OPERATIONS MANUAL TELCOM CLIMATEWATCH SYSTEM MODEL TCS22-***-003 Manual: 2100-444-003A Supersedes: 2100-444-003 File: Vol.
Table Of Contents 1.0 INTRODUCTION ........................................................................................................... 1 1.1 Shipping Damage .........................................................................................................................1 1.2 Package Contents .........................................................................................................................1 1.3 Additional Requirements .............................................
.2.3 3.2.4 3.2.5 3.2.6 3.3 Wiring - Sensors ..................................................................................................................12 Wiring – Inputs & Outputs...................................................................................................13 Wiring - Telephone Line......................................................................................................14 Wiring - Ethernet ............................................................................
5.3.2 Unit Status Screen..................................................................................................................30 5.3.2.1 Unit #1 Economizer .............................................................................................................30 5.3.2.2 Unit #1 Compressor .............................................................................................................30 5.3.2.3 Unit #1 Heater.......................................................................
.3.6.5 5.3.6.6 5.3.7 50HZ Clock..........................................................................................................................44 Zone Humidity Sensor .........................................................................................................44 Password Operation...............................................................................................................45 5.4 Keyboard Map ..........................................................................
Table of Figures and Tables Figure 1 Front Cover ......................................................................................................................8 Figure 2 Control Location ............................................................................................................9 Figure 3 Mounting Template ....................................................................................................10 Table 1 Low Voltage Wire Size ...............................................
1.0 1.1 INTRODUCTION Shipping Damage Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the carrier immediately, preferably in writing, requesting inspection by the carrier's agent. 1.2 Package Contents 11111- 1.
All SOFTWARE supplied with this product is the property of Bard Manufacturing Co. You may not modify, disassemble, de-compile, reverse engineer, or create derivative works from this SOFTWARE. Bard Manufacturing Co. licenses the purchaser of this product to use two copies of this SOFTWARE on two computer systems, one remote computer system and one on site computer system. If installed on a network server, additional software licenses should be purchased for each computer on the network using the SOFTWARE.
1.5.4 SYSTEM POINTS TO BE CONTROLLED: Modem Power 1.5.5 WALLMOUNT POINTS TO BE CONTROLLED: Blower Unit #1 Economizer Unit #1 Compressor Unit #1 Heating Unit #1 Blower Unit #2 1.5.
INPUTS 1 Indoor Temperature Sensor 2 Indoor Humidity Sensor 3 -0 Unit #1 Blower Airflow Sensor -1 Unit #1 Compressor Lockout Relay -2 Unit #1 Dirty Filter Sensor 4 Unit #1 Discharge Air Sensor 5 Spare 6 Spare 7 Unit #1 Compressor Current Switch 8 Spare 9 Fire Trouble 10 Fire Alarm 11 Spare 12 Door Alarm 13 Main Power Sensor 14 Occupied Override Switch 15 Outdoor Temperature Sensor 16 Outdoor Humidity Sensor Required (Standard in TCS22) Optional (Optional in TCS22) Required (Standard in "V" Module) Required
1.6 Model Nomenclature TCS2 2 - H D M - 001 BASIC MODEL SOFTWARE REVISION NUMBER SENSORS H- Humidity & Temperature T - Temperature Only 2.0 2.1 ---- REMOTE COMMUNICATIONS DISPLAY M - With D - With X - Without X – Without E - Ethernet SPECIFICATIONS Electrical Specifications Supply Voltage 208/240 VAC +/- 10% 50/60 HZ Minimum Circuit Ampacity 3 Amp Overcurrent Protection Internal Circuit Breaker - 3 Amp 2.2 Controller Analog Inputs Resolution Voltage Range Current Rating 16 8 bits/ 0.
2.4 Sensor Specifications 2.4.1 TEMPERATURE SENSORS Indoor and Outdoor Type Ohms Temperature Range Interchangeability Thermistor 3000 Ω at 77o F (25o C) -40 to 302 o F (-40 to 150o C) .2 Deg Celsius Discharge 2.4.2 Type Ohms Temperature Range Interchangeability HUMIDITY SENSORS Type Output Supply Voltage Accuracy Sensitivity Repeatability Long Term Stability Interchangeability Temperature Range Humidity Range Thermistor 10000 Ω at 77o F (25o C) -40 to 302 o F (-40 to 150o C) .
