4.0 Site Requirement
13
4.8 Flue Options
1. The Baxi Solo 3 PFL can be fitted with flue systems
as illustrated.
2, The standard flue is suitable only for horizontal
applications.
3. Maximum permissible equivalent flue lengths are:-
Horizontal 3.0 metres
Vertical 4.0 metres
Vertical (Twin) 20.0 metres
4. Any additional “in line” bends in the flue system
must be taken into consideration. Their equivalent
lengths are:-
Concentric Pipes:
45° bend 0.5 metres
90° bend 1.0 metres
Twin Flue Pipes
Air Duct Flue Duct
45° bend 1.3 metres 3.3 metres
90° bend 4.8 metres 12.0 metres
5. The illustrations opposite show examples of
maximum equivalent lengths.
6. Instructions for guidance and fitting are included in
each kit.
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
Horizontal
Flues
Vertical
Flues
Vertical
Flues
(Twin Pipe)
Maximum Length = 2m inc. 2 x 45° bends
Maximum Length = 21m
inc. 4 x 45° bends
Maximum Length = 2m
inc. 2 x 90° bends