Installation guide
BBV_1-2-1 _Protocol_converter_manual_V41_November_2013 Page 35 / 40
Vicon Surveyor (adjust SW3 to suit input protocol)
Set the dome address using the DIL switch to match the number of the camera input of the TX1500. Ensure
that any dome at the end of a daisy chained RS485 run are have the RS485 terminated and the
intermediate domes have the RS485 de-terminated.
Select VPS telemetry using dome DIP DIL.
The following functionality is provided.
Manual pan/tilt control with 16 speed steps.
Zoom with Manual Focus override.
Operating the Zoom will re-enable auto focus after manual adjustment
64 preset positions.
3 tours can be started, tour 81 and 82 using 1 PATROL and 2 PATROL and tour 80 with AUTOPAN.
The tours are defined from the dome menu.
Advanced Function TX1500 Procedure Molynx
Pelco &
Mark Mercer
Procedure
Display dome menu 1 # Cam on then Prog preset 1 Go to Preset 61
MENU AP – ENTER IRIS OPEN IRIS OPEN IRIS OPEN
MENU AI – ESCAPE IRIS CLOSE IRIS CLOSE IRIS CLOSE
AUX 1 WASH
AUX 2 WIPE
AUX 3 LIGHTS
Start TOUR 81 1 PATROL Cam on then Goto 5 Go to Preset 66
Start TOUR 82 2 PATROL Cam on then Goto 6 Go to Preset 67
Start TOUR 80 AUTOPAN Cam on then Goto 7 Go to Preset 68
It is very important that once you have exited the dome menu you send a 1 PRESET to inform the 1-2-1
converter that you are out of the dome menu.
The output baud rate can be selected between 4800 and 9600 baud. SW4/8 ON = 4800 baud, SW4/8 OFF
= 9600 baud. Generally 9600 baud will be used on late systems and 4800 baud on early systems.
Support for earlier V1305DC DC telemetry receivers.
SW4/7 ON and SW4/8 ON
These receivers use 4800 baud so SW4/8 must be ON.
SW4/7 must also be ON to enable control of this receiver type. When in this mode, the WASH function
drives Aux 4 which is the only momentary output.
SW4
Connect dome
COMM_IN+ to BBV 1-2-1 Converter TA and dome
COMM_IN- to BBV 1-2-1 Converter TB.