2.4.5 BLOWER AIRFLOW SWITCH Type Output Supply Voltage Maximum Load Temperature Range Pressure Range Dimensions Mechanical Airflow Switch Form "C" Contact Self Powered 300 VA, at 24 VAC -40 to 180 o F (-40 to 82o C) 0.07 to 0.12 in. wc 6.125 high, 4.125 wide, 3.188 deep (156 mm. high, 105 mm. wide, 81 mm.
Figure 1 Front Cover 2100-444-003A Page 8
Figure 2 Control Location 2100-444-003A Page 9
Figure 3 Mounting Template 16.000 9.356 7.856 6.356 4.856 3.356 1.288 1.000 HIGH VOLTAGE WIRING 22.
3.0 INSTALLATION This section discusses mounting and wiring of the TCS22 into the building. Also included is an installation checklist to be completed by the installing contractor. See installation instructions supplied with the Bard Wall-Mount air conditioners for information on installing the air conditioners. This controller should be installed and serviced by a qualified service technician only. 3.
3.2.2 WIRING - LOW VOLTAGE IMPORTANT: High voltage wiring must not be run in the same conduit as low voltage control or sensor wiring. Failure to comply with this requirement will result in poor or no remote communication and/or in inaccurate sensor reading. Sixteen (16) wires should be run from each Bard Wall-Mount to the low voltage terminal block in the TCS22.
3.2.3.4 Zone Humidity Sensor (ZHS) (Optional) The Zone Humidity Sensor (ZHS) is supplied as part of the TCS22 package (Optional). The Zone Humidity Sensor (ZHS) is a bulk polymer type device. If so equipped, the sensor is premounted to the front door of the TCS22. No wiring is required. 3.2.
should close when door is closed. If a door switch is not used a jumper should be placed across this input. This is a dry contact input only. Do not connect any voltage source to these terminals. Do not connect utility power to these terminals. 3.2.5 WIRING - TELEPHONE LINE When the TCS22 is equipped with a modem, an analog phone line should be connected to the back of the modem in the jack labeled LINE. This jack accepts a standard a RJ-11 six (6) position modular phone plug. 3.2.
Figure 4 External Wiring 2100-444-003A Page 15
Figure 5 Internal Wiring Figure Power 6 2100-444-003A Page 16
Backup System 2100-444-003A Page 17
3.3 Installation Check List TCS22 securely mounted to wall and all conduit connections tight. Main power wiring is NOT in same conduit as low voltage or sensor wiring Main power wires are copper conductors TCS22 is grounded. Check supply voltage. Change both transformer taps if necessary. See Sec. 3.21 Carefully recheck all low voltage wiring for correct connection points . Carefully recheck all sensor connections for correct connection points.
3.4 System Startup 3.4.1 WALLMOUNT STARTUP CHECKLIST Operation Bypassing TCS22 Controller Apply power to both Wall-mounts Compressor Test Blower Test Economizer Test Heater Test Disconnect Power to WallMount AirConditioners Procedure Disconnect power to the TCS22. Unplug the plug in connectors J4 and J5 from the controller Follow recommended startup procedure in the WallMount installation instructions. Compressor damage could occur if startup procedures are not followed.
3.4.2 TCS22 STARTUP CHECKLIST Apply power to Apply power to WallMount air-Conditioners. Wait two minutes for WallMount airwallmount time delays to expire. Conditioners Apply power to TCS22 Apply power to TCS22 and monitor LEDs on the front of the controller. The controller performs a self test on startup. Upon application of power, 9 LEDs will light.
4.0 OPERATION This section describes the sequence of operation of the controller. The tools available for monitoring and controlling the air-conditioners for both on-site and remote operations are explained. The remote trending, alarming, and site setup software are detailed. 4.1 General This section will describe the sequence of operation of the controller. Cooling , heating, dehumidification, and alarm sequences are explained. 4.
4.2.4 OCCUPIED / UNOCCUPIED MODE SEQUENCE In heating mode, activation of the Occupancy Override Button will change the Active Heating Setpoint from Unoccupied Heating Setpoint to Occupied Heating Setpoint for a period of two hours. In cooling mode, activation of the Occupancy Override Button will change the Active Cooling Setpoint from Unoccupied Cooling Setpoint to Occupied Cooling Setpoint for two hours. 4.2.5 ALARM SEQUENCE The controller will alarm on the following failures.
