Datasheet
For more Information
please call
1-800-Belden1
General Description:
22 AWG solid bare copper conductors, FRFPE insulation, Beldfoil® (100% coverage) plus a tinned copper
braid shield (65% coverage), sunlight resistant PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material Dia. (in.)
1 22 Solid BC - Bare Copper .026
Total Number of Conductors: 2
Insulation
Insulation Material:
Insulation Material
FRFPE - Flame Retardant Foam Polyethylene
Outer Shield
Outer Shield Material:
Layer # Outer Shield Trade Name Type Outer Shield Material Coverage (%)
1 Beldfoil® Tape Aluminum Foil-Polyester Tape 100
2 Braid TC - Tinned Copper 65
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride
Overall Cable
Overall Nominal Diameter: 0.315 in.
Pair
Pair Color Code Chart:
Number Color
1 Red & Green
Pair Lay Length & Direction:
Lay Length (in.)
2.750
Mechanical Characteristics (Overall)
Operating Temperature Range: -30°C To +75°C
UL Temperature Rating: 60°C
Bulk Cable Weight: 52 lbs/1000 ft.
Max. Recommended Pulling Tension: 50 lbs.
Min. Bend Radius/Minor Axis: 3.200 in.
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CMG, PLTC
CEC/C(UL) Specification: CMG
AWM Specification: UL Style 20201 (600 V 75°C)
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
Page 1 of 3 01-05-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
3079A Multi-Conductor - DataBus® ISA/SP-50 PROFIBUS Cable