Additional Installation Tips
Note:
Thegroundingwiresshould beshortandtheconductorshouldhavealargearea.
Along,thingroundingwirehasaveryhigh impedance(resistance)athighfrequencies
anddoesnotguidedisturbances to the ground.
Multi-wireconductorsareb etter thans inglewireconductorswiththesamearea.
Abraided conductor wirewiththesame areaisevenbetter. Thebestisashort,thick
groundingbraid.
6.2 EthernetConnectioninthe
OperatorPanel
1
2
3
4
5
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Industrial Ethernet
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and
unshielded
0.1 μF
250 V
1-1
3-3
8-8
2-2
In some industrial units for Ethernet, the RJ45 contact’s shield is connected to the
chassis via a capacitor, see 1 in drawing above.
The operator panel’s Ethernet shield is directly connected to the chassis, see 2 in
drawing above.
1.
Check whether the other Ethernet unit has its shield directly grounded or
grounded via a capacitor.
Note:
Inmanycases,connectingtheshieldedEthernetcablingtothechassisatbothendsis
inappropriate. Humor groundingloopscanoccur. Unshielded cabling may even result
infewercommunicationerrors.