Unit installation

13. WINDOW FITTING
Fitting the window.
Locate the channel at the top of the window over the top of the firebox opening.
Refit the three spring loaded screws and bushes. The wide part of the bushes
should be in contact with the widow frame. Tighten sufficiently to seal the firebox.
Pull the bottom of the window forward and release to check that the window
opens slightly and returns in the event of a delayed ignition explosion.
14. FULL OPERATING CHECKS
14.1 Check for leaks.
Turn on the gas supply and check all joints up to the appliance gas tap for gas
soundness using a soap solution or leak detection fluid.
14.2 Check control operation.
Place the fascia in front of the fire and connect the battery and motor leads. The
motor lead connectors are two different sizes. They will only fit to the correct motor
terminals.
If the fire is turned off or the flames go out, wait at least 3 minutes before
attempting to relight. A safety device in the control stops the fire being turned
back on until it is safe.
(See figure 32).
Depress the bottom half of the rocker
switch located at the right side of the
appliance case. This should cause the flame
control knob (The left-hand control knob) to
rotate clockwise until its bar is pointing
vertically downward. A clicking sound will be
heard while the flame control knob is
rotating.
Push in the right control knob and, while
keeping it depressed, turn anticlockwise
through the ignition position marked and up to the pilot position marked .
The spark should light the pilot. The pilot flame can be seen by looking through the
gap near the front left side of the ceramic fuel effect.
If the pilot does not ignite, keep the knob depressed for a few seconds to purge air
from the supply pipes. Then turn back to the off position marked
•
and repeat the
ignition procedure.
When the pilot has lit, keep the right hand control knob depressed for a few
Page 33
© Baxi Heating U.K. Limited 2009.
Figure 32. Control
INSTALLER GUIDE