Specifications

20
5 RETROFIT RELAYS
DIRECT PLUG AND PLAY
BE1-79A
Multiple Shot Reclosing Relay
(Request bulletin UHN)
Direct replacement for most ACR reclosing relay configurations
Installs in existing case with no wiring or panel modifications
Functionality of ACR is duplicated via cradle mount switches
or front panel RS-232 communications port.
Also available in Basler S1 case for new installations
BE1-50/51B-214 and BE1-50/51B-219
Single Phase Overcurrent Relay Replacements
(Request bulletin UHDS)
Direct replacement for most IAC relays • Direct replacement for CO relays
-214 replaces more than 100 IAC models • -219 replaces 40 CO models
• Installs in existing case with no wiring or panel modifications
• Self powered and includes memory to replicate the reset of E/M disks
• Self-calibrating eliminates need for recalibration, reducing maintenance.
• 10 selectable curves and wide pickup ranges reduce inventory.
• All units equipped with instantaneous element
Basler Electric also provides relays that allow you to enjoy the advantages of modern solid state protective
relays without having to modify the installation. We offer true "plug and play" convenience with utility
grade, solid state, microprocessor-based replacements for three of the most prevalent relays on your system.
By "true plug and play", we mean replacement in the existing cases with no rewiring and no case modifica-
tions. This means you can be back in service with minimal downtime, minimal work, and minimal expense.