Specifications
5
BE1-GPS100
(Request bulletin UHQ)
Features
PROTECTION
• One each Phase and Neutral Instantaneous Overcurrent
elements with settable time delay
• One Phase, Two Neutral, and One Negative Sequence
Time Overcurrent elements
• Phase Overcurrent element with voltage restraint or
voltage control capability
• Internally calculated phase residual, 3I0, available on
all relays. Optional independent ground input available.
• One Instantaneous Neutral Overcurrent and two Time
Overcurrent elements monitor either ground or
calculated residual
• Negative sequence overcurrent element with timing
algorithm based on generator K factors or standard
TOC curves
• All U.S. and IEC timing curves plus user-programmable
curve
• Two each Phase Undervoltage and Overvoltage elements
• Two each auxiliary Undervoltage and Overvoltage
elements
• Negative Sequence Overvoltage element
• Four Under/Overfrequency elements
• Two Forward/Reverse Power elements
• Two Loss of Excitation elements
• Four general purpose logic timers
• Two controllable protection settings groups
• Settings group selection may control tripping logic.
• Automatically configurable internal VT circuits
CONTROL
• One virtual breaker control switch and four virtual
selector switches–controllable from both HMI and
communication ports
INSTRUMENTATION
• Real time three phase watts, vars, and power factor
• Real time frequency, current, and voltage
• Real time ground current for optional independent
ground input
• Watt hour and Var hour
REPORTS
• Demand reporting
• 255 event sequence of events report
• Fault reporting: Fault Summary reports, oscillographic
records
SELF TEST AND ALARM FUNCTIONS
• Relay Fail, major alarm, minor alarm LEDs, and
fail-safe alarm output contact
• Extensive internal diagnostics monitor all internal
functions of the relay.
• More than 20 additional alarm points—programmable
for major or minor priority
Functional Description
The BE1-GPS100 Generator Protection System is an
economical, microprocessor based, multifunction system that
provides a comprehensive mix of protective functions to detect
generator faults and abnormal operating conditions along with
control and metering functions in an integrated system. Two
Basler Electric half-rack units can be dovetailed together to
mount in a standard 19” equipment rack with no special
mounting hardware. The innovative half-rack case is fully
drawout with current circuit shorting provisions. The system
includes:
• Fuse loss detection • Breaker failure protection
• Three phase, ground, and negative • Voltage protection
sequence overcurrent protection • Loss of excitation
• Forward and reverse power protection
protection • Frequency protection
• Sync check protection • Volts per hertz protection
Application
The BE1-GPS100 Generator Protection System can be
applied in any generator protection application. Its unique
capabilities make it ideally suited for applications:
• Requiring the flexibility provided by wide settings
ranges, multiple settings groups, multiple coordination
curves, and an extremely versatile programmable logic,
in one unit.
• Requiring the economy and space savings provided by a
multifunction unit that can provide all of the protection,
control, metering, and local and remote indication
functions required in many typical units.
• Where space constraints dictate protection systems with
small size and minimal behind-panel projection for
substation modernization projects.
• Where protection redundancy is provided by having
differential relaying in an independent protective relaying
package.
• Requiring communications and protocol support.
• Where drawout construction is desirable.
• Requiring high accuracy across a wide frequency range.