Compressor Lockout Failure Unit #1 If Compressor operation is not verified because the High or Low Pressure Lockout Relay has been energized, Output 5, Unit #1 Compressor, is de-energized and locked out. A critical alarm is logged in the Event List and Output 12, Shelter Alarm, is energized. Lead unit switches to lag unit .The Output Alarm must be cleared to resume operation. Verify is tried 3 times before the output is locked out.
Door Alarm If Input #9,Door Alarm, is open for more than three minutes indicating an open door, a medium priority alarm is logged in the Event list and Output 12, Shelter Alarm, is energized. The door must be opened continuously for more than three minutes for the alarm to be logged. This is a self clearing alarm. 4.2.6 DEHUMIDIFICATION SEQUENCE Dehumidification Setpoint is compared to Space Humidity. If Space Humidity is above Dehumidification Setpoint , Stage 1 cooling is enabled.
4.2.10 SETPOINTS The default setpoint for all points are listed below. All setpoints are user changeable within the ranges listed.
cancels any operation. The double arrow LED is lit when the DAK is receiving or transmitting data normally. It will flash if there is a communication error. The DAK plugs into the 7040 controller through a pre-wired cord set. All communication signals are sent through this cord set to the DAK. The display and keypad (DAK) communicates with the 7040 controller via an RS485 communication bus using a proprietary communication protocol. The DAK will only function when plugged into the 7040 controller.
Enables Each of these screens has up to 32 lines of data in it. Study the Keypad Map in section 5.4 to become familiar with the menu tree structure. This is a handy reference and includes all keystrokes needed to get to any display or function. Pressing the key once from the Building Status screen will take you to the next screen, the Unit Status screen . The screen name will be displayed on the second line. Use the right and left arrows to scroll back and forth through the seven screens.
down respectively through the above screen showing four lines at a time. 5.3.1.1 ROOM TEMPERATURE The room temperature item displays the current temperature inside the structure. 5.3.1.2 ROOM HUMIDITY The room humidity item displays the current humidity inside the structure. This is an optional sensor and may or may not be present in your system. The current value will read one percent, "1 %" if no sensor is present. 5.3.1.
Setpoint will be 70o the same as the fixed Dehumidification Heating Setpoint. 5.3.1.7 FREE COOLING ON / OFF This display item indicates whether outside conditions are suitable to allow the use of outside air to provide free cooling inside the structure. The controller calculates the either outside temperature or enthalpy from the Outdoor Temperature and Outdoor Humidity and compares this value with the Free Cooling Setpoint. The Free cooling setpoint can be either a dry bulb temperature or enthalpy.
5.3.2 Unit Status Screen Authority Level Required to Make Changes - Does not apply. No changes can be made from this screen. The Unit Status screen displays the following information about both air-conditioners. Unit #1 Economizer Unit #1 Compressor Unit #1 Heater Unit #1 Blower Unit #1 Filter Unit #1 Discharge Air Temperature On/Off On/Off On/Off On/Off Clean/Dirty Value DegF UNIT STATUS UNIT#1 ECON. UNIT#1 COMP. UNIT#1 HEAT UNIT#1 BLOWER UNIT#1FILTER U#1 SUPPLY AIR OFF OFF ON OFF CLEAN 90.
5.3.2.5 UNIT #1 FILTER This display item will show "Clean" if the unit #1 dirty filter alarm of the controller is not energized. This display item will show "Dirty" if the unit #1 filter alarm is energized. 5.3.2.6 UNIT #1 DISCHARGE AIR TEMPERATURE This display will show the current discharge air temperature in the supply air duct of Unit #1 in Fo. 5.3.3 Alarms Menu The Alarm menu set displays the following information about the controller.
on the screen. Press the key. Use the key to highlight the dashes next to the alarm item to be acknowledged. Press to enter edit mode. If you do not have authority to acknowledge alarms the dashes will not be highlighted. An Engineer authority level is required to override outputs. If you have authority to dashes will be highlighted after pressing the key.
The Fault alarm takes precedence over the Alarm (High) or Alarm (Low) message. If the Sensor is failed high or low the Alarm (High) or Alarm (Low) alarms will also be activated but only the Fault alarm will be displayed because this is the actual condition causing the other alarms. These are all self-clearing alarms and will reset themselves when the alarm condition no longer exists. This is a medium priority alarm. 5.3.3.
