Product Overview

Product Description
The Beckett GeniSys® Intermittent Pilot Gas Ignition Control is a 24 Vac primary safety control designed for use in residential and light
commercial gas heating applications which use an intermittent pilot for lighting the main burner. Applications may include boilers, furnaces,
water heaters, space heating and commercial cooking equipment. The GeniSys® gas ignition control includes an integrated spark ignition
coil for lighting the pilot and uses ame rectication principles to reliably prove the presence of the pilot ame.
Features & Benets
Designed for use in Single Rod and Dual Rod applications
4 LEDs for improved diagnostics
Continuous retry standard - single or multiple trials for ignition optional
Convenient mounting using screws or fasteners
Selectable ignition timing 10-90 seconds
Selectable pre-purge timing 1-240 seconds
Selectable relight or recycle operation
The microprocessor is checked for proper operation before each cycle
Designed for use with gas valve connector plug
Available model (7586C) with manual reset button and non-volatile lockout
Communication Port links new alarm module and future products
4 LEDs Provide Easy Diagnostics
For faster troubleshooting and service calls
Service personnel can quickly determine control status
PARTS & ACCESSORIES
Quick Status Check
Flame
Status PV
MV
Flame
Status PV
MV
Flame
Status PV
MV
Flame
Status PV
MVFlame
Status PV
MV
Flame
Status PV
MV
Flame
Status PV
MV
Flame
Status PV
MV
No call for heat
or no power to
control
Slow ash,
Pre-purge or
Interpurge
period
Trial for
Ignition
Flame proven
Run Mode,
strong ame
signal
Run Mode,
Flame LED
ashing, low
ame signal
Flashing
Flame and
Status LEDs,
Flame out of
sequence
Control error,
replace control
Flame
Status PV
MV
Fast ash,
lockout
Flame
Status PV
MV
Product Sheet - Model 7586