Manual

APPLICATIONNOTEANBEIH2038 Date:15/02/12
ANBEIH2038ModbusRTUControlandRegisterMapping
1
BFIApplicationsSupportLibrary
ApplicationNote ANBEIP2038
Title ModbusRTUControlandRegisterMapping
RelatedProducts BeijerFrequencyInverterH2
Level
3
1Fundamental‐Nopreviousexperiencenecessary
2BasicSomeBasicdrivesknowledgerecommended
3AdvancedSomeBasicdrivesknowledgerequired
4ExpertGoodexperienceintopicofsubjectmatterrecommended
Overview:
ThisdocumentprovidesinformationontheModbusRTUmemorymappingthatisimplementedintheBeijerFrequencyInverter
H2drives,detailingwhichaddressesareusedtoreadandwritedatato/fromtheBeijerFrequencyInverterH2inaModbusRTU
network.AlldataregisterswithinthedriveareHolding
Registers,andcanbeaccessedbymeansoftheModbuscommands03
ReadMultipleHoldingRegistersand06WriteSingleRegisteronly.
TheModbusRequestPDU specifies the starting registeraddressandthe numberofregisters.In this case, with some Modbus
Master Systems, it may be necessary to subtract
1 from the register number (e.g. some systems treat holding register 1 as
address0).
TheManufactureradoptsapolicyofcontinuousimprovementandwhilsteveryefforthasbeenmadetoprovideaccurateandup
todateinformation,theinformationcontainedinthisdocumentshouldbeusedforguidancepurposes
onlyanddoesnotform
thepartofanycontract.
MODBUSRTUProtocolSpecification:
ThefollowingtablehighlightsthespecificationfortheModbusRTUimplementation.
Protocol ModbusRTU
Errorcheck CRC
Baudrate ParameterSelectableasfollows:
9600bps,19200bps,38400bps,57600bps,115200bps(default)
Dataformat ParameterSelectableasfollows:
1startbit,8databits,1stopbits,noparity.(default)
1startbit,8databits,2stopbits,noparity.
1startbit,8databits,1stopbits,evenparity.
1startbit,8databits,1stopbits,odd
parity.
Physicalsignal RS485(2wire)