User guide

Installation Instructions
Issue Date June 12, 2014
© 2014 BASO Gas Products. 1
Part No. BASO-INS-ECA, Rev. A www.baso.com
E Series CE/AGA Approved
Intermittent Pilot Ignition Control
Application
The E Series CE/AGA Approved Intermittent Pilot
Ignition Control is a safety control designed for indirect
burner ignition and supervision, for use with all gases
and applicable to gas-fired appliances.
The E Series is a microprocessor based ignition
control. The microprocessor provides reliable software
control of all timings and operates a diagnostic
Light-Emitting Diode (LED). It provides ignition
sequence, flame monitoring, and safety shutoff for
boilers, furnaces and other gas-fired heating
appliances.
Installation
IMPORTANT: Only qualified personnel should
install or service BASO Gas Products®. These
instructions are a guide for such personnel. Carefully
follow all instructions for the appliance.
IMPORTANT: Make all gas installations in
accordance with applicable local, national, and
regional regulations.
!
WARNING: Risk of Explosion or Fire.
Do not install the control in an area that is exposed
to water (for example, dripping, spraying, rain). Do
not use the control if it has been exposed to water.
Exposure to water may cause malfunction and can
lead to an explosion or fire and may result in severe
personal injury or death.
IMPORTANT: This control is approved for use
with noise suppression (resistive) spark wires. If the
application has copper wire, it must be replaced.
Instructions for installing the pilot burner/igniter-sensor
are typically provided by the appliance manufacturer. It
is important to follow those instructions. If such
information is not included, refer to the Mounting
section.
Mounting
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical
connections to avoid electric shock.
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the control.
Failure to shut off the gas supply can result in the
release of gas during installation or servicing, which
can lead to an explosion or fire, and may result in
severe personal injury or death.
IMPORTANT: Do not mount the control where
it can be exposed to direct infrared radiation from the
main burner or to temperatures in excess of the
maximum product temperature rating.
Replacement Instructions
Mark wires to existing control. Disconnect the wires
and remove the existing control.
The control is not position sensitive. It may be
mounted horizontally or vertically with two #6 sheet
metal or machine screws.

Summary of content (6 pages)