INSTALLATION AND OPERATOR’S MANUAL SL375 THRU SL7175 OIL FIRED CAST IRON BOILERS Keep these instructions with the boiler at all times for future reference BOYERTOWN FURNACE CO. PO Box 100 BOYERTOWN, PA 19512 1-610-369-1450 www.boyertownfurnace.
Be Aware of Hazard Definitions Danger Denotes presence of a hazard which, if ignored, will result in severe personal injury, death or property damage Warning Denotes presence of a hazard which, if ignored could result in severe personal injury, death or substantial property damage.
Table of Contents Ratings and Data………………………………………………………………………4 Clearances……………………………………………………………………..............5 Ventilation and Combustion Air………………………………………………………5 Boiler Assembly……………………………………………………………….............6 Temperature control Installation and Adjustment Boiler Trim Piping Jacket Installation System Piping………………………………………………………………...……….9 Bypass Piping Low Water Cut-Off Relief Valves Expansion Tanks Venting Systems……………………………………………………………………...
Ratings and Data Boiler Model No. Firing Rate - #2 Fuel Input BTU/HR DOE Capacity BTU/HR Net IBR Rating BTU/HR Net Rating Sq. Ft. AFUE Rating Water Capacity Approx. Shipping Weight SL375 0.75 105,000 91,000 79,000 526 85.5 3.6 300 Cabinet Height Cabinet Width Cabinet Length Supply Outlet Height C.L. Return Outlet Height C.L. Flue Outlet Diameter Flue Outlet Height C.L. SLD375 0.75 105,000 91,000 79,000 526 85.5 3.6 300 28 7/8" 17 3/4" 19 1/4" 25 3/8" 4 1/2" 6" 20 3/4" SL4100 1.
Installation Clearances WARNING Boilers in rooms shall be installed with the clearances from combustible materials not less than indicated below. Combustible materials are those made of or surfaced with wood, compressed paper, plant fibers, plastics, or other material that will ignite and burn, whether flame proofed or not, or whether plastered or not. The boiler must not be installed on combustible flooring. The boiler is approved for installation on non combustible flooring only.
hundred (100) square inches. These openings must freely communicate with the interior areas having adequate infiltration from the outside. When the boiler is installed in a confined space and all air is provided from the outdoors, the confined space shall be provided with two permanent openings, one commencing within 12 inches from the top, and one commencing 12 inches from the bottom of the enclosure.
the crated boiler to the carrier in good condition. ANY CLAIMS FOR DAMAGE OR SHORTAGE IN SHIPMENT MUST BE FILED IMMEDIATELY against the carrier by the consignee. Temperature Controls Installation and Adjustment 1. After cabinet installation is complete install the temperature control on the right side of the boiler. a) Carlin Aquastat – Attach the 4 x 4 Junction box supplied with the Carlin control using the 1/2” electrical box connector attached to the side of the jacket.
Jacket installation 1. Open Cabinet Parts Box Check for damages. Damage claims must be filed immediately with carrier. 2. Install the (4) 3/4” OD x 1-9/16” bottom bracket spacers onto the tie rods, followed by the bottom brackets, with the tabs pointing outward, which are fastened in place with the 10mm nuts provided. 3. Mount top brackets on the boiler tie rods with the tabs pointing outward. Fasten in place between the 10mm nuts provided on the casting.
System Piping Important… INSTALLATION MUST BE PERFORMED BY TECHNICALLY QUALIFIED SERVICEMEN SOLAIA BOILERS HAVE A MAXIMUM OPERATING PRESSURE OF 58PSI NOTE: If normal operating pressures are greater than 30psi please contact the manufacturer for required trim. Pipes that are connected to boiler fittings must be supported and placed so that they do not create stresses on the boiler fittings themselves.
VENTING WARNING Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death. All chimneys must meet the requirements of NFPA 211 and NFPA 31 Chimney The boiler must be connected to an adequate chimney or an approved venting system in accordance with these instructions. An adequate chimney or venting system is one that is sealed and lined with the capability of producing a -.04" W.C.
Evidence of potential or existing chimney damage should be determined by visual inspection of the chimney and liner. Exterior indicators such as missing or loose mortar/bricks, white deposits on the brick or water stains on the interior building walls should be investigated further. The operational flue temperatures for boilers range from 350ºF to 450ºF at the outlet of the boiler.
With the burner operating, use a draft gauge to adjust the regulator to the proper setting (see instructions enclosed with draft gauge to adjust the regulator to the proper setting). When the burner air supply and draft are properly adjusted, the draft in the flue should be a negative .02" W.C. to negative .04” W.C.
3. COMBINATION AIR INTAKE/VENT SYSTEM The vent system consists of 10, 15, or 20 foot lengths of 5” single wall flexible stainless vent piping, or 10 or 15 foot lengths of double wall insulated flexible stainless vent piping and an equal length of 4” air intake piping and a stainless steel intake/vent termination end. Consult the Direct Vent manual included with the direct vent kit for more detailed installation instructions.
