Instruction Manual
Installation
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
• Ensurethattheoperatorpanelandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrorsincommunicationmay
occur.
• Theoperatorpanelmustbebroughttoambienttemperaturebeforeitisstarted
up. Ifcondensationf orms,ensurethattheoperatorpanelisdrybeforeconnecting
ittothepoweroutlet.
• Ensurethatthevol tageandpolarityofthepowersourceiscorrect.
• Useonlyshieldedc ommunicationcables.
• Separatehighvoltagecablesfromsignalandsupplycables.
24V DC
RS422/RS485
24V DC
1
CF CARD
B
A
C
D
RS232
Controller
Power
Ethernet
– Connect cable A.
– Connect cable B, using an M5 screw and a groundin g conductor (as short
as possible) with a cross-section of minimum 2.5 mm
2
.
– Connect cable C.
– Connect cable D.
5.
Carefully remove the laminated film over the operator panel display, to avoid
static electricity that could damage the panel.
BeijerElectronics, MAEN008
12