Datasheet

62
50 A
AC
Output
Analog
Measurement and test equipment in accordance with EN 61557 |
Accessories
CHB1
Leakage current clamp adapter
(AC)
Functions
Clamp adapter for measuring leakage currents
in conjunction with a multimeter
Stray current measurement in connection with
GT-800
Product information
Current output, output signal:
1 mA corresponds to 1 A test current
Jaw opening 30 mm
Fixed test leads
No batteries required
Not suitable for earth measurements
Technical specifications
Ranges
Current AC 1mA ...50 A
Basic accuracy ± (6 % + 0.5 mA)
Output current 1 mA/A
Frequency range 40 Hz…10 kHz
Protection class IP 30
Pollution degree 2
Measurement category CAT II/600 V
Safety cert.: DIN VDE 0411/EN 61010/IEC
61010
Jaw opening approx. 30 mm
Length of connection cable approx. 1.5 m
Dimensions approx. 140 x 45 x 20 mm
Weight approx. 75 g
Ordering Information:
Description Model Article no.
CHB1 1311 2390055
PAT-BRUSH
Brush probe
• Measurement of protective earth resistance and
touch current
• Enables stray current measurement on moving or
rotating parts
• Reduces transition resistance due to multiple
contacting
• Simplifies measurement on refined or oxidized
surfaces
• Max. test current 0.2 A
• 4 mm plug-in technology
• Total length 190 mm, brush dimensions 60 mm x
Æ20mm
• With protective packaging for safe storage
• Can be used for all testing equipment
Ordering Information:
Description Model Article no.
Brush probe PAT-BRUSH 4151667
ADAPTER-PE
Adapters for protective earth
• Measurement of protective earth resistance
with securely attached equipment
• Secure contacting of the protective earth to a
Schuko socket
• 4 mm plug-in technology
Ordering Information:
Description Model Article no.
Adapter for protective
earth ADAPTER-PE
4151659
PA-1
Adapter for 3-pole plug
Measurement of protective earth resistance and
insulation
• For C5 power cable types
(DIN VDE 0623, IEC/EN60320)
Ordering Information:
Description Model Article no.
Adapter for
3-pole plug PA-1
4362289

Summary of content (1 pages)