A.3.3. 3 (0x03) Read Holding Registers
This function code is used to read the contents of a contiguous block of holding registers in a remote device. The
Request PDU specifies the starting register address and the number of registers.
The register data in the response message are packed as two bytes per register, with the binary contents right
justified within each byte. For each register, the first byte contains the high order bits and the second contains the
low order bits.
Request
Field name
Example
RTU
ASCII
ASCII (bus line)
Start of Frame
-
t1-t2-t3
,
0x3A
Slave Address
0x07
0x07
07
0x30, 0x37
Function Code
0x03
0x03
03
0x30, 0x33
Starting Address Hi
0x08
0x08
08
0x30, 0x38
Starting Address Lo
0x00
0x00
00
0x30, 0x30
Quantity of Register Hi
0x00
0x00
00
0x30, 0x30
Quantity of Register Lo
0x02
0x02
02
0x30, 0x32
Error Check (CRC/LRC)
-
0xC6, 0x0D
EC
0x45, 0x43
End of Frame
-
t1-t2-t3
CR, LF
0x0D, 0xA
Response
Field name
Example
RTU
ASCII
ASCII (bus line)
Start of Frame
-
t1-t2-t3
,
0x3A
Slave Address
0x07
0x07
07
0x30, 0x37
Function Code
0x03
0x03
03
0x30, 0x33
Byte Count
0x04
0x04
04
0x30, 0x34
Output Register #0 Hi
0x11
0x11
11
0x31, 0x31
Output Register #0 Lo
0x22
0x22
22
0x32, 0x32
Output Register #1 Hi
0x33
0x33
33
0x33, 0x33
Output Register #1 Lo
0x44
0x44
44
0x34, 0x34
Error Check (CRC/LRC)
-
0x2D, 0xC6
38
0x33, 0x38
End of Frame
-
t1-t2-t3
CR, LF
0x0D, 0xA
- In case of address 0x0800, 0x0801 output register value: 0x1122, 0x3344.