Telaris Telaris Telaris Telaris Telaris Telaris Telaris ProInstall-100-EUR ProInstall-200-EUR ProInstall-100-D ProInstall-200-D ProInstall-100-CH ProInstall-200-CH ProInstall-100-DK Users Manual 7/2013, 6001109 A ©2013 Amprobe Test Tools. All rights reserved.
Limited Warranty and Limitation of Liability Your Amprobe product will be free from defects in material and workmanship for one year from the date of purchase unless local laws require otherwise. This warranty does not cover fuses, disposable batteries or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling. Resellers are not authorized to extend any other warranty on the behalf of Amprobe.
Telaris ProInstall-100 / Telaris ProInstall-200 CONTENTS INTRODUCTION................................................................................................................. 4 SAFETY............................................................................................................................... 4 UNPACKING THE TESTER.................................................................................................. 5 OPERATING THE TESTER..................................................
Testing the Fuse...................................................................................................................... 25 DETAILED SPECIFICATIONS...........................................................................................25 Features by Model.................................................................................................................. 25 General Specifications...................................................................................................
Introduction The Amprobe Model Telaris ProInstall-100 and Telaris ProInstall-200 are battery powered electrical installation testers. This manual applies to all models. All figures show the Model Telaris ProInstall-200.
• Do not use the product around explosive gas, vapor or in damp or wet environments. • Do not use test leads if they are damaged. Examine the test leads for damaged insulation, exposed metal, or if the wear indicator shows. Check test lead continuity. • Use only current probes, test leads, and adapters supplied with the product. • Measure a known voltage first to make sure that the product operates correctly. • Do not use the product if it is damaged. • Have an approved technician repair the product.
Operating the Tester Using the Rotary Switch Use the rotary switch (Figure 1 and Table 4) to select the type of test you want to perform. Understanding the Pushbuttons Use the rotary switch to select the type of test you want to perform.Use the pushbuttons to control operation of the tester, select test results for viewing, and scroll through selected test results. 3 4 13 14 7 12 8 1 9 2 NO TRIP 11 15 RCD 16 20 10 17 5 Number 6 19 18 Measurement Function 1 Starts the selected test.
11 Continuity. 12 Insulation resistance. 13 Loop impedance — Hi current trip mode 14 Loop impedance — No trip mode. 15 RCD tripping time. 16 RCD tripping level. 17 Volts 18 Phase rotation. 19 Earth resistance. 20 Rotary switch. Understanding the Display 21 22 23 24 25 26 L 40 27 28 39 38 32 Comp b 35 30 kA V Hz 34 33 36 Number 29 31 37 Descri ption 21 Displays the selected Memory mode. Memory modes are: Select (F1), Store (F2), Recall (F3), or Clear (F4).
Indicates the selected rotary switch setting. The measurement value in the primary display also corresponds to the switch setting. Rotary switch settings are: 25 Insulation RCD trip time Continuity RCD trip current Loop no trip Earth Loop hi current trip Phase Rotation Indicates the preset fault voltage limit. The default setting is 50 V. Some locations require the fault voltage be set to 25 V, as specified by local electrical 26 codes.
Input Terminals Use the rotary switch to select the type of test you want to perform. 43 42 Number 44 Descri ption 42 L (Line) 43 PE (Protective Earth) 44 N (Neutral) Using the IR Port The Model Telaris ProInstall-100 and Telaris ProInstall-200 have an IR (infrared) port, see Figure 23, which allows you to connect the tester to a computer and upload test data using a Amprobe PC software.
Over-temp 2 Wait while the tester cools down. Fault Voltage 4 Check the installation, in particular, the voltage between N and PE. Excessive Probe Resistance 6 Put the stakes deeper into the soil. Tamp down the soil directly around the stakes. Pour water around the stakes but not at the earth ground under test. Power-On Options To select a power-on option, press and the function key simultaneously and then release button. Power-on options are retained when the tester is turned OFF.
Making Measurements Measuring Volts and Frequency Figure 8. Volts Display/Switch and Terminal Settings To measure voltage and frequency: 1. Turn the rotary switch to the V position. 2. Use all (red, blue, and green) terminals for this test. You can use test leads or mains cord when measuring AC voltage. • The primary (upper) display shows the AC voltage. The tester reads AC voltage to 500 V. Press F1 to toggle the voltage reading between L-PE, L-N, and N-PE.
