User manual
8
Voltage detection Automatic
Polarity detection Full range
Range detection Automatic
Automatic load
(RCD trip test)
Yes
Internal load
Approximately 2.4 W at 690 V (load
buttons activated)
Current Is
<3.5 mA at 690 V (load buttons
activated
Connectable load Approximately 240 W at 690 V
Test current
connectable load
<350 mA
Operation time
(DT)
30 s
Recovery time 240 s
Automatic power
on
>12 V
(activated load buttons)
>24 V (w/o load buttons)
Data Hold
(2100-Beta only)
12...690V AC/DC
Single Pole Phase Test
Voltage range 180…690 V AC against earth
Frequency range 40 Hz…70 Hz
Acoustic
indication
yes
LED indication Red LED
Continuity Test
Range 0….500 kΩ
Tolerances 0% to +50%
Test current <5 μA
Acoustic
indication
yes
LED indication Red LED
Overvoltage
protection
690 V AC/ DC
Automatic power
on
< 500 kΩ
Rotary Field Detection
Voltage range 340…440 V AC phase to phase
Frequency range 47 Hz…63 Hz
LED indication Red LED
General Specifications
Operating
temperature
range
-15°C to +55°C
Storage
temperature
range
-15°C to +55°C
Humidity Max. 95% RH
Operating
altitude
Up to 2000 m
Measurement
category
CAT IV 600V,
CAT III 690V
Pollution degree 2
IP Protection IP 64
Safety
regulations
EN 61243-3:2010
Agency approval GS from TÜV Rheinland, CE
Power Supply 2x 1.5V (AAA/ IEC LR03)