User Manual

O300.ZL-GW1J.72N7/7 19.5.2017
Index Subindex (dec) Access Parameter name Coding Defi nition
0x000C (12) 0 R/W Parameter (write)
Access Lock
Uint16 0: Unlocked (default)
1: Device is operating properly
0x0010 (16) 0RVendor Name String Baumer Electric AG
0x0011 (17) 0RVendor Te xt String www.baumer.com
0x0012 (18) 0RProduct Name String <Product Key External>
(<Product Key Internal>)
0x0013 (19) 0RProduct Id String Baumer Article Number
0x0014 (20) 0RProduct Text String Sensor specifi c
0x0015 (21) 0RSerial Number String <Production Order Nr>_<Serial Nr>
0x0017 (23) 0RFirmware Version String Major.Minor “##.##”
0x0018 (24) 0 R/W Application
Specifi c Ta g
String Default: Filled with ******,
as recommended by the IO-Link spec.
0x0024 (36) 0RDevice Status Uint16 0: Device is OK
1: Device is operating properly
2: Out-of-Specifi cation
3: Functional-Check
4: Failure
5 - 255: Reserved
0x0025 (37) 0RDetailed Device Status Uint16 EventQualifi er “0x00”
EventCode “0x00, 0x00”
IO-Link Pre defi ned parameters
IO-Link Baumer specifi c parameters
Index Subindex (dec) Access Parameter name Coding Defi nition
0x0050 (80) 0 R/W Local Teach Unit8
0x0060 (96) 01 R/W Response Delay
Filter
Uint16 0: fi lter OFF (default)
5 … 60000. Delay in ms in steps of
1ms
02 R/W Release Delay
Filter
Uint16 0: fi lter OFF (default)
5 … 60000. Delay in ms in steps of
1ms
03 R/W Minimal Pulse
Duration Filter
Uint16 0: pulse duration OFF (default)
5 … 60000. Minimum pulse in ms in
steps of 1ms
0x0064 (100) 0 R/W Teach Method Uint16 0: xPert
Full functionality
1: xPress Refl ector teach only
(tap qTeach for 2 sec to teach
refl ector)
0: Local teach never locked
1 ‒ 120: Local teach locked
after n minutes
0xFF: Local teach always
locked
Default value: 5
IO-Link Event codes for devices
Event Codes Defi nition and recommended maintenance action Device Status Value Type
0x5000 Device hardware fault  Device exchange 4 Error