Operating instructions

Manual 2100-422G
Page 12 of 42
OIL LINE PIPING
First determine whether the pipe system is to be a
single line system or a two line system. All
connections must be absolutely air tight or you will
have a malfunction of the burner. When installing the
piping, a good oil filter should be installed close to the
burner. A single line system is recommended for
gravity feed.
A typical single inside tank installations shown in
Figure 6. For installation details for this and other tank
configurations, refer to NFPA31 -- latest edition. All
tank and pipe setups must comply with NFPA31.
BECKETT AFG OIL BURNER
This furnace is equipped with a high static Beckett AFG
oil burner which is designed to produce adequate draft
in nearly any vertically vented application. The burner
employs the latest time tested controls of the highest
quality. The controls consist of a high voltage Beckett
solid state igniter, a Beckett “CleanCut” oil pump with
an integral solenoid valve, and a Beckett R7184B
primary control.
FIGURE 6
TYPICAL SINGLE INSIDE TANK INSTALLATION
6"
2" Cap
Vent Cap
2" Fill Pipe
1-1/4"
Vent Pipe
Return Line
Guage
Bushing,
2" x 1-1/2" or
1-1/4"
Oil Filter
3/8" O.D. Copper
Fuel Tubing
3/8" x 3/8"
Adapter
Gate Valve
3/8" x 4"
nipple
Bushing
Legs (either 1-1/4"x10"
or 1-1/2"x10" nipples)
Oil
Tank
MIS-1823