Measuring Continuity R LO Figure 10. Continuity Zero Display/Switch and Terminal Settings A continuity test is used to verify the integrity of connections by making a high resolution resistance measurement. This is especially important for checking Protective Earth connections. Note: In countries where electrical circuits are laid out in a ring, it is recommended that you make an end-to-end check of the ring at the electrical panel.
Loop Impedance (Line to Protective Earth L-PE) Loop impedance is source impedance measured between Line (L) and Protective Earth (PE). You can also ascertain the Prospective Earth Fault Current (PSC) that is the current that could potentially flow if the phase conductor is shorted to the protective earth conductor. The tester calculates the PSC by dividing the measured mains voltage by the loop impedance. The loop impedance function applies a test current that flows to earth.
To measure loop impedance—Hi current tri p mode: If no RCDs are present in the system under test, you can use the high current Line Earth (LPE) loop impedance test. position. 1. Turn the rotary switch to the 2. Connect all three leads to the L, PE, and N (red, green, and blue) terminals of the tester. Only the calibrated test lead which are in scope of supply must be used! The resistance of the calibrated test leads is subtracted from the result automatically. 3. Press F1 to select L-PE. The selected.
�Warning At this step,be careful not to select L-PE because a high current loop test will take place. Any RCDs in the system will tri p if you proceed. Note: Connect the leads in a single-phase test to the system live and neutral. To measure line-to-line impedance in a 3-phase system, connect the leads to 2 phases. 4. Press and release . Wait for the test to complete. • The primary (upper) display shows the line impedance. • The secondary (lower) display shows the Prospective Short Circuit Current (PSC).
�Warning • Leakage currents in the circuit following the residual current protection device may influence measurements. • The displayed fault voltage relates to the rated residual current of the RCD. • Potential fields of other earthing installations may influence the measurement. • Equi pment (motors,capacitors) connected downstream of the RCD may cause considerable extension of the tri pping time. Note: If the L and N terminals are reversed, the tester will auto-swap them internally and continue testing.
To measure RCD tri pping time using Auto mode: 1. Plug the tester into the outlet. 2. Turn the rotary switch to the position. 3. Press F1 to select the RCD current rating (10, 30, or 100 mA). 4. Press F2 to select Auto mode. 5. Press F3 to select the RCD test-current waveform. 6. Press and release The tester supplies ½x the rated RCD current for 310 or 510 ms (2 seconds in the UK). If the RCD trips, the test terminates. If the RCD does not trip, the tester reverses phase and repeats the test.
This test measures the RCD tripping current by applying a test current and then gradually increasing the current until the RCD trips. You can use the test leads or mains cord for this test. A 3 wire connection is required for testing of RCD type B. �Warning • Leakage currents in the circuit following the residual current protection device may influence measurements. • The displayed fault voltage relates to the rated residual current of the RCD.
RCD Mains Supply PE (L2/Green) N (L3/Blue) L (L1/Red) Figure 18. Connection for RCD Testing on IT Electrical Systems The test current flows through the upper side of the RCD, into the L terminal, and returns though the PE terminal. Measuring Earth Resistance Figure 19. Earth Resistance Display/Switch and Terminal Settings The earth resistance test is a 3-wire test consisting of two test stakes and the earth electrode under test. This test requires an accessory stake kit. Connect as shown in Figure 20.
To measure earth resistance: 1. Turn the rotary switch to the 2. Press and release position. . Wait for the test to complete. • The primary (upper) display shows the earth resistance reading. • Voltage detected between the test rods will be displayed in the secondary display. If greater than 10 V, the test is inhibited. • If the measurement is too noisy, Err 5 will be displayed. (The measured value accuracy is degraded by the noise).
Memory mode You can store measurements on the tester: • Telaris ProInstall-100 – up to 399 • Telaris ProInstall-200 – up to 1399 The information stored for each measurement consists of the test function and all user selectable test conditions. Data for each measurement is assigned a data set number, data subset number, and a data id number. Memory location fields are used as described below. Field Description Use the data set field (a) to indicate a location such as a room or electrical panel number.
• If the memory is not full, the data will be saved, the tester will automatically exit Memory mode and the display will revert back to the previous test mode. • If the data identity has been previously used, the display will show STO? Press F2 again to store the data, press F1 to choose another data identity, press to exit Memory mode. Recalling a Measurement To recall a measurement: 1. Press to enter Memory mode. 2. Press F3 to enter the Recall mode. 3.
