INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS J17A2 J17L2 J24A2 J24L2 J30A2 J30L2 J36A2 J36L2 J42A2 J42L2 J48A2 J48L2 J60A2 J60L2 J70A2 J70L2 Manual : Supersedes: File: Date: 2100-588A 2100-588 Volume III Tab 16 03-05-14 Manual Page 2100-588A 1 of 29
Contents Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature............................... 4 Shipping Damage...................................................... 4 General .................................................................. 4 Duct Work.................................................................. 5 Filters .................................................................. 5 Fresh Air Intake.........................................
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. FOR MORE INFORMATION, CONTACT THESE PUBLISHERS: ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W.
WALL MOUNT GENERAL INFORMATION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE J 42 A – A REVISIONS MODEL NUMBER CAPACITY 17 - 1½ Ton 24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton 70 - 6 Ton 2 10 X X X X J CONTROL MODULES (See Spec.
DUCT WORK FILTERS All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. A two-inch pleated filter is standard with each unit.
INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION WARNING 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figures 3A-3C. 2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. 3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
FIGURE 2 Dimensions of Basic Unit for Architectural and Installation Requirements (Nominal) SUPPLY RETURN MODEL WIDTH (W) DEPTH (D) HEIGHT (H) R S T J17A, L J24A, L 33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 11.00 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 4.19 12.00 5.00 J30A, L J36A, L 38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 11.00 25.75 17.93 26.75 28.75 29.25 27.00 2.75 39.19 22.75 9.14 4.19 12.00 5.00 J42A, L J48A, L J60A, L J70A, L 42.075 22.
Manual 2100-588A Page 8 of 29 13 3 16 " 5" 12" 12" 12" 12" 12" 4" Typ. 1" 20" 1 1 7 16 " 2" 38" 4" Typ. Return Opening Supply Opening 20" Wall Opening and Hole Location View 2" 7 8" 3" 1 7 16 " 1" 12" 1 20 2 " 8" WALL TOP HEATER ACCESS PANEL SEAL WITH BEAD OF CAULKING ALONG ENTIRE LENGTH OF TOP. FIGURE 3A J17A2, J17L2, J24A2, J24L2 MOUNTING INSTRUCTIONS Right Side View MIS-3157 W**A UNIT SHOWN, W**L UNIT CONTROLS AND HEATER ACCESS IS ON OPPOSITE (LEFT) SIDE.
Manual 2100-588A Page 9 of 29 E 11 4 16 " 5 16 " 1 12" 7 8" 4" Typ. C E B 11 4 16 " 14" Wall Opening and Hole Location View 4" Typ. 7 8" 1 38" 28" 12" 7 28" Return Opening Supply Opening A 12" 12" 12" D C 7 8" WALL 4 5/8 4 7/16 16 7/8 D REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM 29 7/8 9 7/8 COMBUSTIBLE MATERIALS C 5 3/8 3 11/16 17 5/8 B REQUIRED DIMENSIONS TO MAINTAIN 28 3/8 8 3/8 1/4" MIN.
Manual 2100-588A Page 10 of 29 2 7 18" 16" 16" 16" 16" 16" 1 1 4" Typ. 1 1 62" 38" C 5 1/2 6 1/4 C Dimension is 21" on 95" tall units. Dimension is 10" on T48H1 & T60H1. Dimension is 6" on T48H1 & T60H1. 4" Typ. 1" 3" 30" Return Opening Supply Opening A 12 10 1/2 B Wall Opening and Hole Location View 3 2 1 1 62" 1 62" C 32 REQUIRED DIMENSIONS TO MAINTAIN RECOMMENDED 1" CLEARANCE FROM COMBUSTIBLE MATERIALS D 30 1/2 REQUIRED DIMENSIONS TO MAINTAIN 1/4" MIN.
FIGURE 4 ELECTRIC HEAT CLEARANCE J30A2, J30L2, J36A2, J36L2, J42A2, J42L2, J48A2, J48L2, J60A2, J60L2, J70A2, J70L2 NOTE 1: SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURES 3A-3C – MOUNTING INSTRUCTIONS FACTORY SUPPLIED RAIN FLASHING. MOUNT ON UNIT BEFORE INSTALLATION WALL STRUCTURE SUPPLY AIR OPENING SUPPLY AIR OPENING SUPPLY AIR DUCT RETURN AIR OPENING RETURN AIR OPENING RETURN AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT.
FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN FLASHING RAFTERS RAIN FLASHING FINISHED CEILING SURFACE SUPPLY AIR DUCT SUPPLY AIR DUCT W/ GRILLE FINISHED CEILING SURFACE RETURN AIR OPENING W/ GRILLE RETURN AIR OPENING W/ GRILLE OUTSIDE WALL RAFTERS OUTSIDE WALL FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN FLASHING RAFTERS SUPPLY DUCT MA
WIRING – MAIN POWER WIRING – LOW VOLTAGE WIRING Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate.
24V TRANSFORMER OUTPUT 24V HOT COMPRESSOR ECONOMIZER STAGE 1 ECONOMIZER STAGE 2 ELECTRIC HEAT STAGE 1 ELECTRIC HEAT STAGE 2 N.C. CONTACT N.O.
FAN (BLOWER) 24V TRANSFORMER OUTPUT 24V HOT COMPRESSOR ECONOMIZER STAGE 1 ECONOMIZER STAGE 2 ELECTRIC HEAT STAGE 1 ELECTRIC HEAT STAGE 2 N.C. CONTACT N.O.
FAN (BLOWER) 24V TRANSFORMER OUTPUT 24V HOT COMPRESSOR ECONOMIZER STAGE 1 ECONOMIZER STAGE 2 ELECTRIC HEAT STAGE 1 ELECTRIC HEAT STAGE 2 N.C. CONTACT N.O.
START UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to ensure optimal system performance.
START UP (Continued) IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance wash the indoor coil with a dish washing detergent. All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. HIGH PRESSURE SWITCH All J**A/J**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch.
SEQUENCE OF OPERATION Alarm Relay Output COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. (See NOTE under Condenser Fan Operation if equipped with Low Ambient Control.) The G (indoor motor) circuit is automatically completed by the thermostat on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation.
TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS Shown in Figure 11 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to Table 1 for unit specific dimension. Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
TABLE 4 COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Model J17A/L J24A/L J30A/L J36A/L J42A/L J48A/L J60A/L J70A/L Return Air Temp (DB/WB) Pressure 75 80 85 90 95 100 105 110 115 120 75/62 Low Side High Side 124 321 126 340 128 362 130 384 132 409 133 434 135 461 137 490 138 521 140 553 80/67 Low Side High Side 133 329 135 349 137 371 139 394 141 419 142 445 144 473 146 503 148 534 150 567 85/72 Low Side High Side 138 341 140 361 142 384 1
TABLE 5 Electrical Specifications — J**A Series MODEL J17A2-A00,A0Z A05 A08 A10 J24A2-A00, A0Z A04 A05 A08 A10 J24A2-B00, B0Z B06 J24A2-C00, C0Z C06 J30A2-A00*, A0Z* A05* A08 A10* A15 J30A2-B00*, B0Z* B06 B09* B15 J30A2-C00*, C0Z* C06 C09* C15 J36A2-A00*, A0Z* A05* A08 A10* A15 J36A2-B00*, B0Z* B06* B09* B15 J36A2-C00*, C0Z* C06* C09* C15 J42A2-A00, A0Z A05 A10 A15 A20 J42A2-B00, B0Z B09 B15 B18 J42A2-C00, C0Z C09 C15 J48A2-A00, A0Z A05 A10 A15 A20 J48A2-B00, B0Z B09 B15 B18 J48A2-C00, C0Z C09 C15 J60A2-A
TABLE 6 Electrical Specifications — J**L Series MODEL J17L2-A00,A0Z A05 A08 A10 J24L2-A00, A0Z A05 A08 A10 J24L2-B00, B0Z B06 J24L2-C00, C0Z C06 J30L2-A00*, A0Z* A05* A08 A10* A15 J30L2-B00*, B0Z* B09* B15 J30L2-C00*, C0Z* C09* C15 J36L2-A00*, A0Z* A05* A10* A15 J36L2-B00*, B0Z* B09* B15 J36L2-C00*, C0Z* C09* C15 J42L2-A00, A0Z A05 A10 A15 J42L2-B00, B0Z B09 B15 J42L2-C00, C0Z C09 C15 J48L2-A00, A0Z A05 A10 A15 J48L2-B00, B0Z B09 B15 J48L2-C00, C0Z C09 C15 J60L2-A00, A0Z A05 A10 A15 J60L2-B00, B0Z B09 B15
TABLE 7 RECOMMENDED AIRFLOW Model Nominal Rated CFM * Nominal Rated ESP * Recommended Airflow Range Factory Speed Connection J17A, J17L 600 .40 550 - 725 Low J24A, J24L 800 .30 700 - 950 Single J30A, J30L 1000 .30 850 - 1300 High J36A, J36L 1100 .20 930 - 1350 High J42A, J42L 1400 .45 1600 - 1150 High J48A, J48L 1550 .30 1750 - 1285 High J60A, J60L 1700 .40 1950 - 1375 High J70A, J70L 1700 .20 1950 - 1375 High * Rated CFM and ESP on factory speed connection.
