Owner`s manual

Solutions to Problems
Problem Solution
No Control Module power indication.
Check for 24VAC power between
terminals “R” and “C” on the
Furnace/AC connector, or if using the
power supply, check for power at the
outlet.
Unplug Alert input and Thermostat
connectors, if power light comes on
there is a short or improper connection
on one or both of these connections.
Contact support for replacement
Control Module.
Keypad is dark, no power at keypad.
Check Control Module has power.
Check wiring between Keypad and
Control module.
Check for power (3.3 VDC) on the red
and white terminals of the Thermostat
connector of the Control Module, and
on the wires at the Thermostat Keypad.
Contact support for a replacement
Thermostat Keypad.
Fan control does not function.
Verify on the Thermostat Keypad that
the Fan is selected ON.
Verify on the Control Module that the
Fan light is ON.
Check the red and green wires
between the Furnace/AC connector on
the Control Module and your
Furnace/AC.
Check that the Furnace/AC has power.
Heat does not function.
Verify that Heat mode is selected on
the Thermostat Keypad.
Verify that the set point is higher than
the current temperature.
Verify on the Control Module that the
Heat light is ON.
Check the red and white wires between
the Furnace/AC connector on the
Control Module and your Furnace/AC.
Check that the Furnace/AC has power.
23