To upload test results: 1. Connect the IR serial cable to the serial port on the PC. 2. Attach the IR adapter and the device to the tester as shown in Figure 23. 3. Start the Amprobe PC software program. 4. Press to turn on the tester. 5. Refer to the software documentation for complete instructions on how to upload data from the tester. MAINTAINING THE TESTER Cleaning Periodically wipe the case with a damp cloth and mild detergent. Do not use abrasives or solvents.
5. Replace the batteries and the battery door. Note: All stored data will be lost if the batteries are not replaced within approximately one minute 6. Secure the door by turning the screws one-quarter turn clockwise. Figure 24. Replacing the Batteries Testing the Fuse 1. Turn the rotary switch to switch setting. 2. Short the leads and press and hold 3. If the fuse is bad, FUSE or Err1 will appear on the display to indicate the tester is damaged and needs repair.
DETAILED SPECIFICATIONS Features Measurement Function Telaris ProInstall-100 Telaris ProInstall-200 Voltage & Frequency √ √ Wiring polarity checker √ √ Insulation Resistance √ √ Loop & Line Resistance √ √ Prospective Short-Circuit current (PSC/IK) √ √ RCD switching time √ √ RCD tripping level √ √ Automatic RCD test sequence √ √ Test pulse current sensitive RCDs (Type A) √ √ Test smooth dc sensitive RCDs (Type B) None √ Earth Resistance None √ Phase Sequence Indicator √
Safety Complies with EN61010-1 Ed 3. Overvoltage Category: 500 V/CAT III 300 V/CAT IV Measurement Category III is for measurements performed in the building installation. Examples are distribution panels, circuit breakers, wiring and cabling. Category IV equipment is designed to protect against transients from the primary supply level, such as an electrical meter or an overhead or underground utility service.
Test Probe Zeroing Press the F3 to compensate the test probe. Can subtract up to 2 Ω of lead resistance. Error message for >2 Ω. Live Circuit Detection Inhibits test if terminal voltage >10 V ac detected prior to initiation of test. Insulation Resistance Measurement (RISO) Test Voltages 100-250-500-1000 V Accuracy of Test Voltage (at rated test current) +10 %, -0 % Test Voltage 100 V Insulation Resistance Range Resolution Test Current 1 mA @ 100 kΩ 100 kΩ to 20 MΩ 0.01 MΩ 20 MΩ to 100 MΩ 0.
Range Resolution Accuracy [1] 20 Ω 0.01 Ω No Trip mode: ±(4 % + 6 digits) 200 Ω 0.1 Ω ±(5 %) 2000 Ω 1Ω ±6 %[2] Hi Current mode: ±(3 % + 4 digits) Note: [1] Valid for resistance of neutral circuit <20 Ω and up to a system phase angle of 30 °. [2] Valid for mains voltage >200 V.
Test Signals RCD Type Test Signal Descri ption AC (sinusoidal) The waveform is a sinewave starting at zero crossing, polarity determined by phase selection (0 ° phase starts with low to high zero crossing, 180 ° phase starts with high to low zero crossing). The magnitude of the test current is IPn x Multiplier for all tests.
Maximum Tri p Time RCD IPN Tri p Time Limits AC G, A, B X1 Less than 300 ms AC G-S, A-S, B-S X1 Between 130 ms and 500 ms AC G, A, B X5 Less than 40 ms AC G-S, A-S, B-S X5 Between 50 ms and 150 ms RCD/FI-Tri pping Current Measurement/Ramp Test ( IPN ) Measurement Range Current Range Step Size 30 % to 110 % of RCD rated current[1] 10 % of IPN[2] Type G Type S Measurement Accuracy 300 ms/step 500 ms/step ±5 % Notes [1] 30 % to 150 % for Type A IPN >10 mA 30 % to 210 % for Type A IPN
Phase Sequence Indication Icon icon Phase Sequence indicator is active. Display of Phase Sequence Mains Input Voltage Range (phase-tophase) Displays “1-2-3” in digital display field for correct sequence. Displays “3-2-1” for incorrect phase. Dashes in place of a number indicate a valid determination could not be made. 100 to 500 V Mains Wiring Test Icons ( ) indicate if L-PE or L-N terminals are reversed.
Visit www.Amprobe.com for • • • • Catalog Application notes Product specifications User manuals Amprobe® www.Amprobe.com info@amprobe.com Everett, WA 98203 Tel: 877-AMPROBE (267-7623) Amprobe® Europe Beha-Amprobe In den Engematten 14 79286 Glottertal, Germany Tel.