5.3.3.7 FIRE TROUBLE The Fire Trouble alarm item monitors the fire alarm system in the structure. A "None" alarm message indicates that no alarm is present and that the fire alarm system is operating normally. A "Fault" alarm message indicates that an alarm is present and the fire alarm system is malfunctioning. This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This is a medium priority alarm. 5.3.3.
5.3.4 Setpoints Screen The Setpoints screen displays the following information about the controller.
SETPOINTS F1 = EDIT MODE ENTER TO EDIT Occ. Cooling SP 75.00 F Unocc. Clg. SP 80.00 F Occ. Heating SP 70.00 F Unocc. Htg. SP 68.00 F Hi Temp Alarm SP 87.00 F Lo Temp Alarm SP 56.00 F Hi Humidity SP 80.0 RH Low Humidity SP 20.0 RH Dehum. Setpoint 60.0 RH FC Enth Setpoint 23.00 BTU/LB FC DB Setpoint 48.00 F 5.3.4.1 OCCUPIED COOLING SETPOINT The occupied cooling setpoint requires an authority level of Supervisor or higher to change. Anyone may view the setpoint value.
5.3.4.3 OCCUPIED HEATING SETPOINT The occupied heating setpoint requires an authority level of Supervisor or higher to change. Anyone may view the setpoint value. The Occupied Heating Setpoint Range is from 68.0 to 70.0 Fo. The default value is 70.0 Fo 5.3.4.4 UNOCCUPIED HEATING SETPOINT The unoccupied heating setpoint requires an authority level of Supervisor or higher to change. Anyone may view the setpoint value. The Unoccupied Heating Setpoint Range is from 60.0 to 70.0 Fo. The default value is 68.
change. Anyone may view the setpoint value. The dehumidification setpoint range is from 50 to 65 % RH. The default value is 50 % RH. 5.3.4.10 FREE COOLING ENTHALPY SETPOINT The Enthalpy Setpoint is used to determine if the outside air is suitable to use for cooling the structure. The default value for this point is 23.00 BTU/ lb. of dry air. Consult the Enthalpy Lookup Table to adjust this value for the specific conditions that you wish to maintain in the structure.
Table 2. Enthalpy Lookup Table Desired Indoor Temp. Desired Indoor Temp. 85 84 83 82 81 80 79 78 77 76 75 Desired Indoor % Relative Humidity 35% 23.00 22.50 22.00 21.50 20.75 20.25 20.00 19.50 19.00 18.50 18.00 40% 25.00 24.50 24.00 23.50 22.00 22.25 21.50 21.00 20.50 20.25 19.50 45% 27.25 26.75 26.25 25.25 24.50 24.25 23.75 23.00 22.50 22.00 21.50 50% 29.50 29.00 28.25 27.50 26.75 26.25 25.50 25.00 24.50 24.00 23.25 55% 31.50 30.75 30.25 29.50 29.00 28.25 27.50 27.00 26.25 25.50 25.00 60% 33.50 32.
screen. Press the key. To override the displayed item press the key again. There are seven (7) actions now available, On, Off, Reset, O/R On, O/R OFF, Clr Verify Alr, and Clear O/R. Use the and keys to choose 1 of the 7 actions available. Not all actions are available for each item. The available actions are shown above. Once the desired action is displayed press the key to initiate the action.
This list item uses the Clr Verify Alr, O/R On, O/R Off, and Clr O/R actions. The Clr Verify Alr action clears a blower failure alarm in the alarm object. In the event of a unit #1 blower failure alarm, the output of the controller will be disabled until the problem is corrected and the alarm is cleared. Once the problem is corrected use the Clr Verify Alr action to re-enable normal operation of the output. Any alarm of the Unit #1 Blower must be cleared before an override is accepted.
Entering the O/R On action will turn on the heater output to unit #1 and it will remain on until cleared. Entering the O/R Off action will disable the output to the unit #1 heater and it will remain disabled until cleared. Once overridden the output will remain overridden until the Clr O/R action is sent to the output or power is interrupted to the controller. Use the Clr O/R to cancel an override action and resume normal operation. A supervisor authority level is needed to use this item. 5.3.5.
5.3.6 Enables Menu The Enables menu set displays the following information about the controller. Economizer Operation Enabled / Disabled ENABLES Free Cooling DB Changeover Enabled / Disabled F1 = EDIT MODE Free Cooling Enthalpy Changeover Enabled / Disabled ENTER TO EDIT Daylight Savings Time Enabled / Disabled 50 HZ Clock Enabled / Disabled Enable Econ.
