Datasheet

For more Information
please call
1-800-Belden1
Description:
22 AWG stranded (7x30) tinned copper conductors, polyolefin insulation, Beldfoil® shield (100%
coverage), tinned copper drain wire, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material Dia. (in.)
1 22 7x30 TC - Tinned Copper .030
Insulation
Insulation Material:
Insulation Material
PO - Polyolefin
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
20 7x28 TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride
Overall Cabling
Overall Nominal Diameter: 0.196 in.
Pair
Pair Color Code Chart:
Number Color
1 Blue & Orange
Pair Lay Length & Direction:
Lay Length (in.)
1.500
Mechanical Characteristics (Overall)
Operating Temperature Range: -30°C To +105°C
UL Temperature Rating: 105°C
Bulk Cable Weight: 18 lbs/1000 ft.
Max. Recommended Pulling Tension: 27 lbs.
Min. Bend Radius (Install)/Minor Axis: 2.200 in.
Page 1 of 3 03-17-2011
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
3077F Multi-Conductor - DataBus® ISA/SP-50 FOUNDATION Fieldbus Cable

Summary of content (3 pages)