Operating instructions
37
912.808.1 - IT
INSTALLATION AND OPERATING MANUAL
Before starting the user module, open the on/off valves on the hydraulic connectors and check the system lling pressure
in the boiler room and distribution columns (< 3 bar).
The centralised plant must have an automatic lling device.
19. FILLING THE SYSTEM
In the rst plant lling operation, vent any air in the system, including the user module. The appliance is tted with an
automatic air vent valve.
20. AIR VENT AND PUMP RESET
20.1 AIR VENT
The user module is tted with a pump reset device (not present in model RP/1) which, if no heat demand (heating and/
or domestic water) is received for 24 consecutive hours, automatically runs the pump for one minute. This function is
operative if the system is powered.
If, however, the pump/s need/s to be reset after a period of inactivity or during initial starting, simply remove the cap
screwed onto the shaft, insert a screwdriver and turn the rotor a few times in order to reset it and allow it to start. Collect
the water owing from the pump shaft.
20
.2 PUMP RESET (MODELS: RP/1 – RSP - R2Z – RS2Z)
START-UP AND OPERATING INSTRUCTIONS