4 BASOTROL CE Approved Class B Shutoff Gas Valve Installation Instructions
Setup and Adjustments
Checkout
IMPORTANT: All adjustments must be made in
conjunction with the gas appliance and in
accordance with the appliance manufacturer’s
instructions. Only authorized personnel should make
adjustments.
!
WARNING: Risk of Explosion or Fire.
Follow this or an equivalent checkout procedure
after installation. Before leaving the installation,
verify that the gas valve functions properly and that
the system has no gas leaks. Gas leaks can lead to
an explosion or fire, and may result in severe
personal injury or death.
Make sure all components are functioning properly by
performing the following test.
1. Test all joints and connections for leaks with a rich
soap and water solution. If leaks occur, see Step 8
in the Installation section.
2. Close the main manual shutoff valve and wait at
least 5 minutes for unburned gas to escape from
the appliance, and then reopen the shutoff valve.
3. Turn on the main electrical power switch and close
the thermostat contacts. The appliance should
operate in accordance with the manufacturer’s
specified sequence of operation.
4. Turn the thermostat to a low dial setting to open
the contacts. All burner flames should be
extinguished. Repeat Steps 3 and 4 in this section
at least three times.
5. Return the thermostat to a normal setting before
leaving the installation.
Repairs and Replacement
Table 1: Replacement Solenoid Coil
Part Number Description
RSDA16A-12
12 VDC; 2-tab 15 VA Coil
RSDA16A-25
25 VAC; 50/60 Hz; 3-tab 15 VA Coil
RSDA16A-25V
25 VDC; 3-tab 17 VA Coil
RSDA16A-120
120 VAC; 50/60 Hz; 3-tab 15 VA Coil
RSDA16A-240
240 VAC; 50/60 Hz; 3-tab 15 VA Coil
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the BGA171/H96.
Failure to shut off the gas supply can result in the
release of gas during installation or servicing, which
can lead to an explosion or fire, and may result in
severe personal injury or death.
!
WARNING: Risk of Explosion, Fire, or
Electric Shock. Label all wires before they are
disconnected when replacing or servicing the
BGA171/H96. Wiring errors can cause improper or
dangerous operation and may result in an explosion,
fire, or electric shock leading to severe personal
injury or death.
Field repairs must not be made to the BGA171/H96
valve. Any attempt to repair this assembly voids the
manufacturer’s warranty. For a replacement valve,
contact the original equipment manufacturer or the
nearest BASO Gas Products distributor.