TABLE 10 ELECTRIC HEAT Models 240V-1 208V-1 KW Amps BTUH Amps BTUH 4 16.7 13650 14.4 10240 5 20.8 17065 18.1 12800 33.3 27300 28.8 20475 41.6 34130 36.2 25600 62.5 51250 54.0 38400 83.2 68260 72.1 51200 6 8 9 10 240V-3 208V-3 Amps BTUH Amps BTUH Amps BTUH 14.4 20500 12.5 15360 7.2 20500 21.7 30600 18.7 23030 10.8 30700 14.4 40950 36.2 51200 31.2 38400 18.0 51200 43.3 61430 37.
X EHWA03-A05 X X EHWA03-A08 X X EHWA03-A10 X X EHWA03-A15 X EHWA03-B06 X X EHW36A-B06 X EHWA03-B09 X EHWA37-B15 X X X EHWC03A-C06 X X EHWC03A-C09 X X EHWA03A-C12 X X EHWA03A-C15 X X EHWA05-A05 X X EHWA05-A10 X X X X EHWA05-A15 X X X X EHWA05-A20 X X X X EHWA05-B09 X X EHWA05-B15 X X X EHW05A-B18 X X EHWA05-B18 X X EHWA05A-C09 X X EHWA05A-C15 X X EHWA60-A05 X X X X EHW60A-B09 X X X EHW70A-B09 X CIRCUIT BREAKER (WMCB) & PULL DISCON
HEATER KITS X EHWA03-A08L X EHWA03-A10L X EHWA03-A15L X X X X EHWA03-B09L X EHWA37-B15L X X X EHWC03-C09L X X EHWA03-C15L X X EHWA05-A05L X X EHWA05-A10L X X X X EHWA05-A15L X X X X EHWA05-B09L X EHWA05-B15L X X X X X X EHWA05A-C09L X X X EHWA05A-C15L X X X EHWA60-A05L X X X EHWA60-B09L X CIRCUIT BREAKER (WMCB) & PULL DISCONNECT (WMPD) EHW70A-B09L X WMCB-01B X X WMCB-02B WMCB-03A X X WMCB-04B WMCB-05A X X X WMCB-05B X X WMCB-06B X WMCB-08A
Description BFAD-2 Barometric Fresh Air Damper - Standard X ECONWMS-E2 ECONWMT-E2 ECONWMT-T2 Economizer - School Version, Enthalpy Economizer - Bldg. Equipment, Enthalpy Economizer - Bldg. Equipment, DB Temp. X X X J42, J48, J60, J70 Part Number W30, J36 J17, J24 TABLE 12 VENT & CONTROL OPTIONS BFAD-3 Barometric Fresh Air Damper - Standard X ECONWMS-E3 ECONWMT-E3 ECONWMT-T3 Economizer - School Version, Enthalpy Economizer - Bldg. Equipment, Enthalpy Economizer - Bldg. Equipment, DB Temp.