Technical data
18
© Baxi Heating UK Ltd 2014
5.0 Site Requirements
5.11 Condensate Disposal - Pipe Runs
1. 3.5 metres of flexible 10mm condensate discharge
pipe and a 10mm push fit elbow are supplied with the
boiler.
2. The 10mm pipe can be routed to a maximum of
2.5 metres vertically as measured from the outlet
(equivalent to the total available head of 3 metres)
and then discharge via gravity or be routed
horizontally (Fig. 12).
3. The pipe must be adequately supported, either
using suitably spaced clips or run within larger
diameter pipe. When using clips take care not to
deform or restrict the pipe.
4. When routing the pipe through a wall it must be
suitably sleeved. Also the pipe must not be exposed
to sources of heat, and should be protected in
locations where it may be damaged.
5. The pipe should be routed so that any sharp
bends, dips and loops are avoided. A minimum radius
of 100mm is recommended for any bends (Fig. 13).
No slope is necessary and air breaks are not required
on the pumped part of the run.
6. From ‘A’ to ‘B’ (vertical run) must be NOT
GREATER than 2.5 metres (Fig. 14). The length of
vertical run influences the maximum horizontal run
and number of elbows allowed. From ‘B’ to ‘C’
(horizontal run) can be as shown in the table overleaf.
The permissible number of 90° elbows is also given.
NOTE: The pipe from ‘A’ to ‘C’ must be NOT
GREATER than 10mm diameter !
R100 min.
A
B
C
90° ‘Speedfit’ Elbow*
(supplied)
Boiler Condensate
Outlet
Flexible Pipe
Fig. 13
Fig. 14