5.3.6.1 ECONOMIZER OPERATION If the air-conditioners controlled by the TCS do not have economizers, economizer operation should be disabled. This disables two stages of cooling that are normally used to energize the economizers if free cooling is available. Factory default for this value is enabled. 5.3.6.2 FREE COOLING ENTHALPY CHANGEOVER The economizer changeover scheme is selectable between enthalpy changeover or dry bulb temperature changeover. The default for this is enable.
5.3.7 Password Operation The DAK is password protected. A password screen is used to control the active change authorization level of the DAK . Each password is a 4 digit number. There are four security levels within the DAK. Display Only Operator Supervisor Engineer Each level has one password associated with it. Everyone has some access to the DAK. All current values can be looked at by anyone. Display Only -All screens have the "Display Only" security level by default.
left of the first two digits. Use the key to increment the display to equal the value of the third digit of the password. Press the key to shift the first, second and third digits left. A new flashing box will appear to the left of the first three digits. Use the key to increment the display to equal the value of the fourth digit of the password. Press the enter key to send the completed password to the controller.
Screen 1 12/01/96 Screen 2 Screen 3 Screen 4 Screen 5 Screen 6 Screen 7 8:45 AM NO ALARMS UNIT STATUS BUILDING STATUS UNIT#1 ECON. OFF ALARMS SETPOINTS OVERRIDES OVERRIDES ENABLES F1 = EDIT MODE F1 = EDIT MODE UNIT #1 UNIT #2 F1 = EDIT MODE ENTER TO EDIT ENTER TO EDIT ENTER TO EDIT F1 = EDIT MODE ROOM TEMP. 75.59F UNIT#1 COMP. OFF ROOM RH 39.4RH UNIT#1 HEAT ON NOP = NO OPERATION OD TEMP. 73.11F UNIT#1 BLOWER OFF ACK = ACKNOWLEDGE OUTDOOR RH 40.
6.0 PC SOFTWARE OPERATION The TCS22 system can be remotely or directly controlled through a personal computer. Bard supplies a software system, the Telcom ClimateWatch System Software, to communicate with and control the TCS22 controller from a personal computer. 6.1 ClimateWatch System Software Overview The ClimateWatch system software consists of ASI Expert software and custom TCS22 controller programs and Screens designed to provide easy access to the features of the TCS22 controller.
6.3 ASI Expert / Bard ClimateWatch Software Start the Expert software by double clicking on the Expert icon in the ASI Program Group. The Expert program can be used to communicate remotely or directly with the TCS22 or TCS22 controller. 6.3.1 SCREEN OVERVIEW The program will begin with the screen shown below. At the top of the initial screen there is a Menu Bar. Below the menu bar is the Tool Bar. The status bar is at the very bottom of the screen.
The Options menu contains system options and dial out and hang up items. System options include baud rate and serial port selection for dial out sites and other advanced system options. The View menu allows the tool bar and stats bar to be turned on and off and user preferences to be changed. User preferences include default project directory and modem options. The Device menu allows device configurations to be saved and loaded for each specific site.
also be stored in this folder for future evaluation. Once a project folder has been created for a site, setpoints, options, phone numbers, etc. can be updated and saved. This creates a backup configuration in case of hardware failure. 6.3.2 TCS COMMUNICATIONS Communications with the TCS panel can be established either remotely through a phone connection or directly through a computer cable connection. 6.3.2.
To configure settings for the direct communications, start the ASI Expert program and go to Options | System options on the menu bar. Under the baud rate portion of the screen, set the baud rate to 9600 Baud. Set the COM Port to match the COM Port number you are using to connect directly to the controller. Make sure “Use 2 stop bits” is NOT checked. Set response time out to 800. Communications can now be established with the controller either directly or remotely via a modem.
Type a new name for the project. Add any comments about the project. If a short cut is desired on the Windows desktop check the Create Project Shortcut on Windows Desktop box. Check the Dial Out checkbox even if this is a direct connect site. A dial out project can also be used to direct connect to the site. Click OK. The Connect to Project Window will appear. 6.3.2.3 Direct Connection This section deals with directly connecting to the TCS controller via a computer cable.