The purpose of the damper is to act as a vacuum breaker in the event of a blockage in the air intake. NOTE: The balance weight of the vacuum relief valve must be installed in a level position and adjusted to lightly close while burner is operating. Be sure to lock the balancing weight after adjustment. ALL JOINTS IN THE AIR INTAKE ASSEMBLY MUST BE SECURELY FASTENED.
DIRECT VENT OIL BURNERS Riello Burners All Riello direct vent burners are shipped with the nozzle for the SLD375 installed. A separate nozzle is included in the burner carton for the SLD4100 and SLD5125. See the burner set up page or the Installer Serviceman Label attached to the boiler. for the appropriate burner settings. Boilers supplied with Riello burners will also be supplied with a 3” to 4” galvanized adapter.
Oil Tank and Piping Oil tanks and piping should be installed in accordance with the National Board of Fire Underwriters and local codes. Connection of the flexible oil line to burner must be positioned to permit easy opening of the burner swing door. Use continuous heavy walled copper tubing with flare fittings only. Do not use compression fittings. Do not run overhead fuel lines from tank to oil burner.
Swing Door Opening the Door 1. 2. 3. 4. 5. 6. Turn off power to boiler. Allow boiler to cool down. Unplug the burner power cable at factory-supplied burner Molex plug electrical disconnect. Lift the front jacket panel up and off the boiler. Remove the four nuts from swing door studs. Swing open burner door to the left while gently lifting to prevent rubbing of door studs. Closing the Door 1.
Carlin 90200A Temperature Control 1. The Carlin 90200A temperature control functions as a high limit only. Start-Up Warning…Use only … No. 2 fuel oils. Note: Note: Do not attempt to start the burner if excess oil has accumulated. Do not use gasoline, crankcase draining or any oil containing gasoline. 1. 2. 3. 4. Make sure that normal water level has been obtained in the boiler and system. Check that all safety devices are in place. Check that thermostats are correctly connected and set.
2. Direct vented – Take a draft reading from the inspection port of the boiler. This over-fire reading will be a positive pressure. Approximate over- fire draft readings can be found in the burner settings table. 3. Pump pressure – Install a pump pressure gauge in the oil pump following the oil burner manufacturer’s recommendations. Adjust the pump pressure as per the preliminary burner settings. 4. Combustion Set-up – The air settings shown in the table are approximate.
1. High limit control - Remove the temperature control cover as needed and note temperature setting. With the burner running reduce the high limit setting until the burner shuts off. Return the high limit to its original setting. 2. To check the primary control and flame sensor shut off oil supply with hand valve while burner is running, fifteen seconds after flameout, the safety switch locks out, ignition stops and the oil valve should close. To restart, open oil supply value and reset safety switch.
2. Clean nozzle assembly and all air handling parts. 3. Check spacing and condition of ignition electrodes. Clean and replace as required. 4. Nozzles should be inspected every year for plugged orifices. If it is necessary to replace the nozzle, use only the specified nozzle to be sure that the replacement meets spray specifications for the boiler burner combination. 5. Consult oil burner manufacturer’s instructions for additional maintenance requirements.
Trouble Shooting Guide Burner Will Not Start Thermostat Set Above Room Temperature No Adjust Thermostat Yes High Limit Set on No Aquastat to 180 Deg. Min. Adjust High Limit Yes 110 Volts between No L1 and L2 at Aquastat Check Fuses and Safety Switches Yes Remove Thermostat Wires From Aquastat and No Jumper T T terminals.
Burner Goes Off On Safety Oil Tank Full No Fill Tank Yes Bleed Oil Lines No Oil Flows Freely Fuel Supply Valves Open Open All Supply Valves Yes Yes Oil Filter Clean No Air in Oil Lines Check All Fitting Connections Pump Strainer Clean No Adjust Pressure to Burner Specs. No Replace Oil Filter Yes Yes Pump Pressure to Burner Spec.
Item 1 1 1 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 19 20 20 21 22 23 24 Qty.
Solaia Residential Cast Iron Boiler Warranty First Year Limited Warranty for Solaia Residential Cast Iron Water Boilers Boyertown Furnace warrants that its residential cast iron water boilers are free from defects in material and workmanship under normal usage for one year from the date of original installation. If any parts are found to be defective in manufacture during this one-year period, Boyertown Furnace Company will supply a replacement for the defective part.
Installation and Service Check List Boiler Model: _______________________ Serial No.: ____________________ Installation Date: ______________________ Installer Name: ________________________ Phone No.
-----------------Cut and Return This Form or register online at www.boyertownfurnace.com----------------- Warranty Registration Boyertown Furnace Co. P.O. Box 100 Boyertown, PA 19512 Date Installed: ___________________________ Boiler Model No.