Manual

4 H17 Series BASO Automatic Pilot Valve Installation Instructions
Approximately
1/2 in. (12.7 mm)
fig2
Figure 2: Flame Position
Repairs and Replacements
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the H17. Failure
to shut off the gas supply can result in the release of
gas during installation or servicing, which can lead to
an explosion or fire, and may result in severe
personal injury or death.
Field repairs must not be made to the H17 valve. If
the thermocouple meets the output listed in Table 1
and the valve does not function, replace the entire
valve. Any attempt to repair this assembly voids the
manufacturer’s warranty. For a replacement valve,
contact the original equipment manufacturer or the
nearest BASO Gas Products distributor.
Technical Specifications
Product
H17 Series BASO Automatic Pilot Valve
Maximum Operating
Pressure
0.5 psi (35 mbar)
Valve Body
Aluminum
Permissible Ambient
(Surface) Temperature
-40 to 150°F (-40 to 66°C) standard models
-40 to 300°F (-40 to 149°C) high temperature models
Recommended
Thermocouple Lead
Lengths
K15: 12 to 48 in. (305 to 1,220 mm)
K16: 12 to 72 in. (305 to 1,830 mm)
K19: 18 to 72 in. (457 to 1,830 mm)
Inlet/Outlet Pipe Size
1/8, 1/4, 3/8, and 1/2 in. NPT
Types of Gas
Natural, Liquefied Petroleum (LP), or LP gas-air mixtures
Packaging
Bulk pack supplied to original equipment manufacturer (individual pack optional)
Bulk Pack Quantity
60
Bulk Pack Weight
27 lb (12 kg)
Agency Listing
CSA (AGA, CGA) Certificate Number 229521-1656088
UL File Number MH2926 (H17AA, BA, and CA only)
Specification Standards
ANSI Z21.20, CAN1-6.4
ANSI Z21.21, CSA 6.5
UL Standard 372
Performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is performed
under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and may void
the warranty. Product must be protected if exposed to water (dripping, spraying, rain, etc.) or other harsh environments. The original
equipment manufacturer or end user is responsible for the correct application of BASO products. Consult BASO Gas Products LLC for
questionable applications. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from misapplication or
misuse of its products.
Refer to the H17 Series BASO Automatic Pilot Valve Product Bulletin (BASO-PB-H17) for necessary information on operating and
performance specifications of this product.
1007 South 12th Street
PO Box 170
Watertown, WI 53094 www.baso.com
1-877-227-6427 (1-877-BASOGAS) Printed in U.S.A.