Register8:OutputCurrent
Thisregisterdisplaystheoutputcurrentfromthedrive.
Thedatais16bitintegerwithonedecimalplace.E.g.156=15.6A,12=1.2A.
Register10:OutputPower
Thisregisterdisplaystheoutputpowerlevel.
Thedatais16bitintegerwithtwodecimalplaces.E.g.
1000=10.00kW
Register11:Digitalinputstatus
Thevalueinthisregisterrepresentsthedigitalstatusofthedrivecontrolinputterminals.Bit0indicatesthestatusofInput1,Bit
1indicatesthestatusofInput2etc...
Register12:RatingID
Thevalueinthisparameter
includesspecificdriveID information,andisnotrecommendedtobeusedbycustomer. Formore
informationregardingthisparameter,pleasecontactyourlocaldrivesalespartner.
Register13:Powerrating
This gives the drive power rating information to two decimal places, e.g.075 = 0.75.The unit of this register
depends on the
drivetype(KW/HP)
Register14:SupplyVoltagelevel
Thisregistergivestheratedinputvoltageforthedrive.
i.e. 230:230Vnominal(200240+/‐10%) 
400:400Vnominal(380480+/‐10%)
460:460Vnominal(380480Volts+/
‐10%)
Register15:IOsoftwareversion
ThisregistercontainsthedriveIOsoftwareversioninfo.Thevalueincludestwodecimalplaces.
i.e.100meansversion1.00
Register16:Motorcontrolprocessorsoftwareversion
Thisregistercontainsthesoftwareversioninfoofthemotorcontrolprocessor.Thevalueincludestwo
decimalplaces.E.g.100
meansversion1.00
Register17:Drivetype
Thisregistergivesthedriveinternaltypecode.
Register20:Analoginput1value
Thisregistergivesthevalueoftheanalogsignalappliedtoanaloginput1afteranyscalingandoffsetshavebeenapplied.The
valueis
a16bitintegerwhereareturnedvalueof4096representsthemaximuminputvalue,e.g.100%.
Register21:Analoginput2value
Thisregistergivesthevalueoftheanalogsignalappliedtoanaloginput2afteranyscalingandoffsetshavebeenapplied.The
valueisa16
bitintegerwhereareturnedvalueof4096representsthemaximuminputvalue,e.g.100%.
Register22:PreRampSpeedReferenceValue
Thisregistercontainsthereferencespeedinformationthat being usedbythedriveformotorspeedcontrol. The data is in Hz
andwithonedecimalplace(i.e.
234=23.4Hz)
Register23:DCbusvoltage
ThisregistercontainsdriveinternalDCbusvoltageinformation.Thevalueisdisplayedasvolts,withnodecimalplaces.
Register24:Drivetemperature
Thisregistercontainsdrivetemperatureinformation.DataisinCelsiuswithnodecimalplace.