924.674.3 - GBINSTRUCTIONS PERTAINING TO THE INSTALLER
20. DISPLAYING PARAMETERS ON THE DISPLAY (“INFO” MODE)
Proceed as follows to display boiler parameters on the front panel display:
IMPORTANT: the following operations (gure 14), it has to be carried out in fast sequence in a short time (~ 4 seconds)
without making any break during the steps:
1) with the control knob ( ) in any position turns it fully anti-clockwise to the minimum value;
2) quickly turn control knob clockwise through about a
1
/
4
turn;
3) again turns the control knob fully anti-clockwise to it minimum value
4) then set back the control knob to it original position.
turn the control knob ( ) to display the following informations:
A00: domestic hot water output temperature (°C);
A01: outdoor temperature (in °C) with outdoor sensor probe connected;
A02: the value (%) of the modulator current (100% = 230 mA NATURAL GAS - 100% = 310 mA LPG);
A03: heat output (%) power range (max R);
A04: central heating water output setpoint temperature (°C);
A05: central heating water output temperature (°C);
A07: valve (µA) of the ionization current.
Note: program lines from A06 - A08 - A09 are not used.
“INFO” function remains active for 3 minutes. To exit “INFO” function before this time repeat the operation as described
in points 1...4 or cutting OFF the power supply to the boiler.
Note: In “INFO” mode, the display (4 - figure 1) alternates between the message “A00” and CH temperature.