6.3.2.4 Remote Connection For remote connection to the TCS controller type in the phone number of the site including any dialing prefixes. If the phone number is to be saved in the project folder click the Save Modified Phone Number check box. Clicking OK will dial the phone number. The Dialing Screen will appear and the phone number will be dialed.
Once the modems have connected the window will change to the Find It screen. . Make sure the ASIC/2 button is checked. Click the Find It button to establish communications with the controller.
6.3.2.5 Downloading Controller Information The ASIC/2-7040 Device Profile window will appear. If communications have been established the status bar at the bottom of the window will show “ASIC/2-7040 Online…”. If the status bar is flashing red communication have not been established. Check COM port settings and troubleshooting section.
Clicking OK will start the downloading of data from the controller to the computer. Once the preliminary information has been downloaded the TCS New project setup Screen will appear in the Controller information area of the screen. The TCS software version will be displayed for all TCS22 models. Nothing will be displayed for TCS22 models. For TCS22 models refer to the serial plate inside the front cover to determine the software version that is installed.
Now that a project has been created for a site It will appear under the projects folder section of the display. Once the project is created and saved it can be accessed by double clicking on the project name under the projects folder.
6.3.2.6 Saving TCS Configuration While saving project information saves computer settings, site names and controller type information it does not save information specific to each individual controller. A project may have more than one TCS controller and each controller can have it’s own configuration, setpoints, etc. Individual controller information is saved by creating a device archive. A device archive uploads all information from the TCS controller and stores it in a file.
6.4.1 MAIN SCREEN TAB 6.4.1.1 Conditions The Zone Temperature is the current Temperature inside the structure. This, and all the other points being monitored on this screen are updated once a second. The Zone Humidity is the Humidity Level inside of the structure. The Outdoor Temperature and Humidity are the current outdoor conditions at the structure being monitored. The Free Cooling is a Yes or No condition based on an Enthalpy calculation of the Outdoor conditions.
6.4.1.2 Unit #1 Status The Blower status will show if Blower operation is On or Off. The Filter status will show if the Filter is OK or Dirty. The Economizer will show if Economizer operation is On or Off. The Compressor status will show if the Compressor is On or Off. The Heater status will show the status of the Electric Heat Strip, either On or Off. The Supply Air Temperature is the temperature of the Air leaving the unit.
6.4.2 SET POINT TAB The Setpoint screen will allow the user to adjust the Occupied Heating and Cooling, Unoccupied Heating and Cooling, High and Low, Temperature and Humidity Alarm Setpoints. The Lead/Lag Changeover hours and the Enthalpy or Dry Bulb Changeover Setpoints can be adjusted from this screen. Dehumidification setpoint is also changed from this screen. The Continuous Blower may be Enabled or Disabled from this screen. The lead unit can be changed from this screen.
6.4.2.2 Unoccupied Cooling Setpoint The Unoccupied Cooling Setpoint is the default cooling setpoint for a normally unoccupied structure. Cooling of the Structure will begin if the zone temperature is above this setpoint. The Unoccupied Cooling Setpoint will be the active setpoint whenever the occupied override has not been started. The Unoccupied Cooling Setpoint may be adjusted by clicking the right or left arrows next to the Unoccupied Cooling Setpoint Text box.
Alarm Setpoint by 0.50 degrees Fahrenheit until the minimum allowed setpoint of 80.0 degrees is reached. 6.4.2.6 Low Temperature Alarm SetPoint The Low Alarm Setpoint is the temperature at which the low temperature alarm will trigger for the Structure. If the zone temperature of the structure is below the Low Alarm Setpoint then an alarm event is logged in the alarm log and a shelter alarm is generated. Next to the Low Temperature Alarm value is a scroll bar.
Setpoint by .25 BTU / lb. until the Maximum allowed Setpoint of 60 BTU / lb. is reached. Clicking on the Left arrow will decrease the Enthalpy Setpoint by .25 BTU / lb. until the Minimum allowed Setpoint of 5 BTU / lb. is reached. This setpoint may or may not be active and visible depending on the economizer changeover scheme chosen in the Misc. tab. 6.4.2.10 Dry Bulb Changeover Setpoint The Dry Bub Setpoint is used to determine if the outside air is suitable to use for cooling the structure.
determine whether heating is required or not. If the Zone Temperature is below the Active Heating Setpoint, Stage One Heating will be on. The Active Heating Setpoint will be one of three values. If the controller is in occupied mode, the Active Heating setpoint will be the same as the Occupied Heating Setpoint. If the controller is in unoccupied mode, the Active Heating Setpoint will be the same as the Unoccupied Heating Setpoint.
