Product Overview

Form No 61983 R01, Printed in the USA 06/15
Available Lockout Sequences
T Models - Lockout Sequences
Continuous retry - 5 minute waiting period (standard)
Lockout after single trial for ignition (volatile lockout)
Lockout with retrial every 1 hour (volatile lockout)
Lockout after 3 trials for ignition (volatile lockout)
C Models - Lockout Sequence
Shutdown after ame failure or failure to light (no
relight attempt)
5 minute minimum waiting time
1 retry attempt allowed, then non-volatile lockout.
Lockout must be manually reset using reset button
All replacement T models and C models can be wired with or
without a damper. A damper connector is included for use with
existing damper wiring plugs. A damper plug jumper is included
for use if no damper is connected to the ignition control.
Available Models
Beckett GeniSys®
Control Part No.
Lockout
Time
Single or Dual
Rod
Vent Damper
Plug
Multiple Lockout
Sequences
Reset Button and
Non-volatile Lockout
7586T0001 10-90 sec Yes Yes Yes No
7586C0001 10 sec max Yes Yes No Yes
Electrical Ratings
Inputs
Voltage: 24 Vac nominal
Current Draw: 0.2 Amps plus gas valve (MV+PV)
Frequency: 50/60 Hz
Outputs
Pilot Valve Rating: 2.0 Amps (resistive)
Main Valve Rating: 5.0 Amps (resistive)
Note: With no damper installed, max valve current draw = 1.75 Amps
Timings
Ignition Timing: 10-90 seconds
Pre-purge Timing: 1-240 seconds
Inter-purge Timing: 30-300 seconds
Additional Ratings
Minimum Flame Current: 1 µA
Flame Failure Response Time: 0.8 seconds
Thermostat Voltage: 24 Vac
Environmental Ratings
Storage & Operating Ambient Temp.: -40°F to +175°F (-40°C to
+79.4°C)
Moisture: 5 to 95% RH, non-condensing
Approvals
UL listing per ANSI Z21.20, UL372, and CSA
C22.2 No. 199.
The standard 7586 is designed for use on applications below
400,000 BTUs. For applications above 400,000 BTUs, contact
Beckett’s Engineering Group.
PARTS & ACCESSORIES
Single Rod Shown with damper wiring
Dual Rod shown without damper wiring
PV
Burner GND
24V
Comm Port
Reset Button
(optional)
Sense
Spark
Status
Flame
MV
MV/PV/Com
MV
MV
MV/PV
Gas
Valve
Burner
GND
24V GND
TH-W
PV
Model 7586 Control
PV
Transformer
Damper
Connector
(optional)
Controller
(Thermostat)
L1
L2
Vent
Damper
Limit
Controller
Alternate
Limit
Location
Direct Sense
Jumper
Pilot/
Igniter
Burner
GND
SK10310
120 VAC
Comm Port
Reset Button
(optional)
Sense
Spark
Model 7586 Control
Gas
Valve
Remove (Clip)
Jumper
(if present)
Burner
GND
Limit
Controller
L1
L2
Alternate
Limit
Location
Pilot/
Igniter
Burner
GND
Transformer
MV/PV/Com
MV
PV
PV
Burner GND
24V (optional)
MV
MV/PV
24V GND
TH-W
Damper
Connector
(optional)
Status
Flame
MV
PV
SK10311
120 VAC
Controller
(Thermostat)
Product Sheet - Model 7586
R.W. Beckett Corporation
Mail: P.O. Box 1289, Elyria, OH 44036 ● Phone: 800-OIL-BURN (800-645-2876) ● FAX: (440)327-1064
R.W. Beckett Canada Ltd.
Unit 3 - 430 Laird Road, Guelph, Ontario, Canada N1G 3X7 ● Phone: 800-665-6972 ● FAX: (519)763-5656
www.beckettcor p.com