User Guide

4 © Copyright 2010 Schneider Electric All Rights Reserved. F-27194-5
Table-2 Typical Compatible Actuators and Linkages
Actuator Series Control Signal Type Spring Return
Required Valve Linkage
Normal
Position
2-1/2” to 5"
Valves
6" Valves
MA61-7200 Two Position 120 Vac Yes None
a
—Closed
MA61-7201 Two Position 230 Vac Yes None
a
—Closed
MA61-7203 Two Position 24 Vac Yes None
a
—Closed
MA41-7150 Two Position 120 Vac Yes AV-607 AV-609 Closed
b
MA41-7151 Two Position 230 Vac Yes AV-607 AV-609 Closed
b
MA41-7153 Two Position 24 Vac Yes AV-607 AV-609 Closed
b
MA40-7170 Two Position 120 Vac Yes AV-607 AV-609 Closed
b
MA40-7171 Two Position 230 Vac Yes AV-607 AV-609 Closed
b
MA40-7173 Two Position 24 Vac Yes AV-607 AV-609 Closed
b
MF-63103 Floating 24 Vac No AV-672 None
MF-63123 Floating 24 Vac
c
No AV-672 None
MF-63123-211 Proportional Vdc
d
No AV-672 None
MF-63123-411 Proportional mAdc
e
No AV-672 None
MF41-6343
Floating 24 Vac
No AV-609 None
MF41-7153
Yes
AV-607 AV-609 Closed
b
MF40-7173
MF61-7203 None
a
—Closed
MK-6811
f
Pneumatic 5 to 10 psig
f
Yes AV-497 Closed
MK-6911 with AK-42309-500
g
Pneumatic 5 to 10 psig
g
Yes AV-497 Closed
MS41-7153 Proportional 2 to 10 Vdc
h
Yes AV-607 AV-609 Closed
MS40-7170
Proportional 2 to 10 Vdc
h
Yes AV-607 AV-609 Closed
b
MS40-7171
MS40-7173
MS41-6340
Proportional 2 to 10 Vdc
h
No AV-609 NoneMS41-6341
MS41-6343
MS61-7203 Yes None
a
—Closed
a
a
Linkage integral to actuator.
b
As shipped from factory. May be field configured for normally open (spring return stem down).
c
MFC-8000 and MFC-420 plug-in control modules may be field installed for proportional control.
d
MFC-8000 control module factory installed, set for 6 to 9 Vdc, 1” (25 mm) stroke.
e
MFC-420 control module factory installed, set for 4 to 20 mAdc, 1” (25 mm) stroke.
f
AK-42309-500 positive positioner may be ordered separately and field adjusted for other ranges. Order a VK4 valve assembly for factory-installed positive
positioner.
g
AK-42309-500 positive positioner must be used with MK-6911 on 6” VB-8223. Order separately. May be field adjusted for other ranges. Order a VK4 valve
assembly for factory-installed positive positioner.
h
May be field configured for 4-20 mAdc.