Owner manual

iXT10AInstallationGuide
1SafetyPrecautions
Both the installer and the owner and/or operator of the operator panel must read
and understand this installation manual.
1.1 General
Read the safety precautions carefully.
Check the delivery for transportation damage. If damage is found, notify the
supplier as soon as possible.
Do not use the operator panel in an environment with high explosive hazards.
The supplier is not responsible for modified, altered or reconstructed
equipment.
Use only parts and accessories manufactured according to specifications of
the supplier.
Read the installation and operating instructions carefully before installing,
using or repairing the operator panel.
Never allow fluids, metal filings or wiring debris to enter any openings in the
operator panel. This may cause fire or electrical shock.
Only qualified personnel may operate the operator panel.
Storingthe operatorpanel where the temperature is lower/higher than
recommended in this manual can cause the LCD display liquid to
congeal/become isotopic.
The LCD display liquid contains a powerful irritant. In case of skin contact,
wash immediately with plenty of water. In case of eye contact, hold the eye
open, flush with plenty of water and get medical attention.
Thefiguresinthismanualservesanillustrativepurpose. Becauseofthemany
variables associated with any particular installation, the supplier cannot
assume responsibility for actual use based on the figures.
The supplier neither guarantees that the operator panel is suitable for your
particular application, nor assumes responsibility for your product design,
installation or operation.
It is recommendedto turn on and shut down the operator panel at least once
before installing any components/cards or b efore connecting the operator
panel to external devices, like for example serial devices.
1.2 ULandcULInstallation
Caution:
ThissectionisonlyvalidforULlabelediXT10Apanels.
This equipment is suitable for use in Class 2 non-hazardous loca tions only.
[Combinations of equipment in yoursystem are subject to investigation by
the local authority having jurisdiction at the time of installation].
All devices have to be supplied by a Class 2 power supply.
Warning:
Donotdisconnectequipmentunlesspowerhasbeen removedor
theareaisknowntobenon-hazardous
For Canada also AVERTISSEMENT AVANT DE DECONNECTER
L’EQUIPEMENT, COUPER LE COURANT OUS’ASSURER QUE
L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.
Warning:
OnlyULandcULapprovedexpansionunitsareallowedtobe
connectedtotheportdesignated“EXPANSION”. Atthemoment
therearenosuchunitsevaluated orallowed.
Warning:
Donotreplaceexpansionunitunlesspowerhasbeenswitchedoff
ortheareaisknowntobenon-hazardous.
This product contains a battery; this must only be changed in an area known
to be non-hazardous.
Replace the battery with a BR 2032 battery. Use of another type of battery
may present a risk of fire or explosion.
Warning:
Batterymayexplodeifmistreated. Donotrecharge,disassemble
ordisposeofinre.
For u se on a flat surface of a type 4X enclosure indoor use only.
Use75degreeconductorsonly
Usecopper conductors only
To make wiring connections to the power supply connector, follow the table
with cable and torque specifications below:
TerminalBlockNo. WireSizeAWG TQLb.In.
X1/X100Phoenixconnectors
AWG 3012
5–7
X1/X100Anytekconnectors
AWG24–12 3.5
These devices are Class 2 supplied programmable controllers (industrial PCs)
for the use in industrial control equipment and are intended to be (front) panel
mounted (Type 1 and 4x for indoor use only).
1.3 DuringInstallation
The operator panel is designed for stationary installation on a plane surface,
where the followingconditions are fulfilled:
no high explosive risks
no strong magnetic fields
no direct sunlight
no large, sudden temperature changes
Install the product according to the accompanying installation instructions.
Groundthe product according to the accompanying installation instructions.
Only qualified personnel may install the operator panel.
Separate the high voltage, signal and supply cables.
Make sure that the voltage and polarity of the power source is correct before
connecting the product to the power outlet.
Peripheral equipment must be appropriate for the application and location.
1.4 DuringUse
Keep the operator panel clean.
Emergency stop and other safety functions may not be controlled from the
operator panel.
Do not use too much force or sharp objects when touching the keys,
touchscreen etc.
1.5 ServiceandMaintenance
Only qualified personnel should carry out repairs.
The agreed warranty applies.
Before carrying out any cleaning or maintenance operations, disconnect the
equipment from the electrical supply.
Clean the display and surrounding front cover with a soft cloth and mild
detergent.
Replacing the battery incorrectly may result in explosion. Only use batteries
recommended by the supplier. Duringthe warranty period, the battery needs
to be replaced by an authorized Beijer Electronics service center.
1.6 DismantlingandScrapping
The operator panel or parts thereof shall be recycledaccording to local
regulations.
The following components contain substances that might be hazardou s
to health and the environment: lithium battery, electrolytic capacitor and
display.
1.7 AppearanceofAirinTouchScreen
Thelayerstructureofthetouchscreencontainsairandinrarecases
appearance of bubbles can arise. This is purely cosmetic and does not affect
any functionality of the panel. The appearance can occur under certain
environmental conditions such as temperature, humidity, and atmospheric
pressure.
