A.3.9. 16 (0x10) Write Multiple Registers
This function code is used to write a block of contiguous registers (1 to approx. 120 registers) in a remote device.
The requested written values are specified in the request data field. Data is packed as two bytes per register.
The normal response returns the function code, starting address, and quantity of registers written.
Request
Field name
Example
RTU
ASCII
ASCII (bus line)
Start of Frame
-
t1-t2-t3
,
0x3A
Slave Address
0x07
0x07
07
0x30, 0x37
Function Code
0x0F
0x0F
0F
0x30, 0x46
Starting Address Hi
0x08
0x08
08
0x30, 0x38
Starting Address Lo
0x00
0x00
00
0x30, 0x30
Quantity of Registers Hi
0x00
0x00
00
0x30, 0x30
Quantity of Registers Lo
0x02
0x02
02
0x30, 0x32
Byte Count
0x04
0x04
04
0x30, 0x34
Register Value #0 Hi
0x11
0x11
11
0x31, 0x31
Register Value #0 Lo
0x22
0x22
22
0x32, 0x32
Register Value #1 Hi
0x33
0x33
33
0x33, 0x33
Register Value #1 Lo
0x44
0x44
44
0x34, 0x34
Error Check (CRC/LRC)
-
0x3B, 0x12
31
0x33, 0x31
End of Frame
-
t1-t2-t3
CR, LF
0x0D, 0xA
Response
Field name
Example
RTU
ASCII
ASCII (bus line)
Start of Frame
-
t1-t2-t3
,
0x3A
Slave Address
0x07
0x07
07
0x30, 0x37
Function Code
0x0F
0x0F
0F
0x30, 0x46
Starting Address Hi
0x08
0x08
08
0x30, 0x38
Starting Address Lo
0x00
0x00
00
0x30, 0x30
Quantity of Outputs Hi
0x00
0x00
00
0x30, 0x30
Quantity of Outputs Lo
0x02
0x02
02
0x30, 0x32
Error Check (CRC/LRC)
-
0x43, 0xCE
DF
0x44, 0x46
End of Frame
-
t1-t2-t3
CR, LF
0x0D, 0xA
- In case of address 0x0800, 0x0801 output register value: 0x0000, 0x0000 changes to 0x1122, 0x3344.