A” and “AB” ports).
Valve-specific instructions are available on pages 2 and 3. 5.
Checkout
Make sure the valve stem operates smoothly before installing the valve 1.
linkage and the actuator.
If the stem does not operate smoothly, it may indicate that the valve was 2.
twisted or crushed during installation or that the stem was bent by rough
handling. These conditions may require that the valve be replaced.
After the piping is under pressure, check the valve body and the connec-3.
tions for leaks.
After the valve linkage and the actuator are installed, check their opera-4.
tion. Allow valve to move full stroke, ensure performance per Table One.
!
Danger
Do not use for combustible gas applications. The valve •
packings are not rated for combustible gas applications, and
if used in these applications, gas leaks and explosions may
result.