Manual

APPLICATIONNOTEANBEIH2038 Date:15/02/12
ANBEIH2038ModbusRTUControlandRegisterMapping
8
Parameter Register
Number
Description Range Scaling Type
P218 218 Userrelay2outputfunctionselect
0:Driverunning
1:Drivehealthy
2:Motorattargetspeed
3:MotorSpeed>0
4:MotorSpeed>limit
5:MotorCurrent>limit
6:MotorTorque>limit
7:2
nd
Analoginput>limit
U16
P219 219 Userrelay2upper limit P220to2000 1=0.1% U16
P220 220 Userrelay2lowerlimit 0toP219 1=0.1% U16
P221 221 Displayscalingfactor 0to30000 1=0.001 U16
P222 222 Displayscalingsource
0:MotorSpeed
1:MotorCurrent
2:2
nd
Analoginput
U16
P223 223 ZeroSpeedholdingtime 0to600 1=0.1 U16
P224 224 Effectiveswitchingfrequency
0=4kHz
1=8kHz
2=12kHz
3=16kHz
4=24kHz
5=32kHz
U16
P225 225 Fastdecelerationramptime 0to3000 1=0.1s U16
P226 226 Spinstartenable
0:Disabled
1:Enabled
1
U16
P227 227 Standbymode 0to2500 1=0.1 U16
P228 228 Slavespeedscalingcontrol
0:Disabled
1:Presetbyslavespeedscaling
2:P233scaling+analogin1offset
3:P233scaling+analogin1scaling
U16
P229 229 SlaveSpeedscalingfactor‐5000to5000 1=0.1 S16
P230 230 Analoginput1format
0=010V
1=100V
2=‐1010V,
3=020mA,
4=t420mA,
5=r420mA,
6=t204mA,
7=r204mA

U16
P231 231 Analoginput1scaling 0to5000 1=0.1 U16
P232 232 Analoginput1offset‐5000to5000 1=0.1 S16
P233 233 Analoginput2format
0=010V
1=100V
2=PTCThermistor
3=020mA,
4=t420mA,
5=r420mA,
6=t204mA,
7=r204mA

U16
P234 234 Analoginput2scaling 0to5000 1=0.1 S16
P235 235 Analoginput2offset‐5000to5000 1=0.1 U16
P236 236 Startmodeselect
0=Edger
1=Auto0
2=Auto1
3=Auto2
4=Auto3
5=Auto4
6=Auto5
U16
P237 237 Keypadrestartspeed
0:Minimumspeed
1:Previouskeypadspeed
2:CurrentrunningSpeed
3:PresetSpeed8
U16
P238 238 Mainslossstopcontrol
0:Mainslossridethrough
1:CoasttoStop
2:Fastramptostop
U16
P239 239 ParameterLock
0:Unlocked
1:Locked
U16
P240 240
Extendedparameteraccesscode
definition
0...9999
U16