User's Guide

10
Parameter Default Setting Ranges
1 Time/Date 2018
11
-
20 1:11AM
2 System Type Heat only
conventional
Heat only conventional
Cool only conventional
1 stage heat and cool conventional
2 stage heat pump with Aux
1 stage heat pump with Aux and Emer
2 stage heat and cool conventional
2 stage heat pump with Aux and Emer
2 stage heat pump with Aux
3 Fan Control In
Heating
0 0 - Thermostat control fan (default)
1
-
Equipment control fan
4 O/B Terminal
Energized
0 0 - Directional valve opens with cooling
(default)
1 - Reversing valve opens with heating
5 Away Heating
Temp
40 / 4 °F range: 40 - 90
°C range: 4 - 32
6 Away Cooling
Temp
99 / 37 °F range: 50 - 99
°C range: 10
-
37
7 ECO Heating
Temp
64 / 18 °F range: 40 - 90
°C range: 4
-
32
8 ECO Cooling
Temp
79 / 26 °F range: 50 - 99
°C range: 10
-
37
9 Brightness 80 Value range: 0
-
100
10 Dead band 2 / 1.5 °F range: 2 - 9
°C range: 1.5
-
5
11 Temperature Unit F °F - Fahrenheit
°C
-
Celsius
12 1st Stage
Hysteresis
2 / 1 °F range: 1 - 3
°C range: 0.5
-
1.5
13 2nd Stage
Hysteresis
2 / 1 °F range: 1 - 3
°C range: 0.5
-
1.5
14 3rd Stage
Hysteresis
2 / 1 °F range: 1 - 3
°C range: 0.5 - 1.5
15 Furnace Filter 90 Value range: 0 - 360, step value: 30,
A value of 0 means that the function is
turned off.
16 Recovery 0 0 - not enabled
1
-
enabled
17 Compressor
Protect
5 Value range: 0 - 5 mins
18 Heat Temp Range 90 / 32 °F range: 40 - 90
°C range: 4
-
32