Manual
APPLICATIONNOTEAN‐BEI‐H2‐038 Date:15/02/12
AN‐BEI‐H2‐038ModbusRTUControlandRegisterMapping
8
Parameter Register
Number
Description Range Scaling Type
P2‐18 218 Userrelay2outputfunctionselect
0:Driverunning
1:Drivehealthy
2:Motorattargetspeed
3:MotorSpeed>0
4:MotorSpeed>limit
5:MotorCurrent>limit
6:MotorTorque>limit
7:2
nd
Analoginput>limit
U16
P2‐19 219 Userrelay2upper limit P2‐20to2000 1=0.1% U16
P2‐20 220 Userrelay2lowerlimit 0toP2‐19 1=0.1% U16
P2‐21 221 Displayscalingfactor 0to30000 1=0.001 U16
P2‐22 222 Displayscalingsource
0:MotorSpeed
1:MotorCurrent
2:2
nd
Analoginput
U16
P2‐23 223 ZeroSpeedholdingtime 0to600 1=0.1 U16
P2‐24 224 Effectiveswitchingfrequency
0=4kHz
1=8kHz
2=12kHz
3=16kHz
4=24kHz
5=32kHz
U16
P2‐25 225 Fastdecelerationramptime 0to3000 1=0.1s U16
P2‐26 226 Spinstartenable
0:Disabled
1:Enabled
1
U16
P2‐27 227 Standbymode 0to2500 1=0.1 U16
P2‐28 228 Slavespeedscalingcontrol
0:Disabled
1:Presetbyslavespeedscaling
2:P2‐33scaling+analogin1offset
3:P2‐33scaling+analogin1scaling
U16
P2‐29 229 SlaveSpeedscalingfactor‐5000to5000 1=0.1 S16
P2‐30 230 Analoginput1format
0=0‐10V
1=10‐0V
2=‐10‐10V,
3=0‐20mA,
4=t4‐20mA,
5=r4‐20mA,
6=t20‐4mA,
7=r20‐4mA
U16
P2‐31 231 Analoginput1scaling 0to5000 1=0.1 U16
P2‐32 232 Analoginput1offset‐5000to5000 1=0.1 S16
P2‐33 233 Analoginput2format
0=0‐10V
1=10‐0V
2=PTCThermistor
3=0‐20mA,
4=t4‐20mA,
5=r4‐20mA,
6=t20‐4mA,
7=r20‐4mA
U16
P2‐34 234 Analoginput2scaling 0to5000 1=0.1 S16
P2‐35 235 Analoginput2offset‐5000to5000 1=0.1 U16
P2‐36 236 Startmodeselect
0=Edge‐r
1=Auto‐0
2=Auto‐1
3=Auto‐2
4=Auto‐3
5=Auto‐4
6=Auto‐5
U16
P2‐37 237 Keypadrestartspeed
0:Minimumspeed
1:Previouskeypadspeed
2:CurrentrunningSpeed
3:PresetSpeed8
U16
P2‐38 238 Mainslossstopcontrol
0:Mainslossridethrough
1:CoasttoStop
2:Fastramptostop
U16
P2‐39 239 ParameterLock
0:Unlocked
1:Locked
U16
P2‐40 240
Extendedparameteraccesscode
definition
0...9999
U16