Specifications

15
BE1-87G Variable Percentage
Differential Relay
(Request bulletin UBK)
Application
Provides high speed solid-state variable percentage
differential protection for generators, motors, and
shunt reactors.
Features
Single-phase and three-phase units
Sensitivity is adjustable from 0.1 to 1.6 Amps.
Variable percentage restraint characteristic
Current balancing reactors help improve CT
performance on external faults.
High speed (20 milliseconds) operation
BE1-87T Transformer Differential Relay
(Request bulletin UHA)
Application
Used for primary protection against internal faults in
power transformers.
Features
Single-phase sensing with up to five single-phase
inputs
Three-phase sensing with up to three sets of inputs
Provides precision ratio matching in 0.1 Amp steps
Second and fifth harmonic restraint for overexcitation
and inrush security
Phase shift compensation eliminates need for delta or
auxiliary CTs.
Power supply status output
Push-to-energize output switches
Displays percent I
op
BE1-BPR Breaker Protection Relay
(Request bulletin UHG)
MPS Motor Protection Systems
(Request bulletin UPB for MPS200/210,
UPC for MPS100)
Application
Intended for use in any three-pole tripping, breaker
failure protection application.
Features
• Three-phase and neutral current inputs monitor
currents on power system and in protected circuit
breaker.
12 sample per cycle digital signal processing
measures RMS value of current flowing in circuit
breaker.
Seven programmable inputs and five programmable
outputs with BESTlogic provides complete system
configuration flexibility.
Unique timer margin diagnostics to monitor critical
margins after every operation
Available in horizontal 19 rack mount and vertical
panel mount case
Onboard breaker diagnostics
Application
Intended for use in any three-phase, induction motor
protection application. Provides protection from
faults and abnormal operating conditions.
Features
MPS100 provides complete overcurrent and thermal
overload protection for three-phase induction motors.
The MPS200 adds three-phase voltage inputs to
provide voltage and power protection and metering
functions.
The MPS210 adds integrated motor control functions.
All MPS relays include an integrated LCD display for
setup and local indication.
The MPS100 is available in a vertical fixed case. The
MPS2xx relays are available in either vertical or
horizontal fixed cases or a Basler M1 drawout case
with test paddle for current and voltage inputs.