The Override #1 Tab will switch to the screen containing the override information for the Controller. The Override screen will allow the User to override Blower, Economizer, Compressor, and Heater operation of Unit #1. There are three (3) possible override modes. The first mode would be Automatic (Auto). This mode allows the operations to be controlled automatically by the controller and is the normal mode of operation. The second mode would be the Override Off mode.
6.4.3.1 Unit #1 Compressor The override status box displays the current override condition of the Unit #1 Compressor. It will read “Yes” if the output has been overridden on or off. The output value box displays the current condition of the Unit #1 Compressor. It will read either on or off. The Verify Alarm Status box displays the current condition of the Unit #1 Compressor verify alarm. It will read either OK or Alarm.
6.4.3.3 Unit #1 Economizer The override status box displays the current override condition of the Unit #1 Economizer. It will read “Yes” if the output has been overridden on or off. The output value box displays the current condition of the Unit #1 Economizer. It will read either on or off. To override the Unit #1 Economizer on click the Output Verify Action button. Select the “Override Output ON” item and click OK. The override status box will display yes and the Output status will display ON.
6.4.4 ALARMS TAB The Alarms Tab will switch to the screen containing the Alarm information from the Controller. The Alarm screen will allow the user to check the alarm status of the Zone Temperature, Zone Humidity, Outdoor Temperature, Outdoor Humidity, Main Power, Door Alarm, Fire Alarm and Fire Trouble. Blower, Compressor, and Filter alarms of the conditioning units can also be monitored. Several alarms can be enabled or disabled by checking the alarm enable check box.
6.4.4.1 Unit #1 Filter Alarm If a Filter becomes too Dirty, the Shelter Alarm indicator on the main screen will flash, the Unit #1 Filter Status will indicate “Fault Alarm” and an alarm event will be logged in the alarm log. To acknowledge the alarm click the Alarm Action button . Pick the Acknowledge This Alarm & Clear COS Alarm item and click OK. This resets the Shelter Alarm indicator and allows it to capture and indicate any new incoming alarms.
allows the Shelter Alarm indicator to be reset to capture and indicate any new incoming Alarms. The Zone Temperature and Humidity have four possible states. The first of which is OK and indicates that the values are with in the set ranges. The second state would be a High Alarm condition, stating that the value is above the High Alarm setpoint for that value. The third possible state would be the Low Alarm condition, stating that the value is below the Low Alarm setpoint.
Alarm indicator on the Main Screen will flash until the Alarm has been acknowledged or the Power Failure Condition is no longer valid. This is a Self Clearing Alarm. Once the Main Power has been restored, the Alarm will be cleared. 6.4.4.9 Fire Alarm If a Fire Alarm occurs, the Shelter Alarm indicator on the Main Screen will flash. The Fire Alarm can be acknowledged. This will allow the shelter alarm to be reset to capture and indicate any new incoming Alarms. This is a Self Clearing Alarm.
6.4.5 ALARM LOG TAB The Alarm Log Tab has the capability to acquire the last thirty (30) Alarm conditions that the controller has sensed. The alarm log is a rotating file. This means that the oldest data will be overwritten by the newest data if the file is full. Clicking the Alarm tab causes the alarm information to be brought into the program from the controller. As the information is collected, it will be displayed. The alarm conditions are brought into the Alarm Log screen for viewing and analysis.
6.4.6 OFFSETS TAB The Offset screen will allow the User to adjust the sensor offsets to calibrate for sensor tolerances. Click on the offset value to enter a new value. 6.4.6.1 Zone Temperature Offset The Zone Temperature will add the value seen in the textbox from the Zone Temperature to calibrate the sensor 6.4.6.2 Zone Humidity Offset The Zone Humidity Offset will add the value seen in the textbox from the Zone Humidity to calibrate the sensor 6.4.6.
6.4.6.4 Outdoor Humidity Offset The Outdoor Humidity Offset will add the value seen in the textbox from the Outdoor Humidity to calibrate the sensor. 6.4.6.5 Unit #1 Supply Air Temperature Offset The Unit #1 Supply Air Temperature Offset will add the value seen in the textbox from the Unit #1 Supply Air Temperature to calibrate the sensor. 6.4.7 MISC. TAB The misc tab displays several options that are available in the TCS firmware and other information about the controller hardware.
