Specifications

3
BE1-951
(Request bulletin UHR)
Features
PROTECTION
Two each Phase, Neutral, and Negative Sequence
Instantaneous Overcurrent elements with settable
time delay
One Phase, Two Neutral, and One Negative Sequence
Time Overcurrent elements
Neutral Overcurrent elements can be assigned to
calculate residual or optional independent ground input
Phase Overcurrent element has capability of voltage
restraint or control
Breaker Failure protection function
Under and overvoltage protection
Negative sequence overvoltage protection
Four protection settings groups
Fuse loss protection
CONTROL
Four shot automatic recloser
One virtual breaker control switch and four virtual
selector switches–controllable from both HMI and
communication ports
INSTRUMENTATION
Real time three phase watts, vars, and power factor
Real time frequency, current, and voltage
Real time ground current for optional independent
ground input
Watt hour and Var hour
REPORTS
Demand reporting
Breaker operations counter and contact wear duty
255 event sequence of events report
Fault and oscillography records: Settable 6-16
240 cycles oscillography memory @ 12 samples/cycle
SELF TEST AND ALARM FUNCTIONS
Relay Fail, major alarm, minor alarm LEDs, and
fail-safe alarm output contact
Extensive internal diagnostics monitor all internal
functions of the relay.
More than 20 additional alarm points–programmable
for major or minor priority provided by virtual control
and selector switches with select-before-operate logic
through programmable outputs
Functional Description
The BE1-951 Overcurrent Protection System is an
economical, microprocessor based, multifunction system.
Using Basler Electric’s innovative half-rack, drawout design,
systems can be dovetailed to form a standard 19” rack mount
installation with no special mounting hardware. Using adapter
plates, the S1 style fits cutout, drilling, and behind-panel
projection dimensions for common Basler Electric, GE, and
Westinghouse unit case relays. This protection system pro-
vides:
Three phase, ground, and Breaker failure
negative sequence overcurrent Breaker monitoring,
protection with four shot recloser metering, and control
Twelve samples per cycle digital functions
signal processing with Frequency tracking and
frequency compensation voltage restrained
Auto configuring voltage sensing overcurrent
circuits Over/underfrequency
and voltage
Application
The BE1-951 Overcurrent Protection System is intended for
use in any directional or nondirectional overcurrent protection
application. Its unique capabilities make it ideally suited for
applications:
Requiring low burden to extend the linear range of CTs.
Requiring high accuracy across a wide frequency range
such as motor, generator, and generator step-up
transformer protection or in cogeneration facilities.
Requiring the flexibility provided by wide setting ranges,
multiple setting groups, and multiple coordination curves
in one unit.
Requiring the economy and space savings provided by a
multifunction, multiphase unit, while providing all of the
protection, local and remote indication, metering, and
control functions required on a typical circuit.
Requiring directional control and fault locating.
Where overexcitation protection is required, such as
transformer backup applications.
Requiring communications and protocol support.
Where the capabilities of digital multifunction relays
with drawout construction are desirable.
Where bus protection is provided by a high speed
overcurrent blocking scheme on the transformer bus
mains instead of a dedicated bus differential circuit.
Where space constraints dictate protection systems
with small size and minimal behind-panel projection
for substation modernization projects.