A.3.8. 15 (0x0F) Write Multiple Coils
This function code is used to force each coil in a sequence of coils to either ON or OFF in a remote device. The
Request PDU specifies the coil references to be forced. Coils are addressed starting at zero. A logical '1' in a bit
position of the field requests the corresponding output to be ON. A logical '0' requests it to be OFF.
The normal response returns the function code, starting address, and quantity of coils forced.
Request
Field name
Example
RTU
ASCII
ASCII (bus line)
Start of Frame
-
t1-t2-t3
,
0x3A
Slave Address
0x07
0x07
07
0x30, 0x37
Function Code
0x0F
0x0F
0F
0x30, 0x46
Starting Address Hi
0x10
0x10
10
0x31, 0x30
Starting Address Lo
0x00
0x00
00
0x30, 0x30
Quantity of Outputs Hi
0x00
0x00
00
0x30, 0x30
Quantity of Outputs Lo
0x0A
0x0A
0A
0x30, 0x41
Byte Count
0x02
0x02
02
0x30, 0x32
Output Value #0
0x55
0x55
55
0x35, 0x35
Output Value #1
0x01
0x01
01
0x30, 0x31
Error Check (CRC/LRC)
-
0x21, 0XC9
78
0x37, 0x38
End of Frame
-
t1-t2-t3
CR, LF
0x0D, 0xA
Response
Field name
Example
RTU
ASCII
ASCII (bus line)
Start of Frame
-
t1-t2-t3
,
0x3A
Slave Address
0x07
0x07
07
0x30, 0x37
Function Code
0x0F
0x0F
0F
0x30, 0x46
Starting Address Hi
0x10
0x10
10
0x31, 0x30
Starting Address Lo
0x00
0x00
00
0x30, 0x30
Quantity of Outputs Hi
0x00
0x00
00
0x30, 0x30
Quantity of Outputs Lo
0x0A
0x0A
0A
0x30, 0x41
Error Check (CRC/LRC)
-
0xD1, 0x6A
D0
0x44, 0x30
End of Frame
-
t1-t2-t3
CR, LF
0x0D, 0xA
- In case of address 0x1015~0x1000 output bit value: 00000000_00000000 changes to 00000001_01010101.