2Installation
2.1 SpaceRequirements
Maximum installation plate thickness: 8 mm
Space requirements in millimeters when installing the operator panel:
10022850
100
100
280
50
Note:
Thedimensions on thedrawingarenot proportional.
2.2 InstallationProcess
The following is needed:
A Phillips/slot screwdriver
1.
Unpack and check the delivery. Ifdamage is found, notify the supplier.
Note:
Placetheoperatorpanelonastablesurfaceduring installation.
Droppingthepanelorlettingitfallmaycausedamage.
2.
Use the cut out dimensions that are included on the outline drawing, found
in section Operator Panel Drawings and in the Technical Data table, to cut a
correct opening in the cabinet. A separate cut out drawing is available for
download from the Beijer Electronicswebsite.
3.
Secure the operator panel in position using all the fastening holes and the
provided brackets and screws:
x 8 0.5 - 1.0 Nm
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
Ensurethattheoperatorpanelandthecontrollersystemhavethesame
electricalgrounding(referencevoltagelevel),otherwiseerrorsin
communicationmayoccur.
Theoperatorpanelmustbebroughttoambienttemperaturebeforeit
isstartedup. Ifcondensationforms,ensurethattheoperatorpanelis
drybeforeconnectingittothepoweroutlet.
Ensurethatthevoltageandpolarityofthepowersourceiscorrect.
Useonlyshieldedcommunicationcables.
Separatehighvoltagecablesfromsignaland supplycables.
24V DC
RS232/
RS422/
RS485
24V DC
A
D
Controller
Power
B
Ethernet
C
Connect cable A.
Connect cable B, using an M5 screw and a grounding conductor (as
short as possible) with a cross-section of minimu m 2.5 mm
2
.
Connect cable C.
Connect cable D. The recommended cross-section of the cable is
1.5 mm
2
.
5.
Carefully remove the laminated film over the operator panel display, to avoid
static electricity that could damage the panel.
Note:
OnlyforiXT10Apanels withpartnumber630000301:
Whenconnectingtheoperatorpaneltothepoweroutletforthersttime,
makesurenot toint erruptpowerfora minimum of48 hoursinorde r tochar ge
thebatterycompletely. Afterthat,thebatterymaybechargedpartly during
ashorterperiodoftime.
2.2.1 ConnectionstotheController
For i nformation about the cables to be used when connecting the operator panel to
the controller, please refer to the help file for the driver in question.
2.2.2 OtherConnectionsandPeripherals
Cables, peripheral equipment and accessories must be suitable for the application
and its environment. For further details or recommendations, please refer to the
supplier.
3TechnicalData
Parameter
iXT10A
Frontpanel,W×H×D
280×228×7mm
Cutoutdimensions,W×H
262×209mm
Mountingdepth 44mm(144mminclud ing clearance)
Standalonemounting
VESA75×75
Note: MaximumscrewlengthforVESA
mountingis4mm. Usageoflongerscrews
mayleadtodamage.
Frontpanelseal
IP65
Rear panel seal
IP20
Touchscreenmaterial Polyesterong lass,resistive.
Overlay: AutoexEBA 180L
(1)
.
Touchscreenoperations 1millionngertouchoperations
Reversesidematerial Powder-coated aluminum
Framematerial Powder-coated aluminum
Weight 1.5 kg
Serialportfor
COM1RS232 and
COM2RS422/RS485
9-pinD-subcontactwithRS232RTS/CTS,
chassis-mountedfemalewithstandard
lockingscrews4-40UNC
Serialportfor
COM3RS232 and
COM4RS422/RS485
9-pinD-subcontactwithRS232RTS/CTS,
chassis-mountedfemalewithstandard
lockingscrews4-40UNC
Ethernet 1×10Base-T/100Base-T(shieldedRJ45)
USB 1×USB Host2.0,maxoutputcurrent200mA
Processor
400MHzARM9
Externalstoragemedia 1×SDcard(optional). Onlycompatible
withthestandardSDformatwith up to 2 GB
storage capacity.
Flashmemory
(applicationmemory)
128MBSSD (NANDFlash)
MemoryRAM 128MB(DDR2)
LED
1×blue/redsoftwareprogrammable
Real time clock Y es (on chip)
Battery
(2)
LithiumbatterytypeBR2032,soldered
orrechargeablebattery
(2)
(Seiko
InstrumentsPartNo. MS920-SEorsimilar),
soldered
Powerconsumptionat
ratedvoltage
9.6W
Fuse
InternalDCfuse,2.0AT,5×20mm
Power supply
+24VDC(18-32VDC)
CE:Thepowersupplymustconformwith the
requirementsaccordingtoIEC60950and
IEC61558-2-4.
ULandcUL: The power supplymustconform
withtherequirementsforclass IIpower
supplies.
Display TFT-LCD withLEDbacklight. 640×480pixels,
64kcolors