Owner's manual
APPLICATIONNOTEAN‐BEI‐P2‐038 Date:15/02/12
AN‐BEI‐P2‐038ModbusRTUControlandRegisterMapping
1
BFIApplicationsSupportLibrary
ApplicationNote AN‐BEI‐P2‐038
Title ModbusRTUControlandRegisterMapping
RelatedProducts BeijerFrequencyInverterP2
Level
3
1–Fundamental‐Nopreviousexperiencenecessary
2–Basic–SomeBasicdrivesknowledgerecommended
3–Advanced–SomeBasicdrivesknowledgerequired
4–Expert–Goodexperienceintopicofsubjectmatterrecommended
Overview:
ThisdocumentprovidesanoverviewoftheModbusRTUmemorymappingthatisimplementedintheBeijerFrequencyInverter
P2 drive, detailing which addresses areused to read andwrite data to / from Beijer Frequency Inverter P2 in a Modbus RTU
network.AlldataregisterswithinthedriveareHolding
Registers,andcanbeaccessedbymeansoftheModbuscommands03
ReadMultipleHoldingRegistersand06WriteSingleRegisteronly.
TheModbusRequestPDUspecifiesthestartingregisteraddressandthenumberofregisters.Inthiscase,with some Modbus
Master Systems, it may be necessary to subtract
1 from the register number (e.g. some systems treat holding register 1 as
address0).
TheManufactureradoptsapolicyofcontinuousimprovementandwhilsteveryefforthasbeenmadetoprovideaccurateandup
todateinformation,theinformationcontainedinthisdocumentshouldbeusedforguidancepurposes
onlyanddoesnotform
thepartofanycontract.
MODBUSRTUProtocolSpecification:
ThefollowingtablehighlightsthespecificationfortheModbusRTUimplementationinBeijerFrequencyInverterP2
Protocol ModbusRTU
Errorcheck CRC
Baudrate 9600bps, 19200bps, 38400bps, 57600bps, 115200bps
(default)
AdjustableinParameterP5‐03
Dataformat 1startbit,8databits,1stopbits,noparity.
1startbit,8databits,2stopbits,noparity.
1startbit,8databits,1stopbits,evenparity.
1startbit,8databits,1stopbits,oddparity.
AdjustableinParameterP5‐04
Physicalsignal RS485(2‐wire)