INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS & LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS J18H1 J24H1 J30H1 J36H1 J42H1 J48H1 J60H1 Manual: Supersedes: File: Date: 2100-555 NEW Volume III, Tab 17 06-22-11 Manual Page 2100-555 1 of 30
Contents Getting Other Information and Publications Wall Mount General Information Wall Mount Model Nomenclature ............................ Shipping Damage .................................................... General ................................................................ Duct Work ................................................................ Filters ................................................................ Fresh Air Intake .......................................................
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. FOR MORE INFORMATION, CONTACT THESE PUBLISHERS: ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W.
WALL MOUNT GENERAL INFORMATION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE J 42 H 1 – A 10 X X X KW CAPACITY 18 - 1½ Ton 24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton VOLTS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3 X E CONTROL MODULES See Spec.
DUCT WORK FILTERS All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. A 1-inch throwaway filter is standard with each unit. The filter slides into position making it easy to service.
INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3A - 3C. 2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. 3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installed unit.
FIGURE 2 Dimensions of Basic Unit for Architectural and I nstallation Requirements (Nominal) MODEL WIDTH DEPTH HEIGHT SUPPLY (W) (D) (H) A B RETURN C B E F G I J K L M N O P Q R S T J18H1 J24H1 33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 18.50 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 5.00 12.00 5.00 J30H1 J36H1 38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 18.50 25.75 17.93 26.75 28.75 29.25 27.00 2.63 39.13 22.75 9.14 5.00 12.00 5.00 J42H1 J48H1 42.
Manual 2100-555 Page 8 of 30 FIGURE 3A J18H1, J24H1 MOUNTING INSTRUCTIONS
Manual Page 2100-555 9 of 30 FIGURE 3B J30H1, J36H1 MOUNTING INSTRUCTIONS
Manual 2100-555 Page 10 of 30 FIGURE 3C J42H1, J48H1, J60H1 MOUNTING INSTRUCTIONS
FIGURE 4 ELECTRIC HEAT CLEARANCE J30H1, J36H1, J42H1, J48H1, J60H1 SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURFACES. WARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 – MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 2, FOR ACTUAL DIMENSIONS IF REQUIRED IF REQUIRED Manual 2100-555 Page 12 of 30
FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS Manual Page 2100-555 13 of 30
TABLE 1 DIAGRAM TO USE WITH UNIT AND VENTS No Vents System Type Model Series Heat Pump Economiz er Electronic Programmable Electronic Programmable J**H 1 1 N/A 5 WIRING – MAIN POWER WIRING – LOW VOLTAGE WIRING Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
24V HOT COMPRESSOR C G R Y Y1 B SPARE EMERGENCY HEAT COMPRESSOR LOCKOUT OUTPUT USED WITH OUTDOOR THERMOSTAT VENTILATION INPUT W1 ELECTRIC HEAT STAGE 1 REVERSING VALVE FAN (BLOWER) UNIT 24V TERMINAL BLOCK 24V COMMON (GROUNDED) FIGURE 8 BASIC HEAT PUMP WITH OPTIONAL ELECTRIC HEAT NO ECONOMIZER W2 W3 E L DH 01 MIS-2977 Manual Page 2100-555 15 of 30
COMPRESSOR LOCKOUT OUTPUT USED WITH OUTDOOR THERMOSTAT VENTILATION INPUT Y1 EMERGENCY HEAT Y COOLING STAGE 2 R ELECTRIC HEAT STAGE 1 COMPRESSOR G COOLING STAGE 1 24V HOT C REVERSING VALVE FAN (BLOWER) UNIT 24V TERMINAL BLOCK 24V COMMON (GROUNDED) FIGURE 9 BASIC HEAT PUMP WITH OPTIONAL ELECTRIC HEAT WITH EIFM ECONOMIZER B W1 W2 W3 E L DH 01 1 2 4 2 5 YELLOW ORANGE BLACK 3 PURPLE PINK 1 EIFM ECONOMIZER WIRING HARNESS Manual 2100-555 Page 16 of 30 BLACK BLUE MIS-2978 1 R
COMPRESSOR G R Y 1 COOLING STAGE 1 ELECTRIC HEAT STAGE 1 COOLING STAGE 2 EMERGENCY HEAT COMPRESSOR LOCKOUT OUTPUT USED WITH OUTDOOR THERMOSTAT B W1 W2 W3 E L DH YELLOW RED BLACK ECONWMT ECONOMIZER WIRING HARNESS VENTILATION INPUT (USED IF MINIMUM POSITION REQUIRED FOR VENTILATION) REVERSING VALVE Y1 YELLOW/RED 24V HOT C PURPLE BLUE FAN (BLOWER) UNIT 24V TERMINAL BLOCK 24V COMMON (GROUNDED) FIGURE 10 BASIC HEAT PUMP WITH OPTIONAL ELECTRIC HEAT WITH ECONWM ECONOMIZER 01 1 PINK BROWN/WHIT
START UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POLYOL ESTER OIL. REMEMBER: When adding R-410A refrigerant, it must come out of the charging cylinder/tank as a liquid to avoid any fractionation, and to insure optimal system performance. Refer to instructions for the cylinder that is being utilized for proper method of liquid extraction. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3.
START UP (Continued) IMPORTANT INSTALLER NOTE PHASE MONITOR For improved start up performance wash the indoor coil with a dish washing detergent. All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal. HIGH & LOW PRESSURE SWITCH All J**H wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch.
SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. HEATING – A 24V solenoid coil on reversing valve controls heating cycle operation.
FIGURE 11 DEFROST CONTROL BOARD LOW PRESSURE BYPASS TIMER SWITCH (FACTORY SETTING 120 SECONDS) SW SW 1 2 TIME (SEC) OFF OFF 30 ON OFF 60 OFF ON 120* ON ON 180 COMPRESSOR ANTI-SHORT CYCLE TIMER (FACTORY SETTING 60 MIN.
TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. NOTE: A thorough understanding of the defrost cycle sequence is essential. Review that section earlier in this manual prior to troubleshooting the control. Turn on AC power supply to unit. 2. Turn thermostat blower switch to “fan on” – the indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.) 3. Turn thermostat blower to “auto” position. Indoor blower should stop.
CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open. 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part is ± 10%.) 4. If sensor resistance reads very low, then sensor is shorted and will not allow proper operation of the heat pump control. 5.
TROUBLESHOOTING FAN BLADE SETTING DIMENSIONS Shown in Figure 12 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to Table 5 for unit specific dimension. Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
TABLE 7 COOLING PRESSURE TABLE Model J18H1 J24H1 J30H1 J36H1 J42H1 J48H1 J60H1 Air Temperature Entering Outdoor Coil °F Return Air Temperature Pressure 75 deg. D B 62 deg. WB Low S i de High Side 132 292 134 311 137 332 138 353 140 376 142 400 144 424 146 450 148 477 150 505 80 deg. D B 67 deg. WB Low S i de High Side 141 299 143 319 146 340 148 362 150 386 152 410 154 435 156 462 158 489 160 518 85 deg. D B 72 deg.
TABLE 9 Electrical Specifications — J**H Series Si ngle C i rcui t Model J18H1- A00, A0Z A 04 3 A 08 J24H1- A00, A0Z A 04 3 A 08 J24H1- B00, B0Z B 06 J24H1- C 00, C 0Z C 06 J30H1- A00, A0Z* A 05* 3 A 10* J30H1- B00, B0Z* B 06 3 B 09* J30H1- C 00, C 0Z* C 06 3 C 09* C 15 J36H1- A00, A0Z* A 05 3 A 10* 5 A 15 J36H1- B00, B0Z* B 06 3 B 09* 5 B 15 J36H1- C 00, C 0Z* C 06 3 C 09* C 15 J42H1- A00, A0Z A 05 3 A 10 5 A 15 J42H1- B00, B0Z B 06 3 B 09 5 B 15 J42H1- C 00, C 0Z C 06 3 C 09 5 C 15 J48H1- A00, A0Z A 04 A
TABLE 10 RECOMMENDED AIRFLOW Model Rated C FM * Rated ESP * Recommended Airflow Range Factory Speed Connection J1 8 H 600 1 .30 575 - 725 High J2 4 H 800 .20 700 - 950 High J3 0 H 1000 .40 930 - 1300 High J3 6 H 1100 .30 930 - 1350 High J4 2 H 1400 .30 1600 - 1150 High J4 8 H 1550 .20 1750 - 1285 High J6 0 H 1650 .30 1950 - 1375 High * Rated CFM and ESP on high speed tap. 1 Rated CFM and ESP on low speed tap. TABLE 11 INDOOR BLOWER PERFORMANCE E.S.P. In H 2O .0 .1 .
TABLES 12 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Front Outlet Model Model S p eed K W Model ESP J18H1 J24H1 A 00 A 04 A 08 .50 .50 .40 J24H1 B 00 B 06 .50 .50 J24H1 C 00 C 06 .50 .50 Top Outlet Low S p eed High S p eed Low S p eed High S p eed J30H1 J36H1 A 00 A 05 A 10 A 15 .50 .40 .35 .35 .50 .50 .40 .40 .50 .40 .25 NA .50 .50 .40 NA J30H1 J36H1 B 00 B 06 B 09 B 15 .50 .40 .35 .35 .50 .50 .45 .45 .50 NA .30 NA .50 NA .40 NA J30H1 J36H1 C 00 C 06 C 09 C 15 .50 .50 .
EHWH02A-A04 X EHWH02A-A08 X EHW24H-A04 X EHW24H-A08 X EHW24H-B06 EHWH30-A05 X EHWH30-A10 X EHWH36-A05 X EHWH36-A10 X EHWH36-A15 X J60H1-C J60H1-B J60H1-A J48H1-C X EHW36H-B06 X EHWH03-B09 X X EHW30H-B15 X EHWC03A-C06 X X EHWH42-A05 X X EHWH42-A10 X X EHWH42-A15 X X EHWH-04-A20 X X EHWH05-B06 X X EHWH05-B09 X X X EHWH05-B15 X X X EHWH42-C06 X EHWH05A-C09 X X X EHWH05A-C15 X X X EHWH04-A15 X EHWH04-A10 X EHW05H-B18 CIRCUIT BREAKER (WMCB) &
Manual 2100-555 Page 30 of 30 J42, J48, J60 Part Number Description J18, J24 J30, J36 TABLE 15 VENT & CONTROL OPTIONS BFAD-2 Barometric Fresh Air Damper - Standard X EIFM-2B Economizer X BFAD-3 Barometric Fresh Air Damper - Standard X EIFM-3C Economizer X BFAD-5 Barometric Fresh Air Damper - Standard X EIFM-5C Economizer X