Specifications

5
BE1-GPS100
(Request bulletin UHQ)
Features
PROTECTION
One each Phase and Neutral Instantaneous Overcurrent
elements with settable time delay
One Phase, Two Neutral, and One Negative Sequence
Time Overcurrent elements
Phase Overcurrent element with voltage restraint or
voltage control capability
Internally calculated phase residual, 3I0, available on
all relays. Optional independent ground input available.
One Instantaneous Neutral Overcurrent and two Time
Overcurrent elements monitor either ground or
calculated residual
Negative sequence overcurrent element with timing
algorithm based on generator K factors or standard
TOC curves
All U.S. and IEC timing curves plus user-programmable
curve
Two each Phase Undervoltage and Overvoltage elements
Two each auxiliary Undervoltage and Overvoltage
elements
Negative Sequence Overvoltage element
Four Under/Overfrequency elements
Two Forward/Reverse Power elements
Two Loss of Excitation elements
Four general purpose logic timers
Two controllable protection settings groups
Settings group selection may control tripping logic.
Automatically configurable internal VT circuits
CONTROL
One virtual breaker control switch and four virtual
selector switches–controllable from both HMI and
communication ports
INSTRUMENTATION
Real time three phase watts, vars, and power factor
Real time frequency, current, and voltage
Real time ground current for optional independent
ground input
Watt hour and Var hour
REPORTS
Demand reporting
255 event sequence of events report
Fault reporting: Fault Summary reports, oscillographic
records
SELF TEST AND ALARM FUNCTIONS
Relay Fail, major alarm, minor alarm LEDs, and
fail-safe alarm output contact
Extensive internal diagnostics monitor all internal
functions of the relay.
More than 20 additional alarm points—programmable
for major or minor priority
Functional Description
The BE1-GPS100 Generator Protection System is an
economical, microprocessor based, multifunction system that
provides a comprehensive mix of protective functions to detect
generator faults and abnormal operating conditions along with
control and metering functions in an integrated system. Two
Basler Electric half-rack units can be dovetailed together to
mount in a standard 19” equipment rack with no special
mounting hardware. The innovative half-rack case is fully
drawout with current circuit shorting provisions. The system
includes:
Fuse loss detection Breaker failure protection
Three phase, ground, and negative Voltage protection
sequence overcurrent protection Loss of excitation
Forward and reverse power protection
protection Frequency protection
Sync check protection Volts per hertz protection
Application
The BE1-GPS100 Generator Protection System can be
applied in any generator protection application. Its unique
capabilities make it ideally suited for applications:
Requiring the flexibility provided by wide settings
ranges, multiple settings groups, multiple coordination
curves, and an extremely versatile programmable logic,
in one unit.
Requiring the economy and space savings provided by a
multifunction unit that can provide all of the protection,
control, metering, and local and remote indication
functions required in many typical units.
Where space constraints dictate protection systems with
small size and minimal behind-panel projection for
substation modernization projects.
Where protection redundancy is provided by having
differential relaying in an independent protective relaying
package.
Requiring communications and protocol support.
Where drawout construction is desirable.
Requiring high accuracy across a wide frequency range.