Instruction Manual

Page 4
Pump & Pipe
Installation Instructions
INSTALLATION A:
DIRECT DISCHARGE TO THE OUTSIDE OF
THE BUILDING (Diagram A)
Unplug the main AC pump when installing
the backup pump to avoid electric shock.
Failure to do so could cause serious injury
or death.
1. Cut a piece of 1½” rigid PVC pipe long
enough to reach from the bottom of the sump
pit to one (1) foot above the floor. Prime and
cement it to the 1½” pipe adapter, then
screw the adapter into the pump.
2. Secure the pump wire so that the plug on the
end will not fall into the sump. Attach the
wire to the pipe with a piece of tape.
3. Place the pump with the PVC pipe attachment
on the bottom of the sump floor next to the
main AC pump. The pumps should not touch
each other. Do not mount the pump to any
existing pipes; it should be placed on the
floor of the sump. A brick may be placed
under the pump if there are rocks or other
debris on the sump floor that may clog the
pump.
4. Attach a union or a check valve to the top of
the 1½” pipe. This will allow the pump to be
removed easily, should the need arise.
The path of the rest of the pipe and the details
of each installation will vary. Using sound
plumbing practices, try to route the discharge
pipe to an exterior wall via the shortest path
with the fewest turns. More turns will reduce the
pumping capacity. The pipe section exiting the
building should be on a downward slope so that
the water in the pipe will exit outside instead of
returning to the sump pit. Be sure to seal the
hole in the wall where the pipe exits, and prime
and cement or clamp all connections securely to
prevent leaking. When directly discharging to
the outside of the building, no check valve is
required. However, a check valve will prevent
water from flowing back into the pit when the
pump has stopped.
If you use more than a total of 20 feet
of
pipe (including vertical and horizontal runs)
in the installation, install a check valve in
place of a union. Make sure it is installed
with the arrow pointing up, or it will not
prevent the backflow of water. When a check
valve is used, a 1/8” hole must be drilled in
the PVC pipe above the Basement Watchdog
pump. Drill the hole at a 45° angle toward
the bottom of the sump to avoid splashing
water outside the sump pit. Make sure the
hole is above the water line and below the
check valve. If a hole is not drilled above
the pump, an air lock may prevent the pump
from operating.
PUMP
WIRE
PIPE ADAPTER
DRILL 1/8" HOLE
IF CHECK
VALVE USED
FLOOR
JOIST
MAIN
AC PUMP
SLOPE
PIPE
DOWN
RIGID
1-1/2"
PVC PIPE
UNION
OR CHECK
VALVE
CHECK
VALVE
BASEMENT
WATCHDOG
PUMP
DRAIN TILE
1
2
3
4
Diagram A
!
DANGER
CAUTION