Also included is access to an area of the controller where the TCS model and serial number can be stored. The controller software and firmware version are also displayed. 6.4.7.1 Clear Alarm Event Log Clicking this button erases any old information in the alarm log and resets all of the messages to the default “OK - No Alarm” condition. 6.4.7.2 Enable Economizer Operation. Checking this check box enables economizer operation.
6.4.7.7 Enable Zone Dehumidification The TCS can provide zone dehumidification by running the air conditioners and cycling electric heat on and off to maintain room temperature. Factory default for this value is disabled. Note: The airconditioner circuit breakers and wiring must be sized for concurrent operations air-conditioning and electric heat. Special dehumidification models are available for use with this feature.
6.4.8 TREND TAB The Trend Logger will access the Remote Site and Acquire the site information stored in the controller. This information is stored in a comma separated value file. The information stored is the Zone Temperature, Zone Humidity, OutDoor Temperature, OutDoor Humidity, Unit #1 Supply Air Temperature, Unit #2 Supply Air Temperature, Mechanical Run Time, and Economizer Run Time. The controller will store all of these values once per hour and will hold up to 128 hours of data.
6.4.
The Dial-Out Screen displays the Site name and Site phone number. The site name is included with other information when the TCS dials out and connects to a Printer. When the TCS dials out to a pager it sends the phone number of the site to the pager so the technician can call in to the site to see what the problem is. The site name that is stored in the controller is displayed and can be changed by clicking on the name The Site phone number is the phone number of the site for modem connection.
6.4.10 NOTES TAB The notes tab is just a group of 8 message boxes that can be used to make notes about the controller or leave messages concerning the controller for the next technician. Clicking on one of the message boxes allows you to type a message up two 32 characters long.
7. MAINTENANCE & TROUBLESHOOTING 7.1 Routine Maintenance The TCS22 requires minimal maintenance. Once every 4 years replace the battery under the controller cover. This battery powers the hardware clock during power outages. Check sensor calibration once every two years. 7.2 Troubleshooting 7.2.
Check operation of the Economizer Modem not responding Zone Temperature Sensor Check status of lights on Modem Check Sensor output Zone Humidity Sensor Check Sensor Input Check Sensor Output OutDoor Temperature Sensor Check Sensor Output OutDoor Humidity Sensor Check Sensor Input Check Sensor Output 2100-444-003A Page 84 to F on the terminal strip on controller with the Unit #1 Economizer light ON. Connect a jumper wire on the A/C unit low voltage terminal strip from R to G.
Discharge Air Sensor #1 or #2 Check Sensor Output Dirty Filter Sensor #1 or #2 Check Output Compressor Current Sensor #1 or #2 Check Sensor Output Blower Airflow Sensor #1 or Check Sensor Output #2 2100-444-003A Page 85 will correspond with the Humidity according to Table 7. Determine the Temperature of the discharge air. Remove plug in connector J2 from the TCS22 controller.
wire between R and G of the A/C unit low voltage terminal block to operate the blower. Check continuity between terminal #8 and #9 of the A/C unit low voltage terminal block. This should be a Closed circuit with the Blower running.
Table 3 Humidity Sensor Output Volts DC vs % RH Humidity % RH Output Volts DC 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00 50.00 55.00 60.00 65.00 70.00 75.00 80.00 85.00 90.00 95.00 100.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00 3.25 3.50 3.75 4.00 4.25 4.50 4.75 5.
Table 4 Thermistor Resistance Vs. Temperature Table. Temp Temp Deg C -20.00 -15.00 -10.00 -5.00 0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 45.00 50.00 55.00 60.00 Deg F -4.00 5.00 14.00 23.00 32.00 41.00 50.00 59.00 68.00 77.00 86.00 95.00 104.00 113.00 122.00 131.00 140.
7.2.2 WALLMOUNT QUICK TROUBLESHOOTING GUIDE. Operation Procedure ByPassing TCS22 Controller Disconnect power to the TCS22. Unplug the plug in connectors J4 and J5 from the controller Compressor Test Connect jumper wire on A/C unit low voltage terminals from R to Y and observe Compressor operation (There will be a Time delay between the installation of the jumper and the starting of the Compressor. The Compressor Time Delay relay will determine the time delay period.).