Product Info

Installation and connection– 21
Installation and connection
This page describes the process of installing and connecting the call panel.
Completness check of the product(see page 21)
Electrical connection(see page 21)
Mechanical mounting(see page 23)
Connection of additional modules(see page 24)
Completness check of the product
Before installation of the outdoor panel, it is necessary to check that it is complete and all
components are available.
Outdoor panel kit includes:
Outdoor panel 1pc
Surface mounting bracket with a hood 1pc
Surface mounting bracket without hood 1pc
Installation manual 1pc
Set of wires with connectors for connection of power supply, lock, and
additional modules
1pc
Set of end-caps for connections 1pc
Set screws with a wrench 1pc
Electrical connection
After verifying whether a device is complete, you can switch to the connection.
For connection you will need:
An Ethernet UTP CAT5 or higher cable connected to a network switch/router.
Cable length recommendations
The maximum length of the UTP CAT5 cable segment should not exceed 100 meters, according
to the IEEE 802.3 standard.
Power supply at + 12V, 2 amps.
Wires must be brought for connecting the lock and additional modules (optional).
1. Connection scheme of electromechanical lock using external power supply for panel and the
lock.
You can connect any type of electromechanical or electromagnetic lockfor which
the switched current does not